24.01.2014 Views

MC – FRAME SIZE 1 / UP TO 160 A - Schrack

MC – FRAME SIZE 1 / UP TO 160 A - Schrack

MC – FRAME SIZE 1 / UP TO 160 A - Schrack

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>MC</strong> <strong>–</strong> <strong>FRAME</strong> <strong>SIZE</strong> 1 / <strong>UP</strong> <strong>TO</strong> <strong>160</strong> A<br />

W RESIDUAL-CURRENT RELEASE RELAY<br />

TYPES <strong>MC</strong>1-XFI.R, <strong>MC</strong>1-4-XFI.R, <strong>MC</strong>1-XFI.U, <strong>MC</strong>1-4-XFI.U<br />

<strong>MC</strong>194608<br />

W SCHRACK-INFO<br />

• Suitable for use in three- and single-phase systems<br />

• Pulse current sensitive acc. to core-balance principle<br />

• For 3- and 4-pole circuit breakers and load-break switches <strong>MC</strong>1, <strong>MC</strong>1-N, not for <strong>MC</strong>1-PN<br />

• Dependant on mains power Ue = 200 <strong>–</strong> 415 V 50/60 Hz<br />

• Meets IEC/EN 60947-2<br />

• Bottom mounting up to 100 A, installed from the right up to 125 A<br />

• Complete unit<br />

• For dimensions, see from page 677.<br />

W TECHNICAL DATA<br />

• At I∆n = 0.03 A: Time delay tv permanently set to 10 ms.<br />

• Alarm message > 30 % Idn via yellow LED.<br />

• Trip-indicating auxiliary contacts can be fitted by user (max. 2 auxiliary contacts):<br />

NO: Order No: MM216376, NC: Order No: MM216378 are reset via a reset toggle lever.<br />

• When using the trip-indicating auxiliary contacts in the FI module, the NC contact works as an NO contact and the<br />

NO contact as an NC contact.<br />

• Not for use in XCS insulated enclosures.<br />

• Type <strong>MC</strong>1-XFI...U cannot be combined with shunt or undervoltage releases and an early-make auxiliary contact.<br />

• Rated short-circuit breaking capacity values are determined by installed <strong>MC</strong>1<br />

or when using a load-break switch <strong>MC</strong>1-N by the back-up fuse to be used.<br />

FOR TYPE RATED DELAY TYPE EAN CODE AVAILABLE ORDER NO.<br />

RESIDUAL CURRENT (I n )<br />

TIME (ms)<br />

3-POLE ATTACHMENT FROM THE RIGHT <strong>UP</strong> <strong>TO</strong> <strong>160</strong> A<br />

<strong>MC</strong>1/<strong>MC</strong>1-N 0.03 10 <strong>MC</strong>1-XFI30R 9004840507416 <strong>MC</strong>194603<br />

<strong>MC</strong>1/<strong>MC</strong>1-N 0.3 10 <strong>MC</strong>1-XFI300R 9004840507454 <strong>MC</strong>194604<br />

<strong>MC</strong>1/<strong>MC</strong>1-N 0.03-0.1-0.3-0.5-1-3 10, 60, 150, 300, 450 <strong>MC</strong>1-XFIR 9004840507478 <strong>MC</strong>194605<br />

4-POLE ATTACHMENT FROM THE RIGHT <strong>UP</strong> <strong>TO</strong> <strong>160</strong> A<br />

<strong>MC</strong>1-4 / <strong>MC</strong>1-N-4 0.03 10 <strong>MC</strong>1-4-XFI30R 9004840507447 <strong>MC</strong>194606<br />

<strong>MC</strong>1-4 / <strong>MC</strong>1-N-4 0.3 10 <strong>MC</strong>1-4-XFI300R 9004840507461 <strong>MC</strong>194607<br />

<strong>MC</strong>1-4 / <strong>MC</strong>1-N-4 0.03-0.1-0.3-0.5-1-3 10, 60, 150, 300, 450 <strong>MC</strong>1-4-XFIR 9004840507485 <strong>MC</strong>194608<br />

3-POLE ATTACHMENT FROM THE BOT<strong>TO</strong>M <strong>UP</strong> <strong>TO</strong> 100 A<br />

<strong>MC</strong>1/<strong>MC</strong>1-N 0.03 10 <strong>MC</strong>1-XFI30U 9004840587302 <strong>MC</strong>194609<br />

<strong>MC</strong>1/<strong>MC</strong>1-N 0.3 10 <strong>MC</strong>1-XFI300U 9004840587319 <strong>MC</strong>194610<br />

Page<br />

600<br />

<strong>MC</strong>1/<strong>MC</strong>1-N 0.03-0.1-0.3-0.5-1-3 10, 60, 150, 300, 450 <strong>MC</strong>1-XFIU 9004840587326 <strong>MC</strong>194611<br />

4-POLE ATTACHMENT FROM THE BOT<strong>TO</strong>M <strong>UP</strong> <strong>TO</strong> 100 A<br />

<strong>MC</strong>1-4 / <strong>MC</strong>1-N-4 0.03 10 <strong>MC</strong>1-4-XFI30U 9004840587333 <strong>MC</strong>194612<br />

<strong>MC</strong>1-4 / <strong>MC</strong>1-N-4 0.3 10 <strong>MC</strong>1-4-XFI300U 9004840587340 <strong>MC</strong>194613<br />

<strong>MC</strong>1-4 / <strong>MC</strong>1-N-4 0.03-0.1-0.3-0.5-1-3 10, 60, 150, 300, 450 <strong>MC</strong>1-4-XFIU 9004840587524 <strong>MC</strong>194614<br />

Order no. blue: on stock, usually ready for delivery on the day of order!