3. Instruction Set<br />

‣ Table of settings for the high-speed interrupts of the software counters and software<br />

comparators:<br />

Counter C232 C233 C234 C235 C236 C237<br />

DHSCS High-speed I010 I050 I070 I010 I020 I030<br />

interrupt<br />

High-speed comparator C232~C242 share 6 software comparators<br />

Set<br />

Counter C238 C239 C240 C241 C242<br />

DHSCS High-speed<br />

interrupt<br />

High-speed comparator<br />

Set<br />

I040 I050 I060 I070 I080<br />

C232~C242 share 6 software comparators<br />

‣ <strong>DVP</strong>-<strong>SS2</strong>/<strong>SA2</strong>/SE does not support the software high speed counter C232.<br />

‣ C253 and C254 is <strong>DVP</strong>/SE are software high speed counters. The high-speed interrupt<br />

is I030.<br />

‣ Block diagram of software counters and comparators:<br />

Software<br />

Counter 1<br />

Software<br />

comparatorx 6<br />

Set / reset<br />

1<br />

Software<br />

counter 2<br />

Count value<br />

Set / reset<br />

2<br />

Software<br />

counter 8<br />

Set / reset<br />

6<br />

6. Explanations on hardware comparators DHSCS/DHSCR instruction:<br />

‣ There are 2 groups of hardware comparators provided respectively for 2 groups of<br />

hardware counters (A group and B group), and each group shares 4 comparators with<br />

individual Compare Set/Reset function.<br />

‣ When programming DHSCS and DHSCR instructions, the total of Set/Reset<br />

comparisons for both instructions can not be more than 4, otherwise syntax check error<br />

will occur.<br />

‣ Each high-speed counter interrupt occupies an associated hardware comparator,<br />

consequently the interrupt number can not be repeated. Also, I010~I040 can only be<br />

applied for group A comparators and I050~I080 for group B.<br />

3-125