<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

a) When X0 (counter input) and X1 (external Interrupt) correspondingly work together with C243,<br />

and I100/I101, PLC will move the count value to D1241 and D1240.<br />

b) When X0 (counter input) and X4 (external Interrupt) correspondingly work together with C246,<br />

C248, C252 and I400/I401, PLC will move the count value to D1241 and D1240<br />

c) When X2 (counter input) and X3 (external Interrupt) correspondingly work together with C244,<br />

and I300/I301, PLC will move the count value to D1243 and D1242.<br />

d) When X2 (counter input) and X5 (external Interrupt) correspondingly work together with C250,<br />

C254 and I500/I501, PLC will move the count value to D1243 and D1242.<br />

Example:<br />

I101<br />

M1000<br />

M1000<br />

DCNT C243 K100<br />

DMOV D1240 D0<br />

EI<br />

FEND<br />

IRET<br />

END<br />

When external interrupt (X 1, I101) occurs duri ng counti ng process of C243, the count value<br />

in<br />

C243 will be stored in (D1241, D1240) and C243 is reset. Af ter this, the interrupt subroutine I101<br />

will be executed<br />

Function Group<br />

Enabling force-ON/OFF of input point X<br />

Number<br />

M1304<br />

Contents:<br />

When M1304 = ON, WPLSoft or ISPSoft can set ON/OFF of input pont X, but the associated<br />

hardware LED will not respond to it.<br />

Function Group Output specified pulses or seek Z phase signal when zero point is achieved.<br />

Number<br />

M1308, D1312<br />

Contents:<br />

When zero point is achieved, PLC can output specified pulses or seek Z phase signal by this<br />

function. Input terminals X2, X3 are the Z-phase signal input point of CH1, CH2. When M1308= ON,<br />

D1312 is the setting register to specify the additional pulses within the range -30,000~30,000.<br />

Specified value exceeds the ra nge will be changed as the max/min value automatically. When<br />

D1312 is set to 0, the additional pulses output function will be disabled.<br />

Functions of other input terminals:<br />

X4 → CH1 DOG signal input<br />

X6 → CH2 DOG signal input<br />

X5 → CH1 LSN signal input<br />

X7 → CH2 LSN signal input<br />

2-72