MV design guide - Schneider Electric
MV design guide - Schneider Electric
MV design guide - Schneider Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Switchgear<br />
definition<br />
Current transformer<br />
Primary operating current (Ips)<br />
An installation's primary operating current I (kA) (for a transformer<br />
feeder for example) is equal to the CT primary operating current (Ips)<br />
taking account of any possible derating.<br />
c If:<br />
S : apparent power in kVA<br />
U : primary operating voltage in kV<br />
P : active power of the motor in kW<br />
Q : reactive power of capacitors in kvars<br />
Ips : primary operating current in A<br />
c We will have:<br />
v incomer cubicle<br />
v generator set incomer<br />
v transformer feeder<br />
v motor feeder<br />
S<br />
Ips =<br />
e• U<br />
S<br />
Ips =<br />
e• U<br />
Ips =<br />
S<br />
e• U<br />
Ips =<br />
P<br />
e• U • cosϕ • η<br />
η : motor efficiency<br />
Example:<br />
A thermal protection device for a motor<br />
has a setting range of between 0.6 and<br />
1.2 • IrTC. In order to protect this motor,<br />
the required setting must correspond to<br />
the motor's rated current.<br />
c If we suppose that Ir<br />
for the motor = 45 A,<br />
the required setting is therefore 45 A;<br />
v if we use a 100/5 CT, the relay will<br />
never see 45 A because:<br />
100 • 0.6 = 60 > 45 A.<br />
v if on the other hand, we choose a<br />
CT 75/5, we will have:<br />
0.6 <<br />
45<br />
< 1.2<br />
75<br />
and therefore we will be able to set our<br />
relay. This CT is therefore suitable.<br />
If you do not know the exact values of ϕ and η,<br />
you can take as an initial approximation: cos ϕ = 0.8 ; η = 0.8.<br />
v capacitor feeder<br />
1.3 is a derating coefficient of 30% to take account of temperature rise<br />
due to capacitor harmonics.<br />
Ips =<br />
1.3 • Q<br />
e•U<br />
v bus sectioning<br />
The current Ips of the CT is the greatest value of current that can flow in<br />
the bus sectioning on a permanent basis.<br />
Rated primary current (Ipr)<br />
The rated current (Ipr) will always be greater than or equal to the<br />
operating current (I) for the installation.<br />
c Standardised values:<br />
10 -12.5 - 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 and their multiples<br />
and factors.<br />
c For metering and usual current-based protection devices, the rated<br />
primary current must not exceed 1.5 times the operating current.<br />
In the case of protection, we have to check that the chosen rated current<br />
enables the relay setting threshold to be reached in the case of a fault.<br />
N.B.: current transformers must be able to withstand 1.2 times the rated current on a constant<br />
basis and this as well must be in conformity with the standards.<br />
<strong>Schneider</strong> <strong>Electric</strong><br />
Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />
55