17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Current<br />

Temperature<br />

Analog input mode Upper limit value Lower limit value<br />

-20 mA~+20 mA +32384 -32384<br />

+4 mA~+20 mA +32384<br />

-384<br />

PT100/PT1000 +8100 -1900<br />

NI100/NI1000 +1800 -900<br />

Device<br />

number<br />

D1115<br />

Function<br />

20<strong>EX2</strong>/<strong>SX2</strong> analog input/output mode setting (Default=<br />

H’0)<br />

bit0~bit5: Selection between the voltage/current mode ( 0: Voltage; 1: Current;<br />

Defa ult: Voltage)<br />

bit0~ bit3: Analog inputs (AD0~AD3)<br />

bit4~ bit5: Analog outputs (DA0~ DA1)<br />

bit8~bit 13: Current mode<br />

bit8~bit11: AD0~AD 3 (0: -20 mA ~20 mA; 1: 4~20 mA)<br />

bit12~bit13: DA0~DA1 (0: 0~20 mA; 1: 4~20 mA)<br />

30<strong>EX2</strong> analog input/output mode setting (Default=H’FFFF)<br />

The description of D1115 for 30<strong>EX2</strong>:<br />

Bit15~12 Bit11~8 Bit7~4 Bit3~0<br />

Analog output Analog input Analog input Analog input<br />

mode of DA0 mode of AD2 mode of AD1 mode of AD0<br />

The analog input modes for 30<strong>EX2</strong>:<br />

Code 0x0 0x1 0x2 0x3<br />

De scription Tow-wire PT100 Three-wire NI100 Two-wire PT1000 Two-wire NI1000<br />

Code 0x4 0x5 0x6 0x7<br />

Description Three-wire PT100 Three-wire NI100 Three-wire PT1000 Three-wire NI1000<br />

Code 0x8 0x9 0xA 0xB<br />

Description<br />

Voltage: Voltage: Voltage:<br />

Current:<br />

-10 V~+10 V -5 V~+5 V +1 V~+5 V -20 mA~+20 mA<br />

Code 0xC 0xD 0xE 0xF<br />

Description<br />

Current:<br />

+4 mA~+20 mA<br />

Reserved<br />

Unused<br />

T he analog output modes for 30<strong>EX2</strong>:<br />

Code 0x0 0x1 0x2 0xF<br />

De scription<br />

Voltage:<br />

Current:<br />

Current:<br />

-10 V~+10 V +0 mA~+20 mA +4 mA~+20 mA<br />

U nused<br />

The example of setti ng D1115 for 30<strong>EX2</strong>:<br />

If the analog input mo de of AD0 is the two-wire NI100, the analog input mo de of AD1 is the<br />

three-wire 1000, the analog input mode of AD2 is the voltage mod e (+1 V~ +5 V), and the<br />

analog output mode of DA0 is the curren t mode (+4 mA ~ +20 mA), the setting value in<br />

D 1115 is H’2A61.<br />

2-68

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!