3. Instruction Set<br />

API Mnemonic Function<br />

07 WDT P Watchdog Timer Refresh<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE<br />

<strong>SX2</strong><br />

OP Descriptions Program Steps<br />

N/A<br />

WDT, WDTP: 1 step<br />

PULSE 16-bit 32-bit<br />

<strong>SA2</strong><br />

<strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE<br />

<strong>SA2</strong><br />

SE<br />

<strong>SX2</strong><br />

Explanations:<br />

1. WDT instruction can be used to reset the Watch Dog Timer. If the PLC scan time (from<br />

address 0 to END or FEND instruction) is more than 200ms, the ERROR LED will flash. In<br />

this case, users have to turn the power OFF and then ON to clear the fault. PLC will<br />

determine the status of RUN/STOP according to RUN/STOP switch. If there is no<br />

RUN/STOP switch, PLC will return to STOP status automatically.<br />

2. Time to use WDT:<br />

a) When an error occurs in the PLC system.<br />

b) When the scan time of the program exceeds the WDT value in D1000. It can be modified by<br />

using the following two methods.<br />

i. Use WDT instruction<br />

STEP0<br />

WDT<br />

END(FEND)<br />

T1<br />

T2<br />

ii.<br />

Use the set value in D1000 (Default: 200ms) to change the time for watchdog.<br />

Points to note:<br />

1. When the WDT instruction is used it will operate on every program scan as long as its input<br />

condition has been made. To force the WDT instruction to operate for only ONE scan,<br />

users have to use the pulse (P) format of the WDT instruction, i.e. WDTP.<br />

2. The watchdog timer has a default setting of 200ms. This time limit can be customized to<br />

users requirement by editing the content in D1000, the wathdog timer register.<br />

3-55