17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>SA2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Mnemonic Function Program steps<br />

END Program End 1<br />

<strong>ES2</strong>/<strong>EX2</strong><br />

Controllers<br />

<strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Explanations:<br />

END instruction needs to be connected at the end of program. PLC will scan from address 0 to<br />

END instruction and return to address 0 to scan again.<br />

Mnemonic Function Program steps<br />

NOP No operation 1<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Explanation:<br />

NOP instruction does not conduct any operations in the program, i.e. the operation result remains<br />

the same after NOP is executed. Generally NOP is used for replacing certain instruction without<br />

altering original program length.<br />

Program example:<br />

Ladder Diagram:<br />

X0<br />

NOP instruction will be<br />

omitted in the ladder diagram<br />

NOP<br />

Y1<br />

Instruction: <strong>Operation</strong>:<br />

LD X0 Load NO contact X0<br />

NOP<br />

No operation<br />

OUT Y1 Drive coil Y1<br />

Mnemonic Function Program steps<br />

NP Negative contact to Positive contact 1<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Explanation:<br />

When the conditions preceding NP command change from false to true, NP command (works as<br />

contact A) will be ON for a scan cycle. In the next scan cycle it turns OFF.<br />

Program Example:<br />

Ladder Diagram:<br />

M0 M1<br />

P<br />

Y0<br />

Instruction: <strong>Operation</strong>:<br />

LD M0 Load NO contact M0<br />

AND M1 Connect NO contact M1 in series<br />

NP<br />

Negative contact to Positive contact<br />

OUT Y0 Drive coil Y0<br />

3-10