Switchgear<br />

definition<br />

Medium voltage circuit breaker<br />

Rated cable-charging breaking current<br />

(cf. § 4 .108 IEC 60 056)<br />

The specification of a rated breaking current for a circuit breaker located<br />

at the head of no-load cables is not compulsory and is considered as not<br />

being necessary for voltages less than 24 kV.<br />

c Normal rated breaking current values for a circuit breaker located at the<br />

head of no-load cables:<br />

Rated voltage<br />

(Ur in kV)<br />

(Ic in kA)<br />

7.2 10<br />

12 25<br />

17.5 31.5<br />

24 31.5<br />

36 50<br />

Rated breaking current<br />

for no-load cables<br />

Rated line-charging breaking current<br />

(cf. § 4.107 IEC 60 056)<br />

The specification of a rated breaking current for a circuit breaker switch<br />

situated at the head of no-load lines is limited to overhead, three-phased<br />

lines and to a rated voltage ≥ 72 kV.<br />

L<br />

A<br />

B<br />

Rated single capacitor bank breaking current<br />

(cf. § 4.109 IEC 60 056)<br />

G<br />

U<br />

Ic<br />

C<br />

The specification of a breaking current for a circuit breaker switch located<br />

upstream of capacitors is not compulsory. Due to the presence of<br />

harmonics, the breaking current for capacitors is equal to 0.7 times the<br />

device's rated current.<br />

Rated current Breaking current for capacitors<br />

(A)<br />

(A)<br />

400 280<br />

630 440<br />

1250 875<br />

2500 1750<br />

3150 2200<br />

By definition<br />

pu =<br />

r<br />

Ur<br />

e<br />

c The normal value of over-voltage obtained is equal to 2.5 pu, this being:<br />

X1<br />

2.5 • Ur r<br />

e<br />

G<br />

U<br />

Rated back-to-back capacitor bank breaking current<br />

(cf. § 4.110 IEC 60 056)<br />

The specification of a breaking current for multi-stage capacitor banks is<br />

not compulsory.<br />

c If n is equal to the number of stages, then the over-voltage is equal to:<br />

C1 C2 C3<br />

2n<br />

2n + 1<br />

• pu with pu =<br />

r<br />

Ur<br />

e<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

51