23.02.2014 Views

MV design guide - Schneider Electric

MV design guide - Schneider Electric

MV design guide - Schneider Electric

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Switchgear<br />

definition<br />

Current transformer<br />

Primary operating current (Ips)<br />

An installation's primary operating current I (kA) (for a transformer<br />

feeder for example) is equal to the CT primary operating current (Ips)<br />

taking account of any possible derating.<br />

c If:<br />

S : apparent power in kVA<br />

U : primary operating voltage in kV<br />

P : active power of the motor in kW<br />

Q : reactive power of capacitors in kvars<br />

Ips : primary operating current in A<br />

c We will have:<br />

v incomer cubicle<br />

v generator set incomer<br />

v transformer feeder<br />

v motor feeder<br />

S<br />

Ips =<br />

e• U<br />

S<br />

Ips =<br />

e• U<br />

Ips =<br />

S<br />

e• U<br />

Ips =<br />

P<br />

e• U • cosϕ • η<br />

η : motor efficiency<br />

Example:<br />

A thermal protection device for a motor<br />

has a setting range of between 0.6 and<br />

1.2 • IrTC. In order to protect this motor,<br />

the required setting must correspond to<br />

the motor's rated current.<br />

c If we suppose that Ir<br />

for the motor = 45 A,<br />

the required setting is therefore 45 A;<br />

v if we use a 100/5 CT, the relay will<br />

never see 45 A because:<br />

100 • 0.6 = 60 > 45 A.<br />

v if on the other hand, we choose a<br />

CT 75/5, we will have:<br />

0.6 <<br />

45<br />

< 1.2<br />

75<br />

and therefore we will be able to set our<br />

relay. This CT is therefore suitable.<br />

If you do not know the exact values of ϕ and η,<br />

you can take as an initial approximation: cos ϕ = 0.8 ; η = 0.8.<br />

v capacitor feeder<br />

1.3 is a derating coefficient of 30% to take account of temperature rise<br />

due to capacitor harmonics.<br />

Ips =<br />

1.3 • Q<br />

e•U<br />

v bus sectioning<br />

The current Ips of the CT is the greatest value of current that can flow in<br />

the bus sectioning on a permanent basis.<br />

Rated primary current (Ipr)<br />

The rated current (Ipr) will always be greater than or equal to the<br />

operating current (I) for the installation.<br />

c Standardised values:<br />

10 -12.5 - 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 and their multiples<br />

and factors.<br />

c For metering and usual current-based protection devices, the rated<br />

primary current must not exceed 1.5 times the operating current.<br />

In the case of protection, we have to check that the chosen rated current<br />

enables the relay setting threshold to be reached in the case of a fault.<br />

N.B.: current transformers must be able to withstand 1.2 times the rated current on a constant<br />

basis and this as well must be in conformity with the standards.<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

55

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!