Design rules<br />

Dielectric withstand<br />

The shape of parts<br />

This plays a key role in switchgear dielectric withstand.<br />

It is essential to eliminate any "peak" effect which would have a disastrous<br />

effect on the impulse wave withstand in particular and on the surface<br />

ageing of insulators:<br />

Air ionization Ozone production Breakdown of moulded insulator surface skin<br />

Distance between parts<br />

Ambient air between live parts<br />

c For installations in which, for various reasons, we cannot test under<br />

impulse conditions, the table in publication IEC 71-2 gives, according to<br />

the rated lightning impulse withstand voltage, the minimum distances to<br />

comply with in air either phase to earth or phase to phase.<br />

V 0<br />

d<br />

c These distances guarantee correct withstand for unfavourable<br />

configurations: altitude < 1 000 m.<br />

c Distances in air* between conductive parts that are live and structures<br />

which are earthed giving a specified impulse withstand voltage under dry<br />

conditions:<br />

U<br />

Rated lightning<br />

impulse withstand<br />

voltage<br />

Up (kV)<br />

40 60<br />

60 90<br />

75 120<br />

95 160<br />

125 220<br />

Minimum distance<br />

in air phase<br />

to earth and phase<br />

to phase<br />

d (mm)<br />

The values for distances in air given in the table above are minimum<br />

values determined by considering dielectric properties, they do not<br />

include any increase which could be required to take account of <strong>design</strong><br />

tolerances, short circuit effects, wind effects, operator safety, etc.<br />

*These indications are relative to a distance through a single air gap, without taking account of<br />

the breakdown voltage by tracking across the surfaces, related to pollution problems.<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

39