DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

API Mnemonic Operands Function<br />

40 ZRST P Zone Reset<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Type Bit Devices Word devices Program Steps<br />

OP X Y M S K H KnX KnY KnM KnS T C D E F ZRST, ZRSTP: 5 steps<br />

D 1 * * * * * *<br />

D 2 * * * * * *<br />

Operands:<br />

D 1 : Starting device of the reset range<br />

PULSE 16-bit 32-bit<br />

<strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE<br />

SE<br />

SE<br />

D 2 : End device of the reset range<br />

Explanations:<br />

1. When the instruction is executed, range D 1 to D 2 will be reset.<br />

2. Operand D 1 and D 2 must be the same data type, Valid range: D 1 ≦ D 2<br />

3. When D 1 > D 2 , only operand designated by D 2 will be reset.<br />

4. This instruction is generally used in pulse execution mode (ZRSTP).<br />

Program Example:<br />

1. When X0 = ON, M300 to M399 will be reset.<br />

2. When X1 = ON, C0 to C127 will all be reset, i.e. present value = 0 and associated contact/<br />

output will be reset as well.<br />

3. When X20 = ON, T0 to T127 will all be reset, i.e. present value = 0 and associated contact/<br />

output will be reset as well.<br />

4. When X2 = ON, the steps of S0 to S127 will be reset.<br />

5. When X3 = ON, the data of D0 to D100 will be reset.<br />

6. When X4 = ON, C235 to C254 will all be reset, i.e. present value = 0 and associated contact/<br />

output will be reset as well.<br />

<strong>SX2</strong><br />

X0<br />

X1<br />

X20<br />

X2<br />

X3<br />

X4<br />

ZRST M300 M399<br />

ZRST C0 C127<br />

ZRST T0 T127<br />

ZRST S0 S127<br />

ZRST D0 D100<br />

ZRST C235 C254<br />

Points to note:<br />

1. Bit devices Y, M, S and word devices T, C, D can be individually reset by RST instruction.<br />