Technical details<br />

Installation of equipment in protection plates:<br />

Pre-drill the sections at the corners, then saw away the section from the<br />

protection plate by using a piercing saw at middle to low cutting speed.<br />

Use coarse toothed saw blades for plastics (e.g. Bosch T 101 B).<br />

<br />

Service<br />

Equipment for busbar supports:<br />

Rated<br />

busbar current<br />

<strong>Mi</strong> ST 25 <strong>Mi</strong> ST 41 <strong>Mi</strong> ST 63<br />

250 A 400 A 630 A<br />

L1, L2, L3 12x10 mm 20x10 mm 30x10 mm<br />

N 12x5 mm 12x10 mm 25x10 mm<br />

PE 12x5 mm 12x5 mm 12x10 mm<br />

Position of busbars<br />

Note:<br />

For containing short-circuit resistance the distance between<br />

busbar suppoerts must not exceed 300 mm.<br />

<br />

<br />

250 A 400 A 630 A<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

DK<br />

KV<br />

Busbar connector<br />

Note to <strong>Mi</strong> busbar boxes:<br />

Busbars 250 A and 400 A can only be connected with busbar<br />

connector <strong>Mi</strong> SV 25.<br />

Electrical figures<br />

Protection class: total insulation<br />

Rated voltage: AC 690 V, VDE 0110<br />

Overvoltage category: III<br />

Degree of pollution: 3<br />

Table:<br />

Rated current and short circuit resistance of busbars<br />

Rated<br />

current<br />

A<br />

Busbar<br />

crosssection<br />

mm<br />

Material<br />

Rated peak<br />

withstand<br />

current<br />

I pk<br />

kA cos ϕ<br />

250 12x10 Cu 30 0.3 300<br />

400 20x10 Cu 30 0.3 300<br />

630 30x10 Cu 45 0.3 300<br />

Distances<br />

between<br />

busbar<br />

supports<br />

max. mm<br />

<strong>Mi</strong><br />

MC<br />

LES<br />

Terminals for incoming cables<br />

2-5-pole, for Cu- and aluminium 1) wires, to be assembled i <strong>Mi</strong> empty boxes sizes 2 to 8, complete on<br />

mounting plates 300 x 300 mm, with fastening screws.<br />

Rated<br />

connecting<br />

capacity<br />

clamping<br />

(round)<br />

sol<br />

units<br />

per pole<br />

s<br />

(round)<br />

sol<br />

(sector)<br />

s<br />

(sector)<br />

outgoing<br />

wiring<br />

strip<br />

(C)<br />

current<br />

carrying<br />

capacity<br />

tightening<br />

torque<br />

<strong>Mi</strong> VE 120 4-pole 150 mm 2 2 (A) 16-50 16-150 50-150 35-150 <strong>Mi</strong> VS .. 250 A 20 Nm<br />

<strong>Mi</strong> VE 125 5-pole<br />

4 (B)<br />

16-50 16-70 50-70 35-70<br />

<strong>Mi</strong> VE 240 4-pole 240 mm 2 2 (A) 25-50 25-240 50-185 35-240 <strong>Mi</strong> VS .. 400 A 40 Nm<br />

<strong>Mi</strong> VE 245 5-pole<br />

4 (B)<br />

25-50 25-120 50-120 35-120<br />

<strong>Mi</strong> VE 302 2-pole 300 mm 2 2 (A) - 120-300 120-185 120-300 <strong>Mi</strong> VS 630 630 A 50 Nm<br />

<strong>Mi</strong> VE 303 3-pole 4 (B) 70 70-185 95-185 95-185<br />

<strong>Mi</strong> VE 304<br />

4-pole<br />

1) Prior to connection, aluminium conductors must be prepared according to the relevant technical recommendations.<br />

The connections must be checked at regular intervals and maintained after 6 months at the latest.<br />