2. Programming Concepts<br />

D1140: Number of r ight-side modules (AIO, PT, TC, etc.), max. 8 modules can be connected.<br />

D1142: Number of input points (X) on DIO modules.<br />

D1143: Number of output points (Y) on DIO modules.<br />

D1145: Number of left-side modules (AIO, PT, TC, etc.), max. 8 modules can be connected.<br />

(Only applicable<br />

for <strong>SA2</strong>/<strong>SX2</strong>).<br />

Function Group Reverse Interrupt Trigger Pulse Direction<br />

Number<br />

M1280, M1284, M1286<br />

Contents:<br />

1. The falgs should be used with EI instruction and should be inserted before EI instruction<br />

2. The default setting of interrupt I101 (X0) is rising-edge triggered. If M1280 is ON and EI<br />

ins truction is executed, PLC will reverse the trigger direction as falling-edge triggered. The<br />

trigger pulse direction of X1 will be set as rising-edge again by resetting M1280.<br />

3. Wh en M0 = OFF, M1280 = OFF. X0 external interrupt will be triggered by rising-edge pulse.<br />

4. Wh en M0 = ON, M1280 = ON. X0 external interrupt will be triggered by falling-edge pulse.<br />

Users do not have to change I101 to I000.<br />

M0<br />

OUT<br />

M1280<br />

EI<br />

FEND<br />

I001<br />

M1000<br />

INC<br />

D0<br />

IRET<br />

END<br />

Function Group<br />

Number<br />

Stores Value of High-speed Counter when Interrupt Occurs<br />

D1240~D1243<br />

Contents:<br />

1. If extertal interrupts are applied on input points for Reset, the interrupt instructions have the<br />

priority in using the input points. In addition, PLC will move the current data in the counters to<br />

the associated data registers below then reset the counters.<br />

Special D D1241, D1240 D1243, D1242<br />

Counter C243 C246 C248 C252 C244 C250 C254<br />

Interrupt signal X1(I100/I101) X4(I400/I401) X3(I300/I301) X5(I500/I501)<br />

2. Function:<br />

2-71