07.03.2014 Views

Flowlink 5.1 Software Instruction Manual - Isco

Flowlink 5.1 Software Instruction Manual - Isco

Flowlink 5.1 Software Instruction Manual - Isco

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Isco</strong> <strong>Flowlink</strong> <strong>5.1</strong> ® <strong>Software</strong><br />

Site Window - 4100/4200/6700<br />

Time Table<br />

Conditions<br />

Parentheses and<br />

Order of Execution<br />

Time table conditions are satisfied when the instrument’s<br />

internal clock is within the defined duration of time. An example<br />

of a Daily Time table condition would read “starting Daily at<br />

08:00:00, stopping Daily at 17:00:00.”<br />

As many as four times can be entered, using any combination of<br />

time table types. For example, to enable a function every Monday,<br />

Wednesday, and Friday, three weekly start/stop times would be<br />

defined in the time table. The three lines would possibly read<br />

“Starting Monday at 08:00:00, Stopping at Monday 17:00:00;<br />

Starting Wednesday at 08:00:00, Stopping Wednesday at<br />

17:00:00; and Starting Friday at 08:00:00, Stopping Friday at<br />

17:00:00.”<br />

To define the time table<br />

1. Select the type of time table. The options are:<br />

• Specific – Start/stop dates and times for one-time<br />

use.<br />

• Weekly – Start/stop days of week and times,<br />

recurring weekly.<br />

• Daily – Start/stop times, recurring daily.<br />

• Mon-Fri – Start/stop times, recurring each day of the<br />

workweek.<br />

2. Complete the Start and Stop fields. The resulting<br />

duration will be displayed in the text box below the entry<br />

fields.<br />

3. To define additional start/stop times, click Add and<br />

repeat the steps above.<br />

Note: Start/stop times can be deleted by highlighting the<br />

line in the text box and clicking Remove.<br />

4. Click Accept. The time table is defined and ready for use<br />

in an equation.<br />

<strong>Flowlink</strong> provides parentheses so that you can group conditions<br />

or even combine groups with logical operators. Parentheses also<br />

let you control the order in which the flow meter evaluates the<br />

conditions in an equation. The instrument will use an algebraic<br />

order of execution when evaluating a trigger equation. The order<br />

of execution is the order in which the instrument tests conditions<br />

and can be summarized as: “from left to right, and from inside,<br />

out.” “From left to right” means that the flow meter tests<br />

conditions in the same order that you read them in an equation:<br />

from left to right.<br />

When evaluating an equation containing two conditions, the<br />

instrument first checks the condition on the left, then the<br />

condition on the right, and finally evaluates the conditions with<br />

regard to the logical operators used to combine them. If the<br />

equation is true, the instrument triggers the designated action.<br />

Equations using three or more conditions are also evaluated from<br />

left to right. Consider the two equations that follow. Both<br />

97

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!