3. Instruction Set<br />

API Mnemonic Operands Function<br />

46 ANS Timed Annunciator Set<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE<br />

<strong>SX2</strong><br />

Type Bit Devices Word devices Program Steps<br />

OP X Y M S K H KnX KnY KnM KnS T C D E F ANS: 7 steps<br />

S *<br />

m *<br />

D *<br />

PULSE 16-bit 32-bit<br />

<strong>SA2</strong><br />

<strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE<br />

<strong>SA2</strong><br />

SE<br />

<strong>SX2</strong><br />

Operands:<br />

S: Alarm timer m: Time setting D: Alarm<br />

Explanations:<br />

1. ANS instruction is used to drive the output alarm device in designated time.<br />

2. Operand S valid range: T0~T183<br />

Operand m valid range: K1~K32,767 (unit: 100 ms)<br />

Operand D valid range: S912~S1023<br />

3. Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled)<br />

4. See ANR instruction for more information<br />

Program Example:<br />

If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is<br />

reset. (T10 will be reset, present value = 0)<br />

X3<br />

ANS T10 K50 S999<br />

3-111