KTB Nr. 2006-35-kj-en Collector test according to EN 12975-1,2:2006
KTB Nr. 2006-35-kj-en Collector test according to EN 12975-1,2:2006
KTB Nr. 2006-35-kj-en Collector test according to EN 12975-1,2:2006
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
8 Pressure drop<br />
The measurem<strong>en</strong>t of the pressure drop ∆p was carried out with water as<br />
fluid up <strong>to</strong> a flow rate of 969 kg/h.The inlet temperature of the water was<br />
20 ◦ C. The measurem<strong>en</strong>t has be<strong>en</strong> carried out up <strong>to</strong> the flow rate 969 kg/h.<br />
The reason for the high number of measurem<strong>en</strong>t points at a low flow rate is<br />
giv<strong>en</strong> by <strong>EN</strong> <strong>12975</strong>-2:<strong>2006</strong>. Five measurem<strong>en</strong>ts of differ<strong>en</strong>t flow rates in<br />
the range of 18 kg/h m 2 <strong>to</strong> 108 kg/h m 2 are necessary. The measurem<strong>en</strong>ts<br />
were performed up <strong>to</strong> a much higher value <strong>to</strong> increase the accuracy of the<br />
parameters. Also, these flow rates are closer <strong>to</strong> flow rates occuring in<br />
collec<strong>to</strong>r fields.<br />
18<br />
16<br />
14<br />
Pressure drop Δp [mbar]<br />
12<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
0 100 200 300 400 500 600 700 800 900 1000<br />
Mass flow [kg/h]<br />
Figure 5: Measured pressure drop of the collec<strong>to</strong>r<br />
The pressure drop ∆p in mbar can be described by the follwing function of<br />
the mass flow x in kg/h:<br />
∆p = 0.005 ∗ x + 1.187 ∗ 10 −5 ∗ x 2<br />
<strong>KTB</strong> <strong>Nr</strong>. <strong>2006</strong>-<strong>35</strong>-k-j-<strong>en</strong> : <strong>Collec<strong>to</strong>r</strong> <strong>test</strong> <strong>according</strong> <strong>to</strong> <strong>EN</strong> <strong>12975</strong>-1,2:<strong>2006</strong><br />
IMMERGAS S.p.A. , Series Collet<strong>to</strong>re Solare Piano CP4M and Collet<strong>to</strong>re Solare Piano CP2M<br />
04.07.2007, Fraunhofer-ISE, Heid<strong>en</strong>hofstraße 2, D-79110 Freiburg<br />
Page 18 of 37