3. Instruction Set<br />

The opposite diagram E, F index register modification<br />

MOV K20E0 D10F0<br />

E0 = 8 F0 = 14<br />

20 + 8 = 28 10 + 14 = 24<br />

Transmission K28 D24<br />

refers to the content in the operand changes with the<br />

contents in E and F.<br />

For example, E0 = 8 and K20E0 represents constant<br />

K28 (20 + 8). When the condition is true, constant K28<br />

will be transmitted to register D24.<br />

Devices modifiable: P, X, Y, M, S, KnX, KnY, KnM, KnS, T, C, D.<br />

E and F can modify the devices listed above but cannot modify themselves and Kn., e.g. K4M0E0<br />

is valid and K0E0M0 is invalid. Grey columns in the table of operand at the beginning page of each<br />

application instruction indicate the operands modifiable by E and F.<br />

If you need to modify device P, I, X, Y, M, S, KnX, KnY, KnM, KnS, T, C and D by applying E, F, you<br />

have to select a 16-bit register, i.e. you can designate E or F.<br />