Blitzschutz/Erdung<br />

Montageanleitung<br />

HVI ® power<br />

HVI ® power long<br />

DE GB<br />

www.dehn.de<br />

Publication No. 1829 / Update 07.13 Id No. 067426 © Copyright 2013 <strong>DEHN</strong> + SÖHNE


INHALTSVERZEICHNIS<br />

1. Anwendung HVI ® power-Leitung.................................................................................. 4<br />

2. Sicherheitshinweise...................................................................................................... 4<br />

3. Spezifikation der HVI ® power-Leitung.......................................................................... 6<br />

3.1 Aufbau der HVI ® power-Leitung.................................................................................... 6<br />

3.2 Technische Daten.......................................................................................................... 7<br />

3.3 Chemische Eigenschaften............................................................................................. 7<br />

4. Verfügbare Varianten.................................................................................................... 8<br />

4.1 HVI ® power-Leitung vorkonfektioniert.......................................................................... 8<br />

4.2 HVI ® power-Leitung zur Anbindung an Blitzspannung behaftete Anlagenteile.......... 10<br />

4.3 HVI ® power long - Trommelware................................................................................. 11<br />

4.4 Benötigtes Zubehör, Werkzeuge und Montageteile................................................... 12<br />

4.5 HVI ® power-Leitung Stützrohrinnenverlegung............................................................ 14<br />

5. Konfektionierung der HVI ® power-Leitung................................................................. 15<br />

5.1 Ablängen und Absetzen der HVI ® power-Leitung........................................................ 15<br />

5.2 Montage von Kopfstück bzw. Anschlusselement........................................................ 16<br />

5.3 Umschrumpfen............................................................................................................ 17<br />

6. Montage..................................................................................................................... 18<br />

6.1 Montage der HVI ® power-Leitung im Stützrohr.......................................................... 18<br />

6.2 Endverschluss............................................................................................................. 20<br />

6.2.1 Bereich des Endverschlusses am Stützrohr am Beispiel einer Antennenanwendung.....................20<br />

6.2.2 Variabler Endverschluss.............................................................................................................23<br />

6.2.3 Endverschluss an einer Gebäudestruktur...................................................................................26<br />

6.3 Verlegung der HVI ® power-Leitung............................................................................. 27<br />

6.4 Montage unter Berücksichtigung der Windzone / Windgeschwindigkeit................... 28<br />

2


7. Checkliste für HVI ® Installation.................................................................................. 30<br />

3


1. Anwendung HVI ® power-Leitung<br />

Um gefährliche Überschläge zwischen Teilen des äußeren Blitzschutzes und inneren Installationen,<br />

z.B. leitfähigen Teilen (Elektroanlage, Rohrleitungen, usw.) zu verhindern, ist die Einhaltung des<br />

Trennungsabstandes "s" bei der Errichtung von Blitzschutzsystemen zwingend erforderlich.<br />

Hohe Impulsspannungen verursachen ohne zusätzliche Maßnahmen Überschläge an Isolierstoffoberflächen.<br />

Dieser Effekt ist als Gleitüberschlag bekannt. Wird die sogenannte Gleitentladungs-Einsetzspannung<br />

überschritten, wird eine Oberflächenentladung initiiert, die problemlos eine Strecke von einigen<br />

Metern überschlagen kann. Um Gleitentladungen zu vermeiden, ist die HVI ® power-Leitung mit<br />

einem äußeren Spezialmantel ausgestattet, der es ermöglicht, hohe Blitz-Impulsspannungen gegen ein<br />

Bezugspotential abzusteuern. Funktionsbedingt wird dazu im Bereich des Endverschlusses eine Verbindung<br />

zwischen dem äußeren halbleitenden Mantel und dem Potentialausgleich des Gebäudes (nicht<br />

Blitzspannung behaftet) geschaffen. Dieser Anschluss an den Funktionspotentialausgleich kann z.B.<br />

an metallene, geerdete Dachaufbauten die im Schutzbereich der Blitzschutzanlage liegen, an geerdete<br />

Teile der Gebäudekonstruktion die nicht mit Blitzspannung behaftet sind oder an den Schutzleiter des<br />

Niederspannungssystems erfolgen.<br />

Im sensiblen Bereich des Endverschlusses dürfen sich im Abstand des Trennungsabstandes "s" keine<br />

elektrisch leitfähigen bzw. geerdeten Teile befinden.<br />

2. Sicherheitshinweise<br />

ÂÂDie Montage der HVI ® power-Leitungen ist grundsätzlich nur im Rahmen der in dieser Montageanleitung<br />

genannten Vorgaben und Bedingungen zulässig.<br />

ÂÂDie Montagearbeiten zur Verlegung der HVI ® power-Leitungen dürfen nur durch ein qualifiziertes,<br />

geschultes Fachpersonal (Blitzschutz-Fachkraft) durchgeführt werden. Wir empfehlen<br />

eine spezielle Schulung zu den HVI ® Produkten bei <strong>DEHN</strong>+SÖHNE (zu finden unter<br />

http://www.dehn.de/de/dehnacademy) durchzuführen.<br />

ÂÂBei erkennbaren bzw. herannahenden Gewittertätigkeiten sind die Montagearbeiten aus Sicherheitsgründen<br />

zu unterbrechen.<br />

Die erhältlichen Komponenten des HVI ® power-Systemes sind als Gesamtsystem abgeprüft worden.<br />

Eine Mischung mit Bauteilen oder jeglicher Komponenten anderer Hersteller ist nicht zulässig.<br />

4


ÂÂVor der Montage sind die HVI ® power-Leitungen auf ordnungsgemäßen Zustand zu kontrollieren.<br />

Sollte eine Beschädigung oder ein sonstiger Mangel festgestellt werden, dürfen die<br />

HVI ® power-Leitungen nicht montiert werden. Der schwarze Mantel der HVI ® power-Leitung darf<br />

grundsätzlich keine Druck- und Schnittverletzungen aufweisen.<br />

ÂÂBei der Montage der HVI ® power-Leitungen müssen bei entsprechenden Anwendungen die Si cherheitsvorkehrungen<br />

gegen Brand- und Explosionsgefahren berücksichtigt werden.<br />

ÂÂSoll die HVI ® power-Leitung auf weich gedeckten Dächern (z.B. Reet, Stroh) eingesetzt werden,<br />

sind für diese feuergefährdeten Betriebsstätten besondere Montagebedingungen einzuhalten. Die<br />

besonderen Montagebedingungen sind für die HVI-Leitung im EB-Hauptkatalog Blitzschutz/Erdung<br />

(HVI-Blitzschutz an Weichdächern) enthalten und sind analog auf die Montage der HVI ® power-Leitung<br />

anzuwenden.<br />

ÂÂWird das Stützrohr durch ein Dach eingeführt, ist eine fachgerechte Abdichtung und bei einem<br />

Warmdach zusätzlich eine fachgerechte Dämmung zu realisieren.<br />

ÂÂDie HVI ® power-Leitung ist geeignet für Außenverlegung und kann nach dem Endverschluss, z.B.<br />

auf Dächern, in Wänden, unter Putz, im Beton oder Fas sa den/Fassadenkonstruktionen verlegt werden.<br />

Die Leitung ist jedoch nicht für dauernde Was se reinwirkung geeignet. Eine Verlegung der<br />

HVI ® power-Leitung mit schwarzem Mantel im Erdreich ist unzulässig.<br />

ÂÂBei Verschmutzung der HVI ® power-Leitung kann diese durch einen mit dem Spezialreiniger,<br />

Art.-Nr. 297 199, getränkten Lappen gereinigt werden. Aus gefahrgutrechtlichen Gründen ist ein<br />

Versand dieses Spezialreinigers nur in Deutschland und Österreich möglich. Alternativ ist ISOPRO­<br />

PYLALCOHOL 99,1 bis 99,9 % (CSA-Nr. 67-63.0) zu verwenden!<br />

ÂÂDurch den speziellen Aufbau des Außenmantels der HVI ® power-Leitung ist grundsätzlich ein Anstrich<br />

unzulässig.<br />

ÂÂDie HVI ® power-Leitung ist ein Bauteil zur Einhaltung des Trennungsabstandes. Konstruktionsbedingt<br />

besitzt diese keine magnetische Schirmwirkung. Induktionswirkungen in sekundären Leitungen/Schleifen<br />

sind zu beachten. Gegebenenfalls sind Maßnahmen zum Überspannungsschutz vorzusehen.<br />

ÂÂBitte wenden Sie sich bei anwendungstechnischen Fragen an das für Sie zuständige Vertriebsteam<br />

oder den Außendienst-Mitarbeiter in Ihrer Region.<br />

  Die Montage in Ex-Bereichen ist aktuell für die HVI ® power-Leitung noch nicht abgeprüft und somit<br />

bis auf Weiteres nicht freigegeben.<br />

5


3. Spezifikation der HVI ® power-Leitung<br />

3.1 Aufbau der HVI ® power-Leitung<br />

Die HVI ® power-Leitung ist eine hochspannungsfeste, isolierte Ableitung mit einem halbleitenden<br />

Außenmantel (siehe Bild 1).<br />

Typisch ist die Anwendung als isolierte Ableitung im Blitzschutz zur Beherrschung des Trennungsabstandes<br />

nach DIN EN 62305-3 (VDE 0185-305-3). Zuerst ist die Berechnung des Trennungsabstandes “s”,<br />

wie in der Norm DIN EN 62305-3 (VDE 0185-305-3) Blitzschutz Teil 3, Abschnitt 6.3 erläutert, mit<br />

dem Ma te ri al faktor k m<br />

= 1 für Luft oder k m<br />

= 0,5 für festen Baustoff durchzuführen. Es muss geprüft<br />

werden, ob dieser errechnete Trennungsabstand mit dem äquivalenten Trennungsabstand der<br />

HVI ® power-Leitung (siehe technische Daten, Tabelle 1 und Seite 7) realisiert werden kann:<br />

errechneter Trennungsabstand ≤ äquivalenter Trennungsabstand.<br />

Ist dies nicht der Fall, dann sind die im Kapitel 6.2 auf Seite 20 beschriebenen Maßnahmen notwendig.<br />

Die Länge für die Berechnung des Trennungsabstandes “s” muss vom Kopfstück bis zur nächsten<br />

Ebene des Blitzschutz-Potentialausgleiches, z.B. Erdungsanlage, gemessen werden.<br />

Bei einer Ableitung k c =1 können somit je nach Schutzklasse des Blitschutzsystems (LPS) folgende maximale<br />

Leitungslängen realisiert werden:<br />

LPS I max. 11,25 m<br />

LPS II max. 15,0 m<br />

LPS III max. 22,5 m<br />

Halbleitender Außenmantel<br />

(Äußerer Halbleiter, schwarz)<br />

Isolationsschicht<br />

Glättungsbelag<br />

Cu-Leiter mehrdrähtig<br />

25 mm²<br />

Bild 1<br />

Aufbau der HVI ® power-Leitung<br />

6


3.2 Technische Daten<br />

Außenmantel schwarz, RAL 9011<br />

Äquivalenter<br />

Trennungsabstand der<br />

HVI ® power-Leitung<br />

Außendurchmesser<br />

minimaler Biegeradius<br />

Luft<br />

festen Baustoff<br />

Dauertemperaturbereich (bei fester Verlegung)<br />

≤ 0,9 m<br />

≤ 1,8 m<br />

27 mm<br />

270 mm<br />

-30° bis +70°C<br />

Umgebungstemperatur und Leitungstemperatur<br />

bei Verlegung und Verarbeitung<br />

max. Zugbelastung<br />

Innenleiter Kupfer mehrdrähtig<br />

-5° bis +40°C<br />

1.200 N<br />

25 mm²<br />

Tabelle 1<br />

Technische Daten HVI ® power-Leitung<br />

3.3 Chemische Eigenschaften<br />

Halogenfreiheit<br />

Brandverhalten<br />

Witterungsbeständig (UV-Beständig)<br />

Brandlast<br />

Weichmacher<br />

ja<br />

nicht selbstverlöschend<br />

ja<br />

6,4 kWh/m<br />

keine<br />

Tabelle 2<br />

Chemische Eigenschaften HVI ® power-Leitung<br />

7


4. Verfügbare Varianten<br />

Das Bauteileprogramm HVI ® power-Leitung-System besteht aus der HVI ® power-Leitung und einem<br />

auf diese Leitung abgestimmten Programm mit Anschluss- und Befestigungselementen. Bei<br />

der Planung und Anwendung der HVI ® power-Leitung sind besondere Kenntnisse erforderlich. Die<br />

HVI ® power-Leitung ist als werksseitig vorkonfektionierte Leitung oder als 100m Trommelware mit<br />

der Bezeichnung HVI ® power long verfügbar. Ergänzende Hinweise über das Bauteileprogramm des<br />

HVI ® power-Leitung-System können aus unseren Druckschriften DS.-Nr. 0210 und DS.-Nr. 0212, unserem<br />

Hauptkatalog Blitzschutz/Erdung oder unter www.dehn.de - Produktdaten entnommen werden.<br />

Grundsätzlich können alle HVI ® power-Leitungen gekürzt, jedoch nicht verlängert werden!<br />

4.1 HVI ® power-Leitung vorkonfektioniert<br />

Generell ist bei der vorkonfektionierten HVI ® power-Leitung werksseitig ein Leitungsende, wie in<br />

Tabelle 3, Seite 9 und Tabelle 4, Seite 10 dargestellt, mit entsprechender Anschlusstechnik vorkonfektioniert.<br />

Damit ist das Kopfstück fest montiert und bereits umschrumpft. Das zweite Leitungsende<br />

kann im Bedarfsfall noch gekürzt werden, um das lose mitgelieferte Anschlusselment entsprechend<br />

des Aufbaues der Anlage genau zu positionieren.<br />

Bei Bestellung der HVI ® power-Leitung ist die Leitungs-/Mindestlänge zu beachten / anzugeben. Diese<br />

Angabe ist bindend und folglich kann auf Grund der auftragsbezogenen Fertigung (Konfektionierung<br />

der Leitungslänge) die Leitung nicht zurückgenommen werden. Die vorkonfektionierte HVI ® power-Leitung<br />

ist in einer Standard-/Mindestlänge von 6 m verfügbar und kann mit 0,5 m-Schritten<br />

erhöht werden. Die Standardmindestlänge von 6 m ist für den Einsatz in Kombination mit dem 3,5 m<br />

langen Stützrohr ausgelegt. Für das Stützrohr mit 5 m Länge wird eine Mindestleitungslänge von 8 m<br />

empfohlen.<br />

Es wird lose beiliegend ein Anschlusselement, ein Schrumpfschlauch und ein Innensechskantschlüssel<br />

mitgeliefert (siehe auch Tabelle 3).<br />

Das Ablängen / Kürzen der HVI ® power-Leitung sollte mit speziellem Werkzeug (HVI ® cutter<br />

und HVI ® strip 27) und das spätere Anbringen des Anschlusselementes bzw. Schrumpfschlauches, unter<br />

Berücksichtigung der beschriebenen Anschlusstechnik, durchgeführt werden (siehe hierzu Kapitel<br />

5 ab Seite 15).<br />

8


HVI ® power-Leitung<br />

vorkonfektioniert<br />

Art.-Nr. Standard-/Mindestlänge Lieferumfang<br />

Varianten 819 160 6 m + x m<br />

(max. 22,5m bei kc = 1)<br />

• 1 Kopfstück werkseitig montiert und<br />

umschrumpft.<br />

• 1 Anschlusselement, 1 Schrumpfschlauch<br />

und 1 Innensechskantschlüssel<br />

lose beigelegt.<br />

Einsatzbereich<br />

Wird verwendet, wenn die Fangeinrichtung des Äußeren Blitzschutzes direkt mit der<br />

Erdungsanlage verbunden wird, z.B. Getrennte Fangeinrichtung an Mobilfunk-Antennen<br />

- Stützrohrinnenverlegung (siehe hierzu Bild 8, Seite 25 und Bild 9, Seite 26).<br />

Kopfstück montiert<br />

Kopfstück und HVI ® power-Leitung<br />

umschrumpft<br />

HVI ® power-Leitung mit Spezialmantel<br />

Lose beigelegt sind:<br />

- Anschlusselement<br />

- Schrumpfschlauch<br />

- Innensechskantschlüssel<br />

Tabelle 3<br />

HVI ® power-Leitung werkseitig vorkonfektioniert - Übersicht<br />

9


4.2 HVI ® power-Leitung zur Anbindung an Blitzspannung behaftete Anlagenteile<br />

Bei Anbindung der vorkonfektionierten HVI ® power-Leitung an Blitzspannung behaftete Anlagenteile<br />

(siehe Kapitel 6.2 auf Seite 20 und Kapitel 6.3 auf Seite 27) muss ein zweiter Endverschluss berücksichtigt<br />

werden. Hierzu muss ein PA-Anschlusselement (Art.-Nr. 410 239) oder ein Variables Dreibeinstativ<br />

mit PA-Element (Art.-Nr. 105 279) separat bestellt werden.<br />

HVI ® power-Leitung Art.-Nr. Standard-/<br />

Mindestlänge<br />

Varianten 819 160 6 m + x m<br />

(max. 22,5m, bei<br />

k c = 1)<br />

Lieferumfang<br />

• HVI ® power-Leitung vorkonfektioniert<br />

• 1 Kopfstück werksseitig montiert und umschrumpft.<br />

• 1 Anschlusselement, 1 Schrumpfschlauch und<br />

1 Innensechskantschlüssel lose beigelegt.<br />

410 239 PA-Anschlusselement<br />

oder 105 279 Variables Dreibeinstativ mit PA-Element<br />

Einsatzbereich<br />

Wird eingesetzt, wenn z.B. mehrere zu schützende Anlagenteile nicht einzeln, sondern<br />

gemeinsam über eine "Getrennte Ringleitung" mit der Erdungsanlage des<br />

Gebäudes verbunden werden (siehe Kapitel 6.2 auf Seite 20). Die Leitung mit<br />

einem im Stützrohr angebrachten Endverschluss und einem vor Ort zu erstellenden<br />

Endverschluss wird typisch dort verwendet, wo die Gesamtleitungslänge nicht<br />

während der Anlagenplanung exakt bestimmt werden kann.<br />

Kopfstück montiert<br />

HVI ® power-Leitung<br />

mit Spezialmantel<br />

Kopfstück und HVI ® -Leitung<br />

umschrumpft<br />

Lose beigelgt sind:<br />

- Anschlusselement<br />

- Schrumpfschlauch<br />

- Innensechskantschlüssel<br />

Separat bestellt werden muss:<br />

- PA-Anschlusselement<br />

oder<br />

- Variables Dreibeinstativ mit<br />

PA-Element<br />

Tabelle 4<br />

HVI ® power-Leitung zur Anbindung an Blitzspannung behaftete Anlagenteile - Übersicht<br />

10


4.3 HVI ® power long - Trommelware<br />

Im Auslieferungszustand ist die HVI ® power long-Leitung auf einer Einwegtrommel aufgerollt.<br />

Zu beachten ist, dass im Lieferumfang das zur Montage zwingend benötigte Anschluss-Set nicht enthalten<br />

ist. Folglich muss das Anschluss-Set und ebenso je nach Bedarf, Art und Aufbau der Anlage das<br />

bzw. die benötigten PA-Anschlusselemente separat dazu bestellt werden (siehe Tabelle 5).<br />

Allgemeines Zubehör und Werkzeuge können aus der Tabelle 6 ab Seite 12 entnommen werden.<br />

HVI ® power long Art.-Nr. Länge Lieferumfang Einsatzbereich<br />

819 137 100 m Einwegtrommel mit<br />

Außen- Ø: ca. 900 m<br />

Breite: ca. 474 mm<br />

inkl:<br />

1 Inbus-Schlüssel<br />

1 Montageanleitung<br />

Zur Konfektionierung vor Ort.<br />

819 142 Anschluss-Set:<br />

1 Kopfstück<br />

1 Anschlusselement<br />

2 Schrumpfschläuche<br />

Kopfstück und Anschlusselement<br />

zum Anschließen an die beiden<br />

Enden der HVI ® power-Leitung<br />

410 239 PA-Anschlusselement PA-Anschlusselement Ø 27 mm<br />

zum Absteuern des elektrischen<br />

Feldes im Bereich Endverschluss.<br />

Wird für den Endverschluss benötigt.<br />

105 279 Variables Dreibeinstativ<br />

mit PA-Element für<br />

den Endverschluss, einstellbare<br />

Höhe von 610<br />

bis 1095 mm (Betonsockel-Oberkante)<br />

Tabelle 5<br />

HVI ® power long - Trommelware und benötigtes Zubehör<br />

11


4.4 Benötigtes Zubehör, Werkzeuge und Montageteile<br />

Für die Montage der HVI ® power-Leitungen stehen nachfolgende Montageteile und Werkzeuge zur<br />

Verfügung:<br />

Art.-Nr. Lieferumfang Beschreibung<br />

819 142 Anschluss-Set:<br />

1 Kopfstück<br />

1 Anschlusselement<br />

2 Schrumpfschläuche<br />

275 240 Metallleitungshalter<br />

HVI ® power-Leitung<br />

Kopfstück und Anschlusselement zum Anschließen an<br />

die beiden Enden der HVI ® power-Leitung.<br />

Leitungshalter NIRO Ø 27 - 30 mm<br />

Gewinde M8<br />

275 249 Metallleitungshalter<br />

HVI ® power-Leitung<br />

Leitungshalter NIRO Ø 27 - 30 mm<br />

Gewinde M8 mit Kunststoffsockel<br />

275 241 Metallleitungshalter<br />

HVI ® power-Leitung<br />

Leitungshalter NIRO Ø 27 - 30 mm<br />

Gewinde M6<br />

275 242 Metallleitungshalter<br />

HVI ® power-Leitung<br />

Leitungshalter NIRO Ø 27 - 30 mm<br />

Langloch Ø 5,5 x 10 mm<br />

410 239 PA-Anschlusselement PA-Anschlusselement Ø 27 mm zum Absteuern des<br />

elektrischen Feldes im Bereich Endverschluss.<br />

Wird für jeden Endverschluss benötigt.<br />

597 227 HVI ® strip 27 Abisolierwerkzeug für mehrdrähtige<br />

Leitungen Ø 27 mm.<br />

Bestehend aus Handgriff und Schneidkopf<br />

597 127 HVI ® head 27 Schneidkopf Ø 27 mm<br />

für Abisolierwerkzeug HVI ® strip 27<br />

12


Art.-Nr. Lieferumfang Beschreibung<br />

597 032 HVI ® cutter Kabelschere zum Ablängen der HVI ® power-Leitung<br />

253 334 Flachdachhalter-SET zum Verlegen der Leitung auf Flachdächern<br />

Gewicht 8,5 kg<br />

202 857 Steildachhalter Strebe mit vorgeformten Biegestellen zum Verlegen<br />

der HVI ® power-Leitung auf Steildächern<br />

459 200 Trennklemme Rd/Rd<br />

Rd/Fl<br />

Trennklemme NIRO 8 - 10 / 8 - 10 mm mit Zwischenplatte<br />

für zwei Rundleiter oder 8 - 10 / 30 mm für<br />

Rund- und Flachleiter<br />

(200 kA für LPS I)<br />

105 279 Variables Dreibeinstativ mit<br />

PA-Element<br />

zum Erstellen des Endverschlusses<br />

105 344 Wandhalter für Stützrohr Wandbefestigungswinkel mit Verstellbereich<br />

von 150 - 200 mm<br />

105 160 Befestigungsschelle<br />

mit Spannband<br />

Klemmbereich 50 - 300 mm<br />

253 333 Flachdachhalter-SET zum Verlegen der Leitung auf Flachdächern<br />

Gewicht 4,6 kg<br />

Tabelle 6<br />

Zubehör und Werkzeug<br />

13


4.5 HVI ® power-Leitung Stützrohrinnenverlegung<br />

Bei den verwendeten Stützrohren für die Stützrohrinnenverlegung der HVI ® power-Leitung ist ein<br />

PA-Element in Form einer Federkontaktierung integriert.<br />

Der Stützrohrkopf ist in sich mechanisch geschlossen und daher wasserundurchlässig.<br />

Eine Überspannung von mehreren Stützrohren zur Stromaufteilung mittels Seilen ist aus statischen<br />

Gründen nur beschränkt möglich! Bitte kontaktieren Sie ggfs. für nähere Informationen das Werk.<br />

Für die Montage zur Stützrohrinnenverlegung der HVI ® power-Leitungen stehen unterschiedliche<br />

Stützrohrvarianten zur Verfügung (siehe nachfolgenden Tabelle 7:<br />

Art.-Nr.<br />

gebündelt,<br />

bestehend aus:<br />

Bauteillänge<br />

Gesamtlänge<br />

Mindestlänge<br />

HVI®power-<br />

Leitung<br />

105 320 Stützrohr 3,5 m 4,5 m 6 m + x m<br />

Fangspitze Ø 10 mm<br />

1,0 m<br />

105 321 Stützrohr 3,5 m 6,0 m 6 m + x m<br />

Fangstange Ø 22/16/10 mm<br />

2,5 m<br />

105 322 Stützrohr<br />

Fangspitze Ø 10 mm<br />

5,0 m<br />

1,0 m<br />

6,0 m 6 m + x m<br />

(empfohlene<br />

Mindestlänge<br />

8m)<br />

105 323 Stützrohr<br />

Fangstange Ø 22/16/10 mm<br />

5,0 m<br />

2,5 m<br />

7,5 m 6 m + x m<br />

(empfohlene<br />

Mindestlänge<br />

8m)<br />

Tabelle 7<br />

Stützrohrvarianten<br />

14


5. Konfektionierung der HVI ® power-Leitung<br />

5.1 Ablängen und Absetzen der HVI ® power-Leitung<br />

Das Ablängen der HVI ® power-Leitung auf die benötigte Länge kann mit dem HVI ® cutter (Kabelschere,<br />

Art.-Nr. 597 032) erfolgen. Es ist auf einen rechtwinkligen Schnitt zu achten!<br />

Zum Absetzen der HVI ® power-Leitung wird das Abisolierwerkzeug HVI ® strip 27 (Art.-Nr. 597 227)<br />

benötigt. Das Werkzeug HVI ® strip 27 ermöglicht in einfacher und sicherer Weise das Absetzen des<br />

äußeren Mantels und der PE-Isolierung ohne den darunterliegenden Cu-Leiter zu verletzen. Es kann<br />

zum Absetzen des halbleitenden Mantels und gleichzeitig der PE-Isolierung der HVI ® power-Leitung<br />

mit einem Außendurchmesser von 27 mm verwendet werden.<br />

Das Werkzeug HVI ® strip 27 besteht aus einem Handgriff und einem austauschbaren Schneidkopf.<br />

Dieser kann einzeln unter der Bezeichnung HVI ® head 27 (Art.-Nr. 597 127) nachbestellt werden. Das<br />

Ansetzen des Schneidkopfes an den Handgriff erfolgt ohne Werkzeug über eine einfache Bajonettkupplung.<br />

Die Abisolierlänge ist in Stufen (Rastpunkte) von 0,2 mm über das in dem Griff eingebaute<br />

Stellrad regulierbar, die eingestellte Länge ist auf der Skala des Handgriffes ablesbar.<br />

Die effektive Abisolierlänge stimmt mit der eingestellten Länge in einer Toleranzbreite von ± 2 mm<br />

überein (siehe hierzu Bild 2).<br />

Bei der Bedienung des HVI ® strip 27 ist wie folgt vorzugehen:<br />

ÂÂAbzusetzende Länge 35 mm am Werkzeug einstellen bzw. korrekte Einstellung kontrollieren.<br />

ÂÂWerkzeug mit Schneidkopf am abgeschnittenen Leitungsende ansetzen.<br />

ÂÂMit Drehbewegung im Uhrzeigersinn und leichter Druckausübung mittels des Werkzeuges erfolgt<br />

der Schneidevorgang / das Absetzen.<br />

!<br />

Sicherheitshinweis<br />

NICHT mit dem Finger in den Schneidkopf greifen.<br />

Verletzungsgefahr!<br />

HVI ® head 27<br />

Schneidkopf<br />

HVI ® strip 27<br />

Handgriff<br />

Stellrad<br />

Abisolierlänge<br />

HVI ® power-Leitung<br />

Bajonettkupplung<br />

Skala<br />

Bild 2 Werkzeug HVI ® head 27<br />

15


5.2 Montage von Kopfstück bzw. Anschlusselement<br />

Die Isolierung der HVI ® power-Leitung ist für die Montage von Kopfstück bzw. Anschlusselement um<br />

35 mm abzusetzen.<br />

Nach dem Absetzen der Isolierung wird das Kopfstück bzw. das Anschlusselement an den Leitungsenden<br />

der HVI ® power-Leitung montiert.<br />

Die nachfolgenden Montageschritte sind dabei zu beachten (siehe auch Bild 3):<br />

ÂÂKopfstück bzw. das Anschlusselement an die HVI ® power-Leitung heranführen und mit Rechtsdrehung<br />

auf das jeweilige Leitungsende bis zum Anschlag aufdrehen. Unterstützend kann dazu auch<br />

ein Gabelschlüssel (Schlüsselweite, SW 19) an der Schlüsselfläche des Kopfstückes bzw. dem Anschlusselement<br />

angesetzt werden.<br />

ÂÂAnschließend werden die beiden Gewindestifte (Innensechskant) mit einem Anzugsdrehmoment<br />

von 5 Nm eingeschraubt und somit der CU-Leiter der HVI ® power-Leitung sicher elektrisch (blitzstromtragfähig)<br />

verbunden.<br />

HVI ® power-Leitung<br />

mehrdrähtige Cu-Leiter<br />

35 mm<br />

Gewindestifte, beschichtet,<br />

Anzugsdrehmoment 5 Nm<br />

Kopfstück<br />

Schlüsselfläche (SW 19)<br />

Anschlusselement<br />

Schlüsselfläche (SW 19)<br />

Ø 10 mm<br />

Bild 3<br />

Montage des Kopfstückes bzw. Anschlusselementes<br />

16


5.3 Umschrumpfen<br />

Verarbeitung der Schrumpfschläuche<br />

Nach der Montage des Kopfstückes bzw. des Anschlusselementes an der HVI ® power-Leitung sind die<br />

entsprechenden Montagebereiche zu umschrumpfen. Die Umschrumpfung erfolgt zum Schutz vor mechanischen,<br />

umweltbedingten oder chemischen Einflüssen. Zum Umschrumpfen stehen zwei Schrumpfschlauchtüllen<br />

(im Lieferumfang Anschluss-Set enthalten) zur Verfügung.<br />

Beim Umschrumpfen sind nachfolgende Punkte zu beachten:<br />

ÂÂDer vorgegebene Umschrumpfungsbereich vom Kopfstück, Anschlusselement bis hin zur<br />

HVI ® power-Leitung ist einzuhalten (siehe Bild 4).<br />

ÂÂDer Schrumpfvorgang erfolgt im vorderen Umschrumpfungsbereich des jeweiligen Kopfstückes bzw.<br />

des Anschlusselementes und endet an der HVI ® power-Leitung. Die Schrumpfschlauchtüllen müssen<br />

bündig mit dem Umschrumpfungsbereich abschließen. Gegebenenfalls müssen sie während der<br />

Umschrumpfung nachpositioniert werden.<br />

ÂÂDie vorgegebene Schrumpftemperatur von max. 150 °C ist einzuhalten!<br />

ÂÂIm Umschrumpfungsbereich der HVI ® power-Leitung dürfen keine zu hohen Schrumpftemperaturen<br />

angewendet werden. Bei überhöhter Schrumpftemperatur kann der halbleitende Mantel der<br />

HVI ® power-Leitung beeinträchtigt oder zerstört werden. Die Funktionalität der HVI ® power-Leitung<br />

ist eventuell nicht mehr gewährleistet.<br />

ÂÂGenerell dürfen beim Umschrumpfen keine Lufteinschlüsse oder Blasenbildungen auftreten!<br />

Umschrumpfungsbereich<br />

Kopfstück<br />

Umschrumpfungsbereich<br />

Anschlusselement<br />

Korrekte Umschrumpfung<br />

Falsche Umschrumpfung<br />

Bild 4<br />

Umschrumpfen des Kopfstückes bzw. Anschlusselementes<br />

17


6. Montage<br />

6.1 Montage der HVI ® power-Leitung im Stützrohr<br />

Vor der Montage des Stützrohres ist die konfektionierte HVI ® power-Leitung mit montiertem Kopfstück<br />

voran in das Stützrohr einzuführen und zu befestigen (siehe hierzu auch Bild 5, Seite 19).<br />

Die nach fol gen den Mon ta ge schritte hierbei sind zu beachten:<br />

ÂÂZuerst die Arretierungsschraube Kopfstück M8 x 25 mm am Stützrohrkopf aufschrauben.<br />

ÂÂNun wird die HVI ® power-Leitung von unten in das Stützrohr eingeführt, dabei muss der Druckwiderstand<br />

der innenliegenden PA-Federkontaktierung überwunden werden. Ein mehrfaches Rein- und<br />

Rausschieben der Leitung in das Stützrohr ist möglich. Zur Kontaktierung des Kopfstückes muss die<br />

HVI ® power-Leitung bis zum oberen Anschlag des Stützrohres eingeschoben und gehalten werden.<br />

ÂÂDanach wird die Arretierungsschraube M8 x 25 mm wieder fest verschraubt und damit das Kopfstück<br />

im Stützrohr fixiert und elektrisch (blitzstromtragfähig) verbunden. Dabei ist ein Anzugsdrehmoment<br />

der Arretierungsschraube von 15 Nm zu beachten. Auf einen korrekten Abstand (ca. 7mm)<br />

des Schraubenkopfes zum Stützrohr nach dem Festziehen ist zu achten. Die Kleberbeschichtung der<br />

Schraube wird erst nach ca. 5 Minuten fest, so dass in diesem Zeitraum die Schraube korrekt positioniert<br />

und angezogen werden kann. Nach dem vollständigen Aushärten der Kleberbeschichtung muß<br />

beim wieder Entfernen der Schraube diese durch eine Neue ersetzt werden.<br />

ÂÂDie ordnungsgemäße mechanische Befestigung der HVI ® power-Leitung im Stützrohr ist zu überprüfen!<br />

(siehe Bild 5). Die korrekte Montage kann mit einem leichten Zug am Austritt der Leitung<br />

überprüft werden.<br />

ÂÂJe nach Aufbau der Anlage muss entweder vor bzw. nach der Montage des Stützrohres die entsprechende<br />

Fangspitze oder Fangstange montiert werden.<br />

  Die Fangspitze bzw. Fangstange wird von oben in den Stützrohrkopf eingeführt und mittels der<br />

beiden Arretierungsschrauben M8x16 mm bzw. M8x10 mm festgeschraubt, dabei ist ebenfalls das<br />

Anzugsdrehmoment von 15 Nm zu beachten.<br />

18


Lieferzustand Montagezustand Korrekte Montage<br />

Stützrohrkopf<br />

Fangstange<br />

ø = 22/16/10 mm<br />

wasserundurchlässig<br />

Arretierungsschraube<br />

Kopfstück, Sechskant M8 x 25 mm,<br />

Anzugsdrehmoment 15 Nm<br />

Fangspitze ø 10 mm<br />

Arretierungsschrauben<br />

Anzugsdrehmoment 15 Nm<br />

-Fangspitze 2x M8x16 mm<br />

-Fangstange 2x M8x10 mm<br />

ca.7 mm<br />

Arretierungsschraube<br />

Kopfstück<br />

(Sechskant M8 x 25 mm,<br />

Anzugsdrehmoment 15 Nm)<br />

GFK/NIRO-Stützrohr<br />

Falsche Montage<br />

ca. 13 mm<br />

ca. 0 mm<br />

HVI ® power-Leitung<br />

(Lieferzustand)<br />

Bild 5<br />

Montage des Kopfstückes im Stützrohr<br />

19


6.2 Endverschluss<br />

Im Bereich des End ver schlus ses ist der<br />

errechnete Tren nungs abstand "s" zu<br />

elektrisch leitfähigen bzw. geerdeten<br />

Teilen ein zuhalten.<br />

Im Bereich des End verschlusses, z.B.:<br />

ÂÂam Stützrohr zwischen Kopfstück und PA-Anschlusselement<br />

(siehe 6.2.1, Seite 20).<br />

ÂÂvariabler Endverschluss an Ringleitung/Attika<br />

(siehe 6.2.2, Seite 23)<br />

ÂÂEndverschluss an einer Gebäudestruktur zwischen<br />

PA-Anschlusselement und Erdanschlusselement<br />

dürfen keine elek trisch leitfähigen<br />

oder geerdeten Teile wie, z.B. metallene Leitungs<br />

halter, Kon struk tionsteile, Ar mierung usw.<br />

angeordnet sein (siehe 6.2.3, Seite 26).<br />

6.2.1 Bereich des Endverschlusses am<br />

Stützrohr am Beispiel einer Antennenanwendung<br />

Der Bereich des Endverschlusses erstreckt sich<br />

vom Anschluss des Kopfstückes bis zu dem im<br />

Stützrohr integrierten PA-Federelement (siehe Bild<br />

6, Detail A und B) und kann von außen betrachtet<br />

über den gesamten Verlauf des GFK-Rohres angenommen<br />

werden.<br />

Über die mechanische Federkontaktierung des<br />

PA-Elements an die HVI ® power-Leitung (halbleitender<br />

Spezialmantel) erfolgt die Absteuerung<br />

gegen das Bezugspotential durch Kontaktierung<br />

der HVI ® power-Leitung an das Stützrohr. Zur Absteuerung<br />

ist eine elektrisch leitende Verbindung<br />

des Stützrohres zum nächstgelegenen Potentialausgleich<br />

der Anlage zwingend erforderlich.<br />

Anschluss<br />

Kopfstück<br />

Detail A<br />

Abgriff<br />

PA-Element<br />

Detail B<br />

Verbindung zum<br />

Potentialausgleich<br />

der Anlage<br />

Detail A:<br />

Anschluss Kopfstück<br />

α<br />

α<br />

s<br />

Anschluss an die<br />

Erdungsanlage<br />

Bereich<br />

Endverschluss<br />

hergestellt (mechanische und elektrische Verbindung).<br />

Antennenstandrohr<br />

Bandrohrschelle<br />

Stützrohr<br />

HVI ® power-Leitung<br />

Detail B:<br />

PA-Element<br />

mechanische Federkontaktierung<br />

Die leitende Verbindung zwischen dem Stützrohr<br />

und dem metallischem Antennenstandrohr wird<br />

z.B. über die Bandrohrschelle (Art.-Nr. 105 360)<br />

Bild 6<br />

Bereich des Endverschlusses im Stützrohr<br />

20


Für den Anschluss des Antennenstandrohres an den Potentialausgleich (Funktionspotentialausgleich)<br />

kann z.B. die Antennenbandrohrschelle (Art.-Nr. 540 100) verwendet werden.<br />

Variante - HVI ® power-Leitung Stützrohrinnenverlegung/Bandrohrschelle an "Mobilfunk-Antenne"<br />

Schutzwinkel α<br />

nach DIN EN 62305-3 (VDE 0185-305-3)<br />

Blitzschutz Teil 3, Tabelle 2<br />

z.B. Fangspitze<br />

NIRO, Ø = 10 mm, L = 1000 mm<br />

Art.-Nr. 101 001<br />

α α<br />

s<br />

Bereich<br />

Endverschluss<br />

1800 mm<br />

z.B. Antenne<br />

Stützrohr GFK/NIRO, z.B. Art.-Nr. 105 320<br />

Stützrohr L = 3500 mm<br />

z.B. Bandrohrschelle<br />

NIRO, Art.-Nr. 105 360,<br />

Klemmbereich Rohr Ø = 50-300 mm<br />

Hinweis:<br />

Antennenerdung nach<br />

DIN VDE 0855 beachten!<br />

HVI ® power-Leitung<br />

Erdanschlusselement<br />

Verbindung zum Potentialausgleich<br />

des Gebäudes<br />

Erdungsanlage<br />

Bild 7<br />

Getrennte Fangeinrichtung mit HVI ® power-Leitung an Mobilfunk-Antenne - Bandrohrschelle<br />

21


Variante - HVI ® power-Leitung Stützrohrinnenverlegung / Wandhalter<br />

Schutzwinkel α<br />

nach DIN EN 62305-3 (VDE 0185-305-3)<br />

Blitzschutz Teil 3, Tabelle 2<br />

α<br />

α<br />

z.B. Fangstange<br />

NIRO, Ø = 22/16/10 mm, L = 2500 mm<br />

Art.-Nr. 103 239<br />

s<br />

Bereich<br />

Endverschluss<br />

1800 mm<br />

Stützrohr mit gebündelter Fangstange<br />

GFK/NIRO, z.B. Art.-Nr. 105 321<br />

Stützrohr L = 3500 mm + Fangstange L = 2500 mm<br />

z.B. Wandbefestigungswinkel<br />

NIRO, Klemmbereich Stützrohr Ø = 40-50 mm,<br />

mit Doppelüberleger, Art.-Nr. 105 344<br />

Doppelüberleger für PA-Anschluss<br />

für den Anschluss von 2x Rd 8-10 mm<br />

HVI ® power-Leitung<br />

Erdungsanlage<br />

Erdanschlusselement<br />

Verbindung zum<br />

Potentialausgleich<br />

des Gebäudes<br />

Bild 8<br />

Getrennte Fangeinrichtung mit HVI ® power-Leitung und Wandhalterung<br />

22


6.2.2 Variabler Endverschluss<br />

Wird die HVI ® power-Leitung nicht bis zur Erdungsanlage, sondern an Blitzspannung behaftete Teile,<br />

(z.B. Attika, Ringleitung) angeschlossen, ist für die effektive Länge des Endverschlusses nachfolgende<br />

Tabelle 8 ausschlaggebend (siehe auch Bild 9, Seite 24 und Bild 10, Seite 25).<br />

Im Bereich unterhalb des Trennungsabstandes "s" 17,5 cm (in Luft) am Erdanschlusselement sind keine<br />

besonderen Montageanforderungen relevant (direkter Anschluss).<br />

Bedingt durch den Leitungsverlauf der HVI ® power-Leitung und des dadurch reduzierten Trennungsabstandes<br />

ist die Realisierung eines zweiten Endverschlusses oberhalb von "s" ≥ 75 cm (in Luft) nicht<br />

üblich.<br />

Länge<br />

Variabler Endverschluss (cm)<br />

200<br />

180<br />

150<br />

maximum<br />

HVI ® power-Leitung<br />

max. variabler Endverschluss<br />

HVI ® power-Leitung<br />

100<br />

35<br />

10 17.5<br />

50<br />

75<br />

90<br />

ÄquivalenterTrennungsabstand<br />

"s" (in Luft)<br />

Tabelle 8<br />

Variabler Endverschluss<br />

23


Variabler Endverschluss an "Getrennte Ringleitung" / Attika<br />

Bei mehreren zu schützenden Anlagenteilen ist es sinvoll, die HVI ® power-Leitung nicht einzeln von<br />

jeder Fangeinrichtung zur Erdungsanlage zu führen. Die von der Fangeinrichtung kommenden<br />

HVI ® power-Leitungen können z.B. an eine "Getrennte Ringleitung oder Attika" an ge schlos sen werden.<br />

Von dieser "Getrennten Ringleitung (Attika)" können dann mehrere Ableitungen zur Erdungsanlage<br />

geführt werden. Dies bewirkt eine Reduzierung des Strom auf tei lungs ko effizienten k C<br />

ab der Höhe<br />

der "Getrennten Ringleitung". Der Trennungsabstand "s" wird dadurch kleiner. Für diese Anwendung<br />

ist die HVI ® power-Leitung vorkonfektioniert oder HVI ® power long vorgesehen (siehe Bild 9 und<br />

10).<br />

Die "Getrennte Ringleitung" muss z.B. auf der Dachebene unter Berücksichtigung des er rech neten<br />

Tren nungs abstandes "s" auf Distanzhaltern und Betonsockel verlegt werden.<br />

Anschlusselement<br />

Variabler Endverschluss<br />

350 mm - max. 1800 mm<br />

HVI ® power-Leitung<br />

Getrennte Ringleitung<br />

Distanzhalter<br />

s<br />

Variables<br />

Dreibeinstativ<br />

mit PA-Element<br />

Leitungshalter<br />

z.B. Art.-Nr. 253 333<br />

Variables Dreibeinstativ<br />

mit PA-Element<br />

Art.-Nr. 105 279<br />

Verbindung zum<br />

Potentialausgleich<br />

des Gebäudes<br />

Bild 9<br />

Getrennte Ringleitung mit HVI ® power-Leitung<br />

24


Variabler Endverschluss<br />

350 mm - max. 1800 mm<br />

Anschlusselement<br />

s<br />

Attika<br />

HVI ® power-Leitung<br />

Leitungshalter<br />

Art.-Nr. 253 333<br />

Variables<br />

Dreibeinstativ<br />

mit PA-Element<br />

Bild 10 Attika<br />

Variables Dreibeinstativ<br />

mit PA-Element<br />

Art.-Nr. 105 279<br />

Verbindung zum<br />

Potentialausgleich<br />

des Gebäudes<br />

25


6.2.3 Endverschluss an einer Gebäudestruktur<br />

Wird die HVI ® power-Leitung an einer Gebäudestruktur verlegt, ist der errechnete Trennungsabstand<br />

"s" im Endverschlussbereich zu den in der Gebäudestruktur befindlichen Metallteilen einzuhalten.<br />

Der Bereich des Endverschlusses erstreckt sich vom PA-Anschlusselement bis zum Anschluss des Erdanschlusselementes<br />

(siehe Bild 11).<br />

Über die mechanische Kontaktierung des PA-Elementes (halbleitender Spezialmantel) erfolgt die Absteuerung<br />

gegen das Bezugspotential. Zur Absteuerung ist eine elektrisch leitende Verbindung zum<br />

nächstgelegenen Potentialausgleich (Potentialausgleichsebene) der Anlage zwingend erforderlich.<br />

Der Anschluss des Erdanschlusselementes der HVI ® power-Leitung erfolgt an die Erdungsanlage mit<br />

einer UNI-Trennklemme (Art.-Nr. 459 200, 200 kA).<br />

Detail A:<br />

PA-Element<br />

PA-Anschlusselement<br />

Detail A<br />

(Art.-Nr. 410 239)<br />

Verbindung zum<br />

Potentialausgleich<br />

der Anlage<br />

PA<br />

Halter, z.B.<br />

Art.-Nr. 275 249<br />

Detail B:<br />

Anschluss Erdanschlusselement<br />

HVI ® power-Leitung<br />

Gebäudestruktur<br />

Bereich<br />

Endverschluss<br />

35 cm -1800 mm<br />

Erdanschlusselement<br />

Detail B<br />

s<br />

s<br />

Ableitung<br />

Anschluss an die<br />

Erdungsanlage<br />

Trennklemme<br />

Art.-Nr. 459 200<br />

Bild 11 Bereich des Endverschlusses an einer Gebäudestruktur<br />

26


Besonders beachtet werden muss:<br />

ÂÂVor der Montage des PA-Anschlusselementes (Art.-Nr. 410 239) ist die HVI ® power-Leitung an der<br />

schwarzen Oberfläche zu säubern.<br />

ÂÂDie Oberfläche muss glatt und fettfrei sein.<br />

ÂÂEventuell vorhandenes Fett muss durch einen mit dem Spezialreiniger (Art.-Nr. 297 199) getränkten<br />

Lappen entfernt werden.<br />

ÂÂDas PA-Anschlusselement darf nicht verschmutzt sein.<br />

ÂÂDie Schraube des PA-Anschlusselementes ist mit einem Dreh moment von 10 Nm anzuziehen.<br />

ÂÂDas PA-Anschlusselement muss die HVI ® power-Leitung fest umschließen.<br />

6.3 Verlegung der HVI ® power-Leitung<br />

Die HVI ® power-Leitung muss in ihrem gesamten Leitungsverlauf im Schutzbereich einer Fang einrich<br />

tung des Äußeren Blitzschutzes verlegt werden. Sie darf im gesamten Leitungsverlauf nicht mit<br />

Blitzspannung behafteten Teilen der Fang ein richtung, Ableitung oder Gebäudekonstruktionsteilen in<br />

Verbindung kommen. Von dieser Festlegung kann abgewichen werden, wenn der Trennungsabstand<br />

"s" am Kreu zungs punkt der HVI ® power-Leitung mit dem Blitzspannung behafteten Teil (Fangeinrichtung,<br />

Attika oder Ableitung) ≤ 35 cm (in Luft) oder ≤ 70 cm (im festen Baustoff) ist. In diesem<br />

Fall ist eine Verbindung zwischen dem Mantel der HVI ® power-Leitung und dem mit Blitzspannung<br />

behafteten Teil zulässig (rückwärtige Spannungsfestigkeit).<br />

Die HVI ® power-Leitung muss bei der Verlegung nach dem Bereich Endverschluss in Abständen von<br />

≤ 1m befestigt werden. Die dabei verwendeten Befestigungsschrauben der metallenen Leitungshalter<br />

sind mit max. 5 Nm anzuziehen.<br />

Wird die HVI ® power-Leitung in einer baulichen Anlage verlegt, sind bauseits festgelegte Schutzmaßnahmen<br />

z.B. Brandschottungen zu beachten.<br />

27


6.4 Montage unter Berücksichtigung der Windzone / Windgeschwindigkeit<br />

Bei der Errichtung von Fangeinrichtungen müssen die Windzonen berücksichtigt werden (siehe<br />

Bild 12 und Bild 13, Seite 29). Die Windzonen sind regional unterschiedlich. Bei Errichtungen von Fangeinrichtungen<br />

außerhalb des Bundesgebietes sind die entsprechenden landesspezifischen Angaben zu<br />

den Windzonen / Windgeschwindigkeit zu berücksichtigen.<br />

Windzone 1<br />

Windzone 2<br />

Windzone 3<br />

Windzone 4<br />

Kiel<br />

Rostock<br />

Schwerin<br />

Hamburg<br />

Bremen<br />

Hannover<br />

Potsdam<br />

Magdeburg<br />

Berlin<br />

Windzone<br />

Grundgeschwindigkeit<br />

Böenwindgeschwindigkeit<br />

WZ 1 22,5 m/s 128 km/h<br />

WZ 2 25,0 m/s 142 km/h<br />

WZ 3 27,5 m/s 156 km/h<br />

WZ 4 30,0 m/s 170 km/h<br />

Essen<br />

Dortmund<br />

Düsseldorf<br />

Köln<br />

Bonn<br />

Erfurt<br />

Halle<br />

Leipzig<br />

Dresden<br />

Chemnitz<br />

Wiesbaden<br />

Frankfurt<br />

Würzburg<br />

Saarbrücken<br />

Mannheim<br />

Nürnberg<br />

Stuttgart<br />

Regensburg<br />

Augsburg<br />

Freiburg<br />

München<br />

Bild 12 Windzonen in Deutschland (Quelle: DIN EN 1991-1-4/NA, Anhang NA.A: Windzonenkarte)<br />

In die Berechnung der tatsächlichen zu erwartenden Windlastbeanspruchung geht neben der zonenabhängigen<br />

Windlast auch die Gebäudehöhe und die örtlichen Gegebenheiten (Gebäude einzeln stehend,<br />

im offenen Gelände oder eingebettet in andere Bebauung) mit ein.<br />

Bei der Auslegung freistehender Fangstangen müssen aus Sicht der Windlastbeanspruchung folgende<br />

Anforderungen erfüllt werden:<br />

ÂÂSicherheit der Fangstange gegen Kippen.<br />

ÂÂSicherheit gegen Bruch der Stangen<br />

ÂÂEinhalten des notwendigen Trennungsabstandes zum zu schützenden Objekt auch unter Windlast<br />

(Vermeidung unzulässiger Durchbiegungen)<br />

Deshalb müssen je nach Bauart der Anlage die einzelnen Komponenten wie z.B. Fangstange, Stützrohr,<br />

Dreibeinstativ usw., hinsichtlich der Windgeschwindigkeiten, richtig ausgewählt werden.<br />

28


Bei der direkten Befestigung der Fangspitze bzw. Fangstange am Stützrohr können unterschiedliche<br />

Windgeschwindigkeiten standgehalten werden. Die entsprechenden Befestigungsmaße des Stützrohres,<br />

siehe Bild 13, müssen eingehalten werden.<br />

Es ergeben sich folgende Varianten, bei denen entsprechende Windgeschwindigkeiten beherrscht werden<br />

können:<br />

ÂÂVariante I (Fangspitze Ø 10 mm, L= 1000 mm) - bis Windzone IV<br />

ÂÂVariante II (Fangstange Ø 22/16/10 mm, L = 2500 mm) - bis Windzone II<br />

Variante I<br />

Stützrohr mit Fangspitze,<br />

Art.-Nr. 105 320 / 105 322, NIRO, ø 10 mm, L = 1000 mm<br />

Variante II<br />

Stützrohr mit Fangstange,<br />

Art.-Nr. 105 321 /105 323, NIRO, ø 22/16/10 mm, L = 2500 mm<br />

α<br />

α<br />

2500 mm<br />

1000 mm<br />

α<br />

α<br />

Stützrohr GFK/NIRO<br />

≤ 2,5 m<br />

≤ 2,5 m<br />

Antenne<br />

≥ 0,5 m<br />

≥ 0,5 m<br />

Antennenmast<br />

Verbindung zum<br />

Potentialausgleich<br />

des Gebäudes<br />

Erdungsanlage<br />

Bild 13 Windgeschwindigkeit - Variante I und II bei der Befestigung am Stützrohr<br />

29


7. Checkliste für HVI ® Installation<br />

Wenn die Fragestellungen in der unten angeführten Checkliste alle mit "JA" beantwortet werden<br />

können, kann von einer ordnungsgemäßen Montage der HVI ® power-Leitung ausgegangen werden.<br />

Die Tabelle kann im Download-Bereich von <strong>DEHN</strong> + SÖHNE GmbH + Co.KG heruntergeladen werden<br />

Checkliste für HVI ® -Installation<br />

Anschrift Prüfobjekt:<br />

Name _____________________________________________________________________________________<br />

Ansprechpartner _____________________________________________________________________________<br />

PLZ, Ort, Straße ______________________________________________________________________________<br />

Telefon ____________________________________________________________________________________<br />

Pos.<br />

Fragestellung<br />

1 Ist die gesamte Anlage im einschlaggeschützten Bereich der Getrennten Fangeinrichtung?<br />

2 Liegt die Berechnung des Trennungsabstandes vor?<br />

(Ableitung bis Erdungsanlage, Insellösung mit Anbindung an bestehende Äußere<br />

Blitzschutzanlage oder Blitzschutz-Potential-Ausgleichsebene auf Dachniveau)<br />

3 Wird für die Anwendung der HVI ® Leitung der von <strong>DEHN</strong> + SÖHNE maximal spezifizierte<br />

äquivalente Trennungsabstand eingehalten?<br />

HVI ® light-Leitung / <strong>DEHN</strong>con H s ≤ 0,45 m in Luft s ≤ 0,9 m fester Baustoff<br />

HVI ® Leitung s ≤ 0,75 m in Luft s ≤ 1,5 m fester Baustoff<br />

HVI ® power-Leitung s ≤ 0,9 m in Luft s ≤ 1,8 m fester Baustoff<br />

Bewertung<br />

JA NEIN<br />

4 Ist im Bereich des Endverschlusses der errechnete Trennungsabstand eingehalten<br />

(fiktive Reuse)?<br />

5 Ist das Stützrohr und ggfs. das PA-Anschlusselement des Endverschlusses korrekt,<br />

nur mit dem Potentialausgleich / der Blitzschutz-Potential-Ausgleichsebene der<br />

Anlage, verbunden?<br />

6 Ist bei parallel geführten HVI ® Leitungen der Mindestabstand von 0,2 m zueinander<br />

eingehalten und der Anschluss an gegenüberliegende Ableitungen beachtet<br />

worden?<br />

7 Ist der minimale Biegeradius eingehalten?<br />

HVI ® light-Leitung (dunkelgrauer Außenmantel) 200 mm<br />

HVI ® Leitung (schwarzer Außenmantel) 200 mm<br />

HVI ® Leitung (grauer Außenmantel)<br />

230 mm<br />

HVI ® power-Leitung (schwarzer Außenmantel) 270 mm<br />

8 Ist das PA-Element des Endverschlusses an der halbleitenden Schicht (nicht grauer<br />

Mantel) kontaktiert?<br />

9 Ist bei Verlegung der HVI ® Leitung im Ex-Bereich die ergänzende Information der<br />

<strong>DEHN</strong>-Montageanleitung Nr. 1501 eingehalten worden?<br />

<strong>DEHN</strong>-Formblatt Nr. 2848/0613<br />

__________________________________<br />

Ort<br />

_________________________<br />

Datum<br />

______________________________________________________________<br />

Unterschrift des Prüfers<br />

Firma<br />

Bild 14 Checkliste<br />

30


Überspannungsschutz <strong>DEHN</strong> + SÖHNE Hans-Dehn-Str. 1 Tel. +49 9181 906-0<br />

Blitzschutz/Erdung GmbH + Co.KG. Postfach 1640 Fax +49 9181 906-1100<br />

Arbeitsschutz 92306 Neumarkt info@dehn.de<br />

<strong>DEHN</strong> schützt. Germany www.dehn.de


Lightning protection/earthing<br />

Installation instructions<br />

HVI ® power<br />

HVI ® power long<br />

DE GB<br />

www.dehn.de<br />

Publication No. 1829 / Update 07.13 Id No. 067426 © Copyright 2013 <strong>DEHN</strong> + SÖHNE


CONTENTS<br />

1. Application of HVI ® power Conductors......................................................................... 4<br />

2. Safety instructions........................................................................................................ 4<br />

3. Specification of HVI ® power Conductors...................................................................... 6<br />

3.1 Design of HVI ® power Conductors................................................................................ 6<br />

3.2 Technical data............................................................................................................... 7<br />

3.3 Chemical properties...................................................................................................... 7<br />

4. Different types of HVI ® power Conductors................................................................... 8<br />

4.1 Pre-assembled HVI ® power Conductors........................................................................ 8<br />

4.2 HVI ® power Conductors for parts of an installation carrying lightning voltage......... 10<br />

4.3 HVI ® power long on a drum......................................................................................... 11<br />

4.4 Required accessories, tools and mounting parts........................................................ 12<br />

4.5 HVI ® power Conductors integrated in the supporting tube........................................ 14<br />

5. Assembly of HVI ® power Conductors.......................................................................... 15<br />

5.1 Cutting HVI ® power Conductors to length/stripping HVI ® power Conductors............ 15<br />

5.2 Mounting the head piece/connection element........................................................... 16<br />

5.3 Wrapping a heat shrinkable sleeve around the head piece/connection element...... 17<br />

6. Installation.................................................................................................................. 18<br />

6.1 Installing HVI ® power Conductors in the supporting tube......................................... 18<br />

6.2 Sealing end................................................................................................................. 20<br />

6.2.1 Sealing end range of the supporting tube based on the example of an antenna.........................20<br />

6.2.2 Variable sealing end.................................................................................................................23<br />

6.2.3 Sealing end on a building’s structure.........................................................................................26<br />

6.3 Installing HVI ® power Conductors............................................................................... 27<br />

6.4 Installation with regard to the wind zone/wind speed.............................................. 28<br />

2


7. Checklist for installing HVI ® Conductors..................................................................... 30<br />

3


1. Application of HVI ® power Conductors<br />

To avoid dangerous flashover between parts of the external lightning protection system and internal<br />

installations such as conductive parts (electrical installation, pipework, etc.), the separation distance<br />

"s" must be observed when installing lightning protection systems.<br />

High impulse voltages cause flashover on the surface of insulating material if no additional measures<br />

are taken. This effect is also referred to as creeping flashover. If the creeping discharge inception voltage<br />

is exceeded, a surface discharge is initiated which can easily flash over a distance of several metres.<br />

To prevent creeping discharges, HVI ® power Conductors feature a special outer sheath which allows<br />

to discharge high lightning impulse voltages to a reference potential. For functional reasons, a connection<br />

is established between the semiconductive outer sheath and the equipotential bonding system of<br />

the building (no lightning voltage) in the sealing end range. This connection to the functional equipotential<br />

bonding can made e.g. on earthed metal roof-mounted structures located in the protected zone<br />

of the lightning protection system, earthed parts of the building construction that do not carry lightning<br />

voltage or on the protective conductor of the low-voltage system.<br />

No conductive or earthed parts may be located in the sensitive sealing end range within the separation<br />

distance "s".<br />

2. Safety instructions<br />

ÂÂHVI ® power Conductors may only be installed under the conditions shown and referred to in these<br />

installation instructions.<br />

ÂÂOnly qualified and trained personnel (lightning protection specialists) may install HVI ® power Conductors.We<br />

recommend to visit a special training course on HVI ® products help by <strong>DEHN</strong>+SÖHNE.<br />

ÂÂFor safety reasons, installation work must be stopped as soon as a thunderstorm approaches/is<br />

noticed.<br />

The components of the HVI ® power system have been tested as a complete system. Mixing components<br />

of the HVI ® power system with components from other manufacturers is not permitted.<br />

  Prior to installation, HVI ® power Conductors must be examined for good order and condition. If<br />

damage or any other defect is found, the HVI ® power Conductors must not be installed. The black<br />

sheath of HVI ® power Conductors must not be damaged by compressive deformation or cuts.<br />

4


ÂÂWhen using HVI ® power Conductors in potentially explosive atmospheres, fire and explosion protection<br />

measures must be taken.<br />

ÂÂIf HVI ® power Conductors are installed on thatched roofs (e.g. reed, straw), special installation<br />

conditions have to be observed for these flammable locations. In our Lightning Protection/Earthing<br />

main catalogue (HVI Lightning Protection for Thatched Roofs), the special installation conditions for<br />

HVI Conductors are described. These conditions also apply to HVI ® power Conductors.<br />

ÂÂIf the supporting tube is led through a roof, the roof must be properly sealed. Warm roofs must be<br />

properly sealed and insulated.<br />

ÂÂHVI ® power Conductors are suitable for outdoor use and can be installed downstream of the sealing<br />

end e.g. on roofs, in walls, in concrete or on facades/facade constructions. However, the conductors<br />

are not suitable for permanent exposure to moisture. HVI ® power Conductors with black<br />

sheath must not be installed in the soil.<br />

ÂÂSoiled HVI ® power Conductors can be cleaned with a cloth soaked with a special cleaning agent<br />

(Part No. 297 199). To be able to comply with dangerous goods regulations, this product is only<br />

transported within Germany and Austria. ISOPROPYL ALCOHOL (99.1 to 99.9 %) (CSA No. 67-63.0)<br />

can be used as an alternative!<br />

ÂÂHVI ® power Conductors must not be painted due to the special design of the outer sheath.<br />

ÂÂThe function of HVI ® power Conductors is to maintain the separation distance. Due to their design,<br />

they do not have a magnetic shielding effect. Induction effects in secondary conductors/loops must<br />

be observed. If required, surge protection measures have to be taken.<br />

ÂÂFor application-specific questions, please contact the relevant sales team or the <strong>DEHN</strong> representative<br />

in your country.<br />

  It has not yet been checked whether HVI ® power Conductors are suitable for installation in hazardous<br />

areas. Therefore, it is not allowed to use HVI ® power Conductors in these areas.<br />

5


3. Specification of HVI ® power Conductors<br />

3.1 Design of HVI ® power Conductors<br />

HVI ® power Conductors are high-voltage-resistant, insulated down conductors with a semiconductive<br />

outer sheath (see Figure 1).<br />

They are typically used as insulated down conductors of lightning protection systems to maintain the<br />

separation distance in accordance with IEC 62305 Part 3. At first, the separation distance “s”must<br />

be calculated as described in subclause 6.3 of IEC 62305 Part 3, with a material factor k m<br />

= 1 in air,<br />

or k m<br />

= 0,5 for solid material. It must be checked whether this calculated separation distance can be<br />

implemented by means of the equivalent separation distance of the HVI ® power Conductors (see<br />

technical data, Table 1 and page 7):<br />

calculated separation distance ≤ equivalent separation distance.<br />

If this is not the case, measures according to 6.2, page 20 are required.<br />

The length required for calculating the separation distance “s” is measured from the head piece to<br />

the next lightning equipotential bonding level, e.g. the earth-termination system.<br />

In case of a down conductor with k c =1, the following maximum conductor lengths are permitted depending<br />

on the class of LPS:<br />

LPS I max. 11.25 m<br />

LPS II max. 15.0 m<br />

LPS III max. 22.5 m<br />

Semiconductive outer sheath<br />

(outer semiconductor, black)<br />

Insulating layer<br />

Smoothing layer<br />

Stranded copper<br />

conductor (25 mm²)<br />

Figure 1<br />

Design of HVI ® power Conductors<br />

6


3.2 Technical data<br />

Outer sheath black, RAL 9011<br />

Equivalent separation<br />

distance of the<br />

HVI ® power Conductor<br />

Outer diameter<br />

Minimum bending radius<br />

Air<br />

Solid material<br />

Permanent temperature range (in case of fixed installation)<br />

≤ 0.9 m<br />

≤ 1.8 m<br />

27 mm<br />

270 mm<br />

-30° to +70°C<br />

Ambient temperature and conductor temperature<br />

during installation and processing<br />

Maximum tensile load<br />

Stranded inner conductor made of copper<br />

-5° to +40°C<br />

1.200 N<br />

25 mm²<br />

Table 1<br />

Technical data of HVI ® power Conductors<br />

3.3 Chemical properties<br />

Halogen-free<br />

Reaction to fire<br />

Weather-proof (UV-resistant)<br />

Fire load<br />

Diluents<br />

yes<br />

not self-extinguishing<br />

yes<br />

6.4 kWh/m<br />

none<br />

Table 2<br />

Chemical properties of HVI ® power Conductors<br />

7


4. Different types of HVI ® power Conductors<br />

The component range of the HVI ® power Conductors system consists of HVI ® power Conductors<br />

and a range of connection and fixing elements matched to these conductors. Special know-how is<br />

required to design and install HVI ® power Conductors. HVI ® power Conductors are available as<br />

pre-assembled conductors or on a 100 m drum (HVI ® power long). More information on the component<br />

range of the HVI ® power Conductors system can be found in our brochures 210 and 212, our<br />

Lightning Protection/Earthing main catalogue and at www.dehn-international.com.<br />

As a basic principle, all HVI ® power Conductors can be shortened, but not extended!<br />

4.1 Pre-assembled HVI ® power Conductors<br />

In general, one conductor end of the pre-assembled HVI ® power Conductors is fitted with the relevant<br />

connection element as shown in Table 3, page 9 and Table 4, page 10. Thus, the head piece is fixed and<br />

a heat shrinkable sleeve is wrapped around it. If required, the second conductor end can be shortened<br />

to exactly match the loose connection element to the design of the installation.<br />

When ordering HVI ® power Conductors , the conductor/minimum length must be observed/indicated.<br />

This information is binding. Since the conductors are tailored to customer needs (customised conductor<br />

lengths), conductors cannot be returned. Pre-assembled HVI ® power Conductors are available with a<br />

standard/minimum length of 6 m. Customised conductors can be ordered in 0.5 m steps. The standard/<br />

minimum length of 6 m must be used in combination with a 3.5 m long supporting tube. A minimum<br />

conductor length of 8 m is recommended for a 5 m long supporting tube.<br />

A loose connection element, heat shrinkable sleeve and hexagon socket wrench are included in delivery<br />

(see also Table 3).<br />

Special tools (HVI ® cutter and HVI ® strip 27) should be used to cut HVI ® power Conductors to<br />

length /shorten HVI ® power Conductors and the connection element/heat shrinkable sleeve should<br />

be attached considering the relevant connection method (see 5., from page 15).<br />

8


Pre-assembled<br />

HVI ® power Conductor<br />

Part.-No.<br />

Standard/minimum<br />

length<br />

Delivery includes<br />

Types 819 160 6 m + x m<br />

(max. 22.5m in case of<br />

kc = 1)<br />

• 1 fixed head piece with heat shrinkable<br />

sleeve.<br />

• 1 connection element, 1 heat shrinkable<br />

sleeve and 1 hexagon socket<br />

wrench (loose).<br />

Field of application<br />

Whenever the air-termination system of the external lightning protection system<br />

is directly connected to the earth-termination system, e.g. isolated air-termination<br />

system of mobile phone antennas - Conductor integrated in the supporting tube (see<br />

Figure 8, page 25 and Figure 9, page 26).<br />

Fixed head piece<br />

Head piece and HVI ® power Conductor<br />

with heat shrinkable sleeve<br />

HVI ® power Conductor with special<br />

sheath<br />

Loosely:<br />

- Connection element<br />

- Heat shrinkable sleeve<br />

- Hexagon socket wrench<br />

Table 3<br />

Pre-assembled HVI ® power Conductors - Overview<br />

9


4.2 HVI ® power Conductors for parts of an installation carrying lightning voltage<br />

A second sealing end is required to connect the pre-assembled HVI ® power Conductor to parts of an<br />

installation carrying lightning voltage (see 6.2, page 20 and 6.3, page 27). To this end, an equipotential<br />

bonding connection element (Part No. 410 239) or a variable tripod with equipotential bonding element<br />

(Part No. 105 279) must be ordered separately.<br />

HVI ® power Conductor Part No Standard/minimum<br />

length<br />

Delivery includes<br />

Types 819 160 6 m + x m<br />

(max. 22.5m in<br />

case of k c = 1)<br />

• Pre-assembled HVI ® power Conductor<br />

• 1 fixed head piece with heat shrinkable sleeve.<br />

• 1 connection element, 1 heat shrinkable sleeve<br />

and 1 hexagon socket wrench (loose).<br />

410 239 Equipotential bonding connection<br />

or 105 279 Variable tripod with equipotential bonding<br />

element<br />

Field of application<br />

For connecting e.g. several parts of an installation to be protected jointly to the<br />

earth-termination system of the building via an "isolated ring conductor" (see 6.2<br />

on page 20). Conductors with a sealing end in the supporting tube and a sealing<br />

end to be adjusted on site are typically used whenever the total condutor length<br />

cannot be exactly determined at the design stage of the installation.<br />

Fixed head piece<br />

HVI ® power Conductor<br />

with special sheath<br />

Head piece and<br />

HVI ® power Conductor<br />

with heat shrinkable sleeve<br />

Loosely delivered:<br />

- Connection element<br />

- Heat shrinkable sleeve<br />

- Hexagon socket wrench<br />

To be ordered separately:<br />

- Equipotential bonding<br />

connection element<br />

or<br />

- Variable tripod with equipotential<br />

bonding element<br />

Table 4<br />

HVI ® power Conductor for parts of an installation carrying lightning voltage - Overview<br />

10


4.3 HVI ® power long on a drum<br />

When delivered, the HVI ® power long Conductor is reeled up on a disposable drum.<br />

It must be observed that the required connection set is not included in delivery.<br />

Consequently, the connection set and the required equipotential bonding connection element(s) depending<br />

on the requirements, type and construction of the installation must be ordered separately (see<br />

Table 5).<br />

General accessories and tools are listed in Table 6, page 12.<br />

HVI ® power long Part No Length Delivery includes Field of application<br />

819 137 100 m Disposable drum with<br />

an outer diameter of<br />

approximately 900 m<br />

Width: approximately<br />

474 mm.<br />

1 Allen key and installation<br />

instructions<br />

819 142 Connection set:<br />

1 head piece<br />

1 connection element<br />

2 heat shrinkable<br />

sleeves<br />

For on-site assembly.<br />

Head piece and connection<br />

element to be connected<br />

to both ends of the<br />

HVI ® power Conductor<br />

410 239 Equipotential bonding<br />

connection element<br />

Equipotential bonding connection<br />

element (Ø 27 mm) for resetting<br />

the electrical field in the<br />

sealing end range. Required for<br />

the sealing end.<br />

105 279 Variable tripod with<br />

equipotential bonding<br />

element for the sealing<br />

end, adjustable height<br />

from 610 to 1095 mm<br />

(top edge of the concrete<br />

base)<br />

Table 5<br />

HVI ® power long on a drum - Required accessories<br />

11


4.4 Required accessories, tools and mounting parts<br />

HVI ® power Conductors can be installed using the following mounting parts and tools:<br />

Part No. Delivery includes Description<br />

819 142 Connection set:<br />

1 head piece<br />

1 connection element<br />

2 heat shrinkable sleeves<br />

275 240 Metal conductor holder<br />

HVI ® power Conductor<br />

Head piece and connection element to be connected to<br />

both ends of the HVI ® power Conductor.<br />

Stainless steel conductor holder (Ø 27 to 30 mm)<br />

M8 thread<br />

275 249 Metal conductor holder<br />

HVI ® power Conductor<br />

Stainless steel conductor holder (Ø 27 to 30 mm)<br />

M8 thread with plastic base<br />

275 241 Metal conductor holder<br />

HVI ® power Conductor<br />

Stainless steel conductor holder (Ø 27 to 30 mm)<br />

M6 thread<br />

275 242 Metal conductor holder<br />

HVI ® power Conductor<br />

Stainless steel conductor holder (Ø 27 to 30 mm)<br />

with slot (Ø 5.5 x 10 mm)<br />

410 239 Equipotential bonding<br />

connection element<br />

Equipotential bonding connection element (Ø 27 mm)<br />

for resetting the electrical field in the sealing end range.<br />

Required for each sealing end.<br />

597 227 HVI ® strip 27 Stripping tool for stranded conductors (Ø 27 mm) consisting<br />

of a handle and a stripping insert<br />

597 127 HVI ® head 27 Stripping insert (Ø 27 mm) for HVI ® strip 27 stripping<br />

tool<br />

12


Part No. Delivery includes Description<br />

597 032 HVI ® cutter Cable pliers for stripping HVI ® power Conductors<br />

253 334 Holder for flat roofs (SET) For installing conductors on flat roofs,<br />

weight: 8.5 kg<br />

202 857 Holder for gable roofs Brace with perforated bending points for installing<br />

HVI ® power Conductors on gable roofs.<br />

459 200 Disconnecting clamp<br />

Rd/Rd<br />

Rd/Fl<br />

Stainless steel disconnecting clamp<br />

(8 to 10/8 to 10 mm) with intermediate plate for two<br />

round conductors or 8 to 10/30 mm for round and flat<br />

conductors (200 kA for LPS I)<br />

105 279 Variable tripod with equipotential<br />

bonding element<br />

For establishing the sealing end<br />

105 344 Wall mounting bracket for<br />

supporting tubes<br />

Wall mounting bracket, adjustment range<br />

from 150 to 200 mm<br />

105 160 Fixing clamp with<br />

tensioning strap<br />

Clamping range: 50 to 300 mm<br />

253 333 Holder for flat roofs (SET) For installing conductors on flat roofs,<br />

weight: 4.6 kg<br />

Table 6<br />

Accessories and tools<br />

13


4.5 HVI ® power Conductors integrated in the supporting tube<br />

The supporting tubes in which HVI ® power Conductors are integrated house an equipotential bonding<br />

element acting as a spring element.<br />

The head of the supporting tube is mechanically closed and thus water-proof.<br />

For static reasons, spanning cables over several supporting tubes to split the current is not possible<br />

in every situation! Please contact us for more detailed information.<br />

Different types of supporting tubes for integrating HVI ® power Conductors are available (see Table 7):<br />

Part No. Consisting of: Component<br />

length<br />

Total<br />

length<br />

Minimum<br />

length of the<br />

HVI®power<br />

Conductor<br />

105 320 Supporting tube 3.5 m 4.5 m 6 m + x m<br />

Air-termination tip<br />

(Ø 10 mm)<br />

1.0 m<br />

105 321 Supporting tube 3.5 m 6.0 m 6 m + x m<br />

Air-termination tip<br />

(Ø 22/16/10 mm)<br />

2.5 m<br />

105 322 Supporting tube<br />

Air-termination tip<br />

(Ø 10 mm)<br />

5.0 m<br />

1.0 m<br />

6.0 m 6 m + x m<br />

(recommended<br />

minimum<br />

length: 8m)<br />

105 323 Supporting tube<br />

Air-termination tip<br />

(Ø 22/16/10 mm)<br />

5.0 m<br />

2.5 m<br />

7.5 m 6 m + x m<br />

(recommended<br />

minimum<br />

length: 8m)<br />

Table 7<br />

Types of supporting tubes<br />

14


5. Assembly of HVI ® power Conductors<br />

5.1 Cutting HVI ® power Conductors to length/stripping HVI ® power Conductors<br />

The HVI ® cutter (cable pliers, Part No. 597 032) can be used to cut HVI ® power Conductors to the<br />

required length. Ensure right-angled cut!<br />

The HVI ® strip 27 stripping tool (Part No. 597 227) allows to easily and reliably strip the outer sheath<br />

and the PE insulation of HVI ® power Conductors without damaging the copper conductor underneath<br />

it. It can be used for stripping the semiconductive sheath and the PE insulation of HVI ® power Conductors<br />

with an outer diameter of 27 mm.<br />

The HVI ® strip 27 tool consists of a handle and an exchangeable stripping insert. This HVI ® head 27<br />

stripping insert (Part No. 597 127) can be reordered individually. The stripping insert is plugged into<br />

the handle without tools via a bayonet coupling. The stripping length can be adjusted in steps of 0.2<br />

mm by means of the knob housed in the handle. The chosen stripping length is visible on the scale of<br />

the handle.<br />

The effective stripping length corresponds to the adjusted length with a tolerance of ± 2 mm<br />

(see Fig. 2).<br />

The HVI ® strip 27 tool is handled as follows:<br />

ÂÂSet the stripping length (35 mm) on the tool or check whether the set length is correct.<br />

ÂÂAttach the stripping insert of the tool to the cut conductor end.<br />

ÂÂThe sheath is cut/stripped by turning the handle clockwise and applying light pressure by means of<br />

the tool.<br />

HVI ® head 27<br />

stripping insert<br />

!<br />

Safety note<br />

Do not place your finger in the stripping insert.<br />

Risk of injury!<br />

knob for adjusting the<br />

stripping length<br />

HVI ® strip 27<br />

handle<br />

HVI ® power Conductor<br />

bayonet coupling<br />

scale<br />

Figure 2<br />

HVI ® head 27 tool<br />

15


5.2 Mounting the head piece/connection element<br />

To mount the head piece/connection element, the insulation of HVI ® power Conductors must be<br />

removed by 35 mm.<br />

After removing the insulation, the head piece/connection element is mounted on the conductor ends of<br />

the HVI ® power Conductor.<br />

The following steps must be observed (see also Fig. 3):<br />

ÂÂBring the head piece/connection element to the HVI ® power Conductor and turn it clockwise onto<br />

the relevant conductor end as far as it will go. To this end, an open-end wrench (wrench size 19) can<br />

be used on the wrench contact surface of the head piece/connection element.<br />

ÂÂSubsequently, tighten the two hexagon socket head screws using a tightening torque of 5 Nm. Thus,<br />

the copper conductor of the HVI ® power Conductor is safely electrically connected (capable of<br />

carrying lightning currents).<br />

HVI ® power Conductor<br />

stranded copper conductor<br />

35 mm<br />

hexagon socket head screw (coated),<br />

tightening torque of 5 Nm<br />

head piece<br />

wrench contact surface 19<br />

connection element<br />

wrench contact surface 19<br />

Ø 10 mm<br />

Figure 3<br />

Mounting the head piece/connection element<br />

16


5.3 Wrapping a heat shrinkable sleeve around the head piece/connection<br />

element<br />

Applying heat shrinkable sleeves<br />

After mounting the head piece/connection element on the HVI ® power Conductor , a heat shrinkable<br />

sleeve must be wrapped around the relevant mounting areas to protect them from mechanical, environmental<br />

or chemical influences. The connection set includes two heat shrinkable sleeves.<br />

The following must be observed when wrapping a heat shrinkable sleeve around the head<br />

piece/connection element:<br />

ÂÂThe indicated shrinking area from the head piece/connection element to the HVI ® power Conductor<br />

must be observed (Fig. 4).<br />

ÂÂThe heat shrinkable sleeve is applied from the front shrinking area of the relevant head piece/<br />

connection element and to the HVI ® power Conductor. The heat shrinkable sleeves must flush with<br />

the shrinking area. If, required they must be repositioned during the shrinking on process.<br />

ÂÂThe specified shrinking temperature of max. 150 °C must be observed!<br />

ÂÂThe shrinking temperatures in the shrinking area of the HVI ® power Conductor must not be too<br />

high. In case of excessive shrinking temperatures, the semiconductive sheath of the HVI ® power<br />

Conductor can be damaged or destroyed and the function of the HVI ® power Conductor may not<br />

be ensured any more.<br />

ÂÂThe heat shrinkable sleeve must not trap air or form bubbles!<br />

Shrinking area of the<br />

head piece<br />

Shrinking area of the<br />

connection element<br />

Correct shrinking<br />

Incorrect shrinking<br />

Figure 4<br />

Wrapping a heat shrinkable sleeve around the head piece/connection element<br />

17


6. Installation<br />

6.1 Installing HVI ® power Conductors in the supporting tube<br />

Before installing the supporting tube, insert and fix the head piece of the pre-assembled HVI ® power<br />

Conductor into the supporting tube (see also Fig. 5, page 19).<br />

The following steps must be observed:<br />

ÂÂScrew the locking screw of the head piece (M8 x 25 mm) to the head of the supporting tube.<br />

ÂÂInsert the HVI ® power Conductor from below into the supporting tube. To this end, the compressive<br />

strength of the integrated spring element must be overcome. The conductor can be inserted<br />

and removed several times. To contact the head piece, insert the HVI ® power Conductor into the<br />

supporting tube as far as it will go and hold it there.<br />

ÂÂThe locking screw (M8 x 25 mm) is firmly tightened again using a tightening torque of 15 Nm. Thus,<br />

the head piece is fixed in the supporting tube and is electrically connected (capable of carrying lightning<br />

currents). Make sure that there is a sufficient distance (about 7 mm) between the screw head is<br />

and the supporting tube after tightening the locking screw. The adhesive coating of the screw only<br />

hardens after about 5 minutes so that the screw can be correctly positioned and tightened during<br />

this period. After hardening of the adhesive coating, the screw must be replaced by a new one if the<br />

screw is removed.<br />

ÂÂCheck whether the HVI ® power Conductor is properly fixed in the supporting tube (see Fig. 5).<br />

Proper installation can be verified by slightly pulling the conductor at the point where the conductor<br />

leaves the supporting tube.<br />

ÂÂDepending on the construction of the installation, the relevant air-termination tip/air-termination<br />

rod must be installed before or after the supporting tube has been installed.<br />

  Insert the air-termination tip/air-termination rod from above into the head of the supporting tube<br />

and tighten the two locking screws (M8 x 16 mm/M8 x 10 mm) using a tightening torque of 15 Nm.<br />

18


As-delivered condition<br />

air-termination rod<br />

ø = 22/16/10 mm<br />

Assembled<br />

conditon<br />

Correct assembly<br />

head of the supporting tube<br />

water-proof<br />

locking screw<br />

head piece, hexagon screw M8 x 25 mm,<br />

tightening torque of 15 Nm<br />

air-termination tip<br />

ø 10 mm<br />

locking screws<br />

tightening torque of 15 Nm<br />

-air-termination tip 2x M8x16 mm<br />

-air-termination rod 2x M8x10 mm<br />

approx.7 mm<br />

locking screw<br />

head piece<br />

(hexagon screw M8 x 25 mm,<br />

tightening torque of 15 Nm)<br />

GRP/StSt-supporting tube<br />

Incorrect assembly<br />

approx. 13 mm<br />

approx.<br />

0 mm<br />

HVI ® power Conductor<br />

(as-delivered condition)<br />

Figure 5<br />

Installation of the head piece in the supporting tube<br />

19


6.2 Sealing end<br />

The calculated separation distance “s”<br />

from conductive/earthed parts has to be<br />

maintained in the sealing end range.<br />

No conductive or earthed parts such as metal conductor<br />

holders, structural parts, reinforcement,<br />

etc., may be installed in the sealing end range, for<br />

example:<br />

ÂÂAt the supporting tube between the head piece<br />

and equipotential bonding connection element<br />

(see 6.2.1, page 20)<br />

ÂÂVariable sealing end on the ring conductor/metal<br />

capping of the roof parapet (see 6.2.2, page<br />

23)<br />

ÂÂSealing end on the building’s structure between<br />

the equipotential bonding connection element<br />

and the earth connection element (see 6.2.3,<br />

page 26).<br />

6.2.1 Sealing end range of the supporting<br />

tube based on the example of an<br />

antenna<br />

The sealing end range ranges from the connection<br />

of the head piece to the equipotential bonding<br />

spring element integrated in the supporting tube<br />

(see Fig. 6, detail A and B) and can be assumed to<br />

run along the entire route of the GRP tube.<br />

Due to the mechanical spring contact, acting as<br />

an equipotential bonding element, the HVI ® power<br />

Conductor (semiconductive special sheath) is<br />

connected to the supporting tube. To this end, the<br />

supporting tube must be conductively connected<br />

with the next equipotential bonding system of the<br />

installation.<br />

No. 105 360) (mechanical and electrical connection).<br />

connection of<br />

the head piece<br />

Detail A<br />

equipotential<br />

bonding element<br />

Detail B<br />

antenna<br />

standpipe<br />

connection the<br />

equipotential<br />

bonding of the<br />

installation<br />

Detail A:<br />

connection of the<br />

head piece<br />

α<br />

α<br />

s<br />

sealing<br />

end range<br />

connection to the<br />

earth-termination<br />

system<br />

pipe clamp<br />

supporting<br />

tube<br />

HVI ® power Conductor<br />

Detail B: equipotential<br />

bonding element<br />

mechanical spring contact<br />

The conductive connection between the supporting<br />

tube and the metallic antenna standpipe is<br />

established by means of e.g. a pipe clamp (Part<br />

Figure 6<br />

Sealing end range in the supporting tube<br />

20


An antenna pipe clamp (Part No. 540 100), for example, can be used to connect the antenna standpipe<br />

to the equipotential bonding (functional equipotential bonding).<br />

HVI ® power Conductor integrated in the supporting tube/pipe clamp installed on a mobile<br />

phone antenna<br />

protective angle α<br />

acc. to IEC 62305 Part 3, Table 2<br />

e.g. stainless steel air-termination tip<br />

(Ø = 10 mm, L = 1000 mm)<br />

Part No. 101 001<br />

α α<br />

s<br />

sealing<br />

end range<br />

1800 mm<br />

e.g. antenna<br />

GRP/StSt supporting tube,<br />

e.g. Part No. 105 320<br />

supporting tube L = 3500 mm<br />

e.g. stainless steel pipe clamp,<br />

Part No. 105 360, clamping range<br />

supporting tube Ø = 50 to 300 mm<br />

Note:<br />

Observe antenna earthing as per<br />

DIN VDE 085!<br />

HVI ® power Conductor<br />

earth connection<br />

element<br />

connection the equipotential<br />

bonding of the building<br />

earth-termination system<br />

Figure 7<br />

Isolated air-termination system with a HVI ® power Conductor installed on a mobile phone antenna<br />

- Pipe clamp<br />

21


HVI ® power Conductor integrated in the supporting tube/wall fixing bracket<br />

protective angle α<br />

acc. to IEC 62305 Part 3, Table 2<br />

α<br />

α<br />

e.g. stainless steel air-termination tip<br />

(Ø = 22/16/10 mm, L = 2500 mm)<br />

Part No. 103 239<br />

s<br />

sealing<br />

end range<br />

1800 mm<br />

GRSP/StSt supporting tube with air-termination rod<br />

e.g. Part No. 105 321<br />

supporting tube L = 3500 mm + air-termination rod L = 2500 mm<br />

e.g. stainless steel wall fixing bracket<br />

clamping range supporting tube Ø = 40 to 50 mm,<br />

with double cleat, Part No. 105 344<br />

double cleat for connecting 2x Rd 8 to 10 mm<br />

to the equipotential bonding<br />

HVI ® power Conductor<br />

earth-termination system<br />

earth connection element<br />

connection with the<br />

equipotential bonding<br />

of the building<br />

Figure 8<br />

Isolated air-termination system with a HVI ® power Conductor and wall fixing bracket<br />

22


6.2.2 Variable sealing end<br />

If the HVI ® power Conductor is not connected to the earth-termination system, but to parts carrying<br />

lightning voltage (e.g. metal capping of the roof parapet, ring conductor), the below table is decisive<br />

for the effective length of the sealing end (see also Fig. 9, page 24 and Fig. 10, page 25).<br />

No special installation conditions must be observed in the area below the separation distance "s" of<br />

17.5 cm (in air) on the earth connection element (direct connection).<br />

Due to the routing of the HVI ® power Conductorand the resulting reduced separation distance, it is<br />

not common to establish a second sealing end if the separation distance "s" is ≥ 75 cm (in air).<br />

Length<br />

of the variable sealing end (cm)<br />

200<br />

180<br />

150<br />

max.<br />

HVI ® power Conductor<br />

max. varible sealing end<br />

HVI ® power Conductor<br />

100<br />

35<br />

10 17.5<br />

50<br />

75<br />

90<br />

Equivalent separation<br />

distance "s" (in air)<br />

Table 8<br />

Variable sealing end<br />

23


Variable sealing end on isolated ring conductors/metal cappings of the roof parapet<br />

f several parts of an installation are to be protected, it is not advisable to lead the HVI ® power Conductor<br />

from each air-termination system to the earth-termination system. The HVI ® power Conductors<br />

arriving from the air-termination system can be connected to e.g. an isolated ring conductor or<br />

to the metal capping of the roof parapet. From this isolated ring conductor (metal capping of the roof<br />

parapet), several down conductors can be led to the earth-termination system. In this case, the partitioning<br />

coefficient k C<br />

is reduced due to the isolated ring conductor. As a result, the separation distance<br />

"s" is also reduced. Pre-assembled HVI ® power Conductors or HVI ® power long Conductors can be<br />

used for this purpose (see Fig. 9 and 10).<br />

The isolated ring conductor must be installed on spacers and concrete bases e.g. on the roof level. The<br />

calculated separation distance "s" must be observed.<br />

connection element<br />

variable sealing end<br />

350 mm - max. 1800 mm<br />

HVI ® power Conductor<br />

isolated ring conductor<br />

spacer<br />

s<br />

variable tripod with<br />

equipotential bonding<br />

element<br />

conductor holder<br />

e.g. Part No. 253 333<br />

variable tripod with<br />

equipotential bonding element<br />

Part No. 105 279<br />

connection with the<br />

equipotential bonding<br />

of the building<br />

Figure 9<br />

Isolated ring conductor with HVI ® power Conductor<br />

24


variable sealing end<br />

350 mm - max. 1800 mm<br />

connection element<br />

metal capping of<br />

the roof parapet<br />

s<br />

HVI ® power Conductor<br />

conductor holder<br />

Part No. 253 333<br />

variable tripod with<br />

equipotential bonding<br />

element<br />

variable tripod with equipotential<br />

bonding element<br />

Part No 105 279<br />

connection with the<br />

equiptential bonding of<br />

the building<br />

Figure 10 Metal capping of the roof parapet<br />

25


6.2.3 Sealing end on a building’s structure<br />

If HVI ® power Conductors are installed on a building’s structure, the calculated separation distance<br />

"s" in the sealing end range from the metal parts in the building’s structure must be kept.<br />

The sealing end range ranges from the equipotential bonding connection element to the connection of<br />

the earth connection element (see Fig. 11).<br />

The mechanical contact of the equipotential bonding element (semiconductive coating) allows to<br />

discharge lightning impulse voltages to a reference potential (see Fig. 11). To this end, a conductive<br />

connection with the next equipotential bonding level of the installation is required.<br />

A UNI earthing clamp (Part No. 459 200, 200 kA) is used to connect the earth connection element of<br />

the HVI ® power Conductor to the earth-termination system.<br />

Detail A: equipotential<br />

bonding<br />

element<br />

equipotential bonding<br />

connection element<br />

(Part No. 410 239)<br />

Detail A<br />

connection with the<br />

equipotential bonding<br />

of the building<br />

EB<br />

holder, e.g.<br />

Part No. 275 249<br />

Detail B: connection of the<br />

earth connection element<br />

HVI ® power Conductor<br />

building´s structure<br />

sealing end range<br />

35 cm -1800 mm<br />

earth connection<br />

element<br />

Detail B<br />

s<br />

s<br />

down conductor<br />

connection to the<br />

earth-termination system<br />

disconnecting clamp<br />

Part No. 459 200<br />

Figure 11 Sealing end range on a building’s structure<br />

26


The following must be observed:<br />

ÂÂThe black surface of the HVI ® power Conductor must be cleaned before installing the equipotential<br />

bonding connection element (Part No. 410 329).<br />

ÂÂThe surface must be smooth and free of grease.<br />

ÂÂPossible grease must be removed using a cloth soaked with a special cleaning agent (Part No.<br />

297 199).<br />

ÂÂThe equipotential bonding connection element must not be soiled.<br />

ÂÂThe screw of the equipotential bonding connection element must be tightened with a tightening<br />

torque of 10 Nm.<br />

ÂÂThe equipotential bonding connection element has to firmly enclose the HVI ® power Conductor.<br />

6.3 Installing HVI ® power Conductors<br />

The entire HVI ® power Conductor has to be installed in the protected zone of the air-termination system<br />

of the external lightning protection system and must not be connected to parts of the air-termination<br />

system, down conductor or structural parts that carry lightning voltage. An exception can be made<br />

if the separation distance "s" at the point where the HVI ® power Conductor crosses the part carrying<br />

lightning voltage (air-termination system, metal capping of the roof parapet, down conductor) is ≤ 35<br />

cm (in air) oder ≤ 70 cm (for solid material). In this case, the sheath of theHVI ® power Conductor<br />

can be connected to the part carrying lightning voltage.<br />

If installed downstream of the sealing end range, the HVI ® power Conductor has to be fixed at intervals<br />

of ≤ 1 m. The fixing screws of the metal conductor holders have to be tightened with a tightening<br />

torque of max. 5 Nm.<br />

If the HVI ® power Conductor is installed in a building, protection measures, e.g. fire barriers, have to<br />

be taken.<br />

27


6.4 Installation with regard to the wind zone/wind speed<br />

When installing air-termination systems, the wind zones must be observed (see Fig. 12 and 13, page<br />

29). These wind zones differ from region to region. When installing air-termination systems outside of<br />

Germany, the country-specific requirements concerning wind zones/wind speeds must be considered.<br />

wind zone 1<br />

wind zone 2<br />

wind zone 3<br />

wind zone 4<br />

Kiel<br />

Rostock<br />

Schwerin<br />

Hamburg<br />

Bremen<br />

Hannover<br />

Potsdam<br />

Magdeburg<br />

Berlin<br />

wind<br />

zone<br />

base wind<br />

speed<br />

gust wind<br />

speed<br />

WZ 1 22.5 m/s 128 km/h<br />

WZ 2 25.0 m/s 142 km/h<br />

WZ 3 27.5 m/s 156 km/h<br />

WZ 4 30.0 m/s 170 km/h<br />

Essen<br />

Dortmund<br />

Düsseldorf<br />

Köln<br />

Bonn<br />

Erfurt<br />

Halle<br />

Leipzig<br />

Dresden<br />

Chemnitz<br />

Wiesbaden<br />

Frankfurt<br />

Würzburg<br />

Saarbrücken<br />

Mannheim<br />

Nürnberg<br />

Stuttgart<br />

Regensburg<br />

Augsburg<br />

Freiburg<br />

München<br />

Figure 12 Wind zones in Germany (source: DIN EN 1991-1-4/NA, Annex NA.A: wind zone map)<br />

To calculate the actual wind load to be expected, the zone-dependent wind load, building height and<br />

local conditions (detached building in open terrain or building surrounded by other buildings) must also<br />

be considered. When designing self-supporting air-termination rods, the following requirements must<br />

be fulfilled with regard to the wind load:<br />

ÂÂTilt resistance of the air-termination rod.<br />

ÂÂBreak resistance of the air-termination rod<br />

ÂÂThe required separation distance from the object to be protected must be maintained even under<br />

wind load (prevention of intolerable bending)<br />

Therefore, the individual components such as air-termination rod, supporting tube, tripod, etc. must be<br />

chosen for the wind load to be expected depending on the construction of the building.<br />

28


If the air-termination tip/air-termination rod is directly attached to the supporting tube, HVI ® power<br />

Conductors can withstand different wind loads. The relevant fixing dimensions of the supporting tube<br />

(see Fig. 13) must be observed.<br />

The following versions are possible:<br />

ÂÂVersion I (air-termination tip Ø 10 mm, L= 1000 mm) - up to wind zone IV<br />

ÂÂVersion II (air-termination rod Ø 22/16/10 mm, L = 2500 mm) - up to wind zone II<br />

Version I<br />

Support tube with air-termination tip,<br />

Part No. 105 320 / 105 322, StSt, ø 10 mm, L = 1000 mm<br />

Version II<br />

Supporting tube with air-termination rod,<br />

Part No. 105 321 /105 323, StSt, ø 22/16/10 mm, L = 2500 mm<br />

α<br />

α<br />

1000 mm<br />

GRP/StSt supporting tube<br />

≤ 2.5 m<br />

2500 mm<br />

α<br />

α<br />

≤ 2.5 m<br />

antenna<br />

≥ 0.5 m<br />

≥ 0.5 m<br />

antenna mast<br />

connection with<br />

the equipotential<br />

bonding of the<br />

building<br />

earth-termination system<br />

Figure 13 Wind speed – Version I and II for fixing the HVI ® power Conductor to the supporting tube<br />

29


7. Checklist for installing HVI ® Conductors<br />

If all questions in the below checklist are answered with “yes”, it can be assumed that the HVI ® power<br />

conductor is installed correctly. A pdf file of the checklist can be downloaded at www.dehn.de.<br />

Checklist for HVI ® Installation<br />

Address of the test object:<br />

Name _____________________________________________________________________________________<br />

Contact partner ______________________________________________________________________________<br />

Postcode, Place, Street _________________________________________________________________________<br />

Phone _____________________________________________________________________________________<br />

Item<br />

Question<br />

1 Is the whole system positioned in the protected area of the isolated air-termination<br />

system?<br />

2 Has the separation distance been calculated?<br />

(down conductor to the earth-termination system, isolated system with connection<br />

to existing external lightning protection system or lightning equipotential<br />

bonding on roof level)<br />

3 Is the maximum equivalent separation distance specified by <strong>DEHN</strong> + SÖHNE for<br />

the application of the HVI ® Conductor kept?<br />

HVI ® light Conductor / <strong>DEHN</strong>con H s ≤ 0.45 m in air s ≤ 0.9 m solid material<br />

HVI ® Conductor s ≤ 0.75 m in air s ≤ 1.5 m solid material<br />

HVI ® power Conductor s ≤ 0.9 m in air s ≤ 1.8 m solid material<br />

YES<br />

Rating<br />

NO<br />

4 Is the calculated separation distance kept in the range of the sealing end?<br />

5 Is the supporting tube and, if required, the equipotential bonding element of the<br />

sealing end correct, i.e. only connected with the equipotential bonding / the lightning<br />

equipotential bonding of the system?<br />

6 Is the minimum distance of 0.2 m kept between HVI ® Conductors routed in parallel<br />

and has the connection to opposite down conductors been considered?<br />

7 Has the minimum bending radius been kept?<br />

HVI ® light Conductor (dark grey outer coating) 200 mm<br />

HVI ® Conductor (black outer coating) 200 mm<br />

HVI ® Conductor (grey outer coating)<br />

230 mm<br />

HVI ® power Conductor (black outer coating) 270 mm<br />

8 Is the equipotential bonding element of the sealing end in contact with the semiconductive<br />

layer (not grey coating)?<br />

9 Has the supplementary information of the <strong>DEHN</strong> installation instructions No. 1501<br />

been considered for the installation of the HVI ® Conductor in hazardous areas?<br />

Company<br />

<strong>DEHN</strong> Form No. 2848/E/0613<br />

__________________________________<br />

Place<br />

_________________________<br />

Date<br />

______________________________________________________________<br />

Signature of tester<br />

Figure 14 Check list<br />

30


Surge Protection <strong>DEHN</strong> + SÖHNE Hans-Dehn-Str. 1 Tel. +49 9181 906-0<br />

Lightning Protection GmbH + Co.KG. Postfach 1640 Fax +49 9181 906-1444<br />

Safety Equipment 92306 Neumarkt export@dehn.de<br />

<strong>DEHN</strong> protects. Germany www.dehn.de