<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Vbase T1 T2+T3 P(1) V(1) P(2) V(2)<br />

Initial<br />

frequency<br />

Ramp-up<br />

time<br />

Rampdown<br />

time<br />

Position of the<br />

first speed<br />

The first<br />

speed<br />

Position of<br />

the second<br />

speed<br />

The<br />

second<br />

speed<br />

Function Group<br />

Number<br />

Contents:<br />

Program Execution Error<br />

M1067~M1068, D1067~D1068<br />

Device Explanation Latched STOP→RUN RUN→STOP<br />

M1067 Program execution error None Clear Unchanged<br />

M1068 Execution error locked None Unchanged Unchanged<br />

D1067 Error code for program execution None Clear Unchanged<br />

D1068<br />

Address of program execution<br />

error<br />

None Unchanged Unchanged<br />

Error code explanation:<br />

D1067 error code<br />

Function<br />

0E18 BCD conversion error<br />

0E19 Divisor is 0<br />

0E1A Use of device exceeds the range (including E, F index register modification)<br />

0E1B Square root value is negative<br />

0E1C FROM/TO instruction communication error<br />

Function Group I/O Modules Detection<br />

Number<br />

D1140, D1142, D1143, D1145<br />

Contents:<br />