<strong>DVP</strong>-<strong>ES2</strong>/<strong>SA2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Mnemonic Operands Function Program steps<br />

SET<br />

Y, M, S<br />

Latches the ON<br />

status<br />

1~3<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Explanations:<br />

When the SET instruction is driven, its designated device will be ON and latched whether the SET<br />

instruction is still driven. In this case, RST instruction can be applied to turn off the device.<br />

Program example:<br />

Ladder Diagram:<br />

Instruction:<br />

<strong>Operation</strong>:<br />

X0<br />

Y0<br />

SET<br />

Y1<br />

LD X0 Load NO contact X0<br />

ANI Y0 Connect NC contact Y0 in series<br />

SET Y1 Drive Y1 and latch the status<br />

Mnemonic Operands Function Program steps<br />

RST<br />

Y, M, S, T, C, D, E,<br />

F<br />

Resets contacts,<br />

registers or coils<br />

3<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Explanations:<br />

Device status when RST instruction is driven:<br />

Device<br />

Status<br />

S, Y, M Coil and contact are set to OFF.<br />

T, C Current value is cleared. Associated contacts or coils are reset .<br />

D, E, F The content is set to 0.<br />

Status of designated devices remains the same when RST instruction is not executed.<br />

Program example:<br />

Ladder diagram:<br />

X0<br />

RST<br />

Y5<br />

Instruction: <strong>Operation</strong>:<br />

LD X0 Load NO contact X0<br />

RST Y5 Reset contact Y5<br />

Mnemonic Operands Function Program steps<br />

Master control<br />

MC/MCR N0~N7<br />

3<br />

Start/Reset<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE <strong>SX2</strong><br />

Explanations:<br />

MC is the master-control start instruction. When MC instruction executes, the program execution<br />

turns to the designated nest level and executes the instructions between MC and MCR. However,<br />

MCR is the master-control reset instruction placed at the end of the designated nest level and no<br />

drive contact is required before MCR. When MC/MCR is not active, devices and instructions<br />

3-8