24.01.2014 Views

MC – FRAME SIZE 1 / UP TO 160 A - Schrack

MC – FRAME SIZE 1 / UP TO 160 A - Schrack

MC – FRAME SIZE 1 / UP TO 160 A - Schrack

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>MC</strong> <strong>–</strong> <strong>FRAME</strong> <strong>SIZE</strong> 1 / <strong>UP</strong> <strong>TO</strong> <strong>160</strong> A<br />

W UNDERVOLTAGE RELEASE WITH TWO EARLY-MAKE AUXILIARY CONTACTS<br />

TYPE <strong>MC</strong>1-XUHIVL<br />

<strong>MC</strong>199565<br />

D1 3.13<br />

D2<br />

3.14<br />

W SCHRACK INFO<br />

• With 2 early-make auxiliary contacts<br />

• For early-make of the undervoltage release in main switch applications and<br />

for interlock- and load-shedding circuits<br />

• Installed in breaker<br />

• Other voltages and connection versions available on request<br />

W TIPS & TRICKS<br />

When the undervoltage release is de-energised, accidental contact with the main contacts of the switch is safely<br />

prevented during attempts to switch on. Early-make of auxiliary contacts during switch on and off (20 ms). Undervoltage<br />

release cannot be installed simultaneously with a shunt release or early-make auxiliary contact <strong>MC</strong>1-XHIV.<br />

VOLTAGE VERSION TYPE EAN CODE AVAILABLE ORDER NO.<br />

208 - 240 VAC incl. 3 m cable <strong>MC</strong>1-XUHIVL208-240 AC 9004840262421 <strong>MC</strong>199565<br />

380 - 440 VAC incl. 3 m cable <strong>MC</strong>1-XUHIVL380-440 AC 9004840262438 <strong>MC</strong>199567<br />

W UNDERVOLTAGE RELEASE, OFF-DELAY<br />

TYPES <strong>MC</strong>-UVU, <strong>MC</strong>-XUVL<br />

W SCHRACK INFO<br />

• Voltage drops of less than 16 s do not cause<br />

<strong>MC</strong>196154<br />

<strong>MC</strong>19<strong>160</strong>7<br />

U<br />

D1<br />

D2<br />

<strong>MC</strong> circuit breakers or <strong>MC</strong>-N load-break<br />

switches to trip.<br />

• Voltage range: 220-240 VAC 50/60 Hz<br />

380-440 VAC 50/60 HZ<br />

480-550 VAC 50/60 HZ<br />

24 VDC / AC<br />

• For dimensions, see from page 677.<br />

W TECHNICAL DATA<br />

• Time-delay adjustable between 70 ms <strong>–</strong> 4 s<br />

• With additional external capacitor:<br />

30,000 μF > 35 V up to 8 s<br />

90,000 μF > 35 V up to 16 s<br />

• Special release <strong>MC</strong>1-XUVL is required.<br />

• Cannot be installed simultaneously with early-make auxiliary<br />

contact <strong>MC</strong>1-XHIV... or shunt release <strong>MC</strong>1-XA....<br />

• Time-delay device for separate assembly<br />

(Mounting: DIN rail or screws).<br />

• Use control transformer for other operating voltages.<br />

DESCRIPTION TYPE EAN CODE AVAILABLE ORDER NO.<br />

Time delay device <strong>MC</strong>-UVU 9004840520392 <strong>MC</strong>190154<br />

Page<br />

603<br />

Special undervoltage release<br />

for time-delay device UVU <strong>MC</strong>1 XUVL 9004840520408 <strong>MC</strong>19<strong>160</strong>7<br />

Order no. blue: on stock, usually ready for delivery on the day of order!

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!