Presentation<br />

Metal-enclosed,<br />

factory-built equipment<br />

Standards<br />

Apart from special cases, MERLIN GERIN equipment is in conformity with<br />

list 2 of the series 1 table in IEC 60 071 and 60 298.<br />

Rated Rated lightning Rated Normal<br />

voltage impulse power-frequency operating<br />

withstand voltage withstand voltage voltage<br />

1.2/50 µs 50 Hz<br />

kV rms. kV peak 1 minute kV rms. kV rms.<br />

list 1 list 2<br />

7.2 40 60 20 3.3 to 6.6<br />

12 60 75 28 10 to 11<br />

17.5 75 95 38 13.8 to 15<br />

24 95 125 50 20 to 22<br />

36 145 170 70 25.8 to 36<br />

Insulation levels apply to metal-enclosed switchgear at altitudes of less<br />

than 1 000 metres, 20°C, 11 g/m 3 humidity and a pressure of 1 013 mbar.<br />

Above this, derating should be considered.<br />

Each insulation level corresponds to a distance in air which guarantees<br />

equipment withstand without a test certificate.<br />

Rated Rated impulse Distance/earth<br />

voltage kV rms. withstand voltage in air cm<br />

1.2/50 µs kV peak<br />

7.2 60 10<br />

12 75 12<br />

17.5 95 16<br />

24 125 22<br />

36 170 32<br />

IEC standardised voltages<br />

Um<br />

U<br />

0.5 Um<br />

Rated power frequency<br />

withstand voltage<br />

50 Hz 1 mm<br />

20<br />

28<br />

38<br />

50<br />

70<br />

Rated voltage<br />

7.2<br />

12<br />

17.5<br />

24<br />

36<br />

60<br />

75<br />

95<br />

125<br />

170<br />

0 1.2 µs 50 µs<br />

Rated lightning<br />

withstand voltage<br />

t<br />

Ud Ur Up<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

7