Switchgear<br />

definition<br />

Medium voltage circuit breaker<br />

IEC 60 056 and ANSI C37-06<br />

define on one hand the operating conditions,<br />

the rated characteristics, the <strong>design</strong> and<br />

the manufacture; and on the other hand<br />

the testing, the selection of controls<br />

and installation.<br />

Introduction<br />

c The circuit breaker is a device that ensures the control and protection<br />

on a network. It is capable of making, withstanding and interrupting<br />

operating currents as well as short-circuit currents.<br />

c The main circuit must be able to withstand without damage:<br />

v the thermal current = short-circuit current during 1 or 3 s<br />

v the electrodynamic current:<br />

2.5 • Isc for 50 Hz (IEC)<br />

2.6 • Isc for 60 Hz (IEC)<br />

2.7 • Isc (ANSI), for a particular time constant (IEC)<br />

v the constant load current.<br />

c Since a circuit breaker is mostly in the "closed" position, the load<br />

current must pass through it without the temperature running away<br />

throughout the equipment's life.<br />

Characteristics<br />

Compulsory rated characteristics<br />

c Rated voltage<br />

c Rated insulation level<br />

c Rated normal current<br />

c Rated short-time withstand current<br />

c Rated peak withstand current<br />

c Rated short-circuit duration<br />

c Rated supply voltage for opening and closing devices<br />

and auxiliary circuits<br />

c Rated frequency<br />

c Rated short-circuit breaking current<br />

c Rated transient recovery voltage<br />

c Rated short-circuit making current<br />

c Rated operating sequence<br />

c Rated time quantities.<br />

Special rated characteristics<br />

c These characteristics are not compulsory but can be requested for<br />

specific applications:<br />

v rated out-of-phase breaking current,<br />

v rated cable-charging breaking current,<br />

v rated line-charging breaking current,<br />

v rated capacitor bank breaking current,<br />

v rated back-to-back capacitor bank breaking current,<br />

v rated capacitor bank inrush making current,<br />

v rated small inductive breaking current.<br />

Rated voltage (cf. § 4.1 IEC 60 694)<br />

The rated voltage is the maximum rms. value of the voltage that the<br />

equipment can withstand in normal service. It is always greater than the<br />

operating voltage.<br />

c Standardised values for Ur (kV) : 3.6 - 7.2 -12 - 17.5 - 24 - 36 kV.<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

45