Mi Distribution boards - IC SYSTEMS automatika
Mi Distribution boards - IC SYSTEMS automatika
Mi Distribution boards - IC SYSTEMS automatika
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Mi</strong> <strong>Distribution</strong> <strong>boards</strong> <br />
Technical details<br />
Installation of equipment in protection plates:<br />
Pre-drill the sections at the corners, then saw away the section from the<br />
protection plate by using a piercing saw at middle to low cutting speed.<br />
Use coarse toothed saw blades for plastics (e.g. Bosch T 101 B).<br />
<br />
Service<br />
Equipment for busbar supports:<br />
Rated<br />
busbar current<br />
<strong>Mi</strong> ST 25 <strong>Mi</strong> ST 41 <strong>Mi</strong> ST 63<br />
250 A 400 A 630 A<br />
L1, L2, L3 12x10 mm 20x10 mm 30x10 mm<br />
N 12x5 mm 12x10 mm 25x10 mm<br />
PE 12x5 mm 12x5 mm 12x10 mm<br />
Position of busbars<br />
Note:<br />
For containing short-circuit resistance the distance between<br />
busbar suppoerts must not exceed 300 mm.<br />
<br />
<br />
250 A 400 A 630 A<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
DK<br />
KV<br />
Busbar connector<br />
Note to <strong>Mi</strong> busbar boxes:<br />
Busbars 250 A and 400 A can only be connected with busbar<br />
connector <strong>Mi</strong> SV 25.<br />
Electrical figures<br />
Protection class: total insulation<br />
Rated voltage: AC 690 V, VDE 0110<br />
Overvoltage category: III<br />
Degree of pollution: 3<br />
Table:<br />
Rated current and short circuit resistance of busbars<br />
Rated<br />
current<br />
A<br />
Busbar<br />
crosssection<br />
mm<br />
Material<br />
Rated peak<br />
withstand<br />
current<br />
I pk<br />
kA cos ϕ<br />
250 12x10 Cu 30 0.3 300<br />
400 20x10 Cu 30 0.3 300<br />
630 30x10 Cu 45 0.3 300<br />
Distances<br />
between<br />
busbar<br />
supports<br />
max. mm<br />
<strong>Mi</strong><br />
MC<br />
LES<br />
Terminals for incoming cables<br />
2-5-pole, for Cu- and aluminium 1) wires, to be assembled i <strong>Mi</strong> empty boxes sizes 2 to 8, complete on<br />
mounting plates 300 x 300 mm, with fastening screws.<br />
Rated<br />
connecting<br />
capacity<br />
clamping<br />
(round)<br />
sol<br />
units<br />
per pole<br />
s<br />
(round)<br />
sol<br />
(sector)<br />
s<br />
(sector)<br />
outgoing<br />
wiring<br />
strip<br />
(C)<br />
current<br />
carrying<br />
capacity<br />
tightening<br />
torque<br />
<strong>Mi</strong> VE 120 4-pole 150 mm 2 2 (A) 16-50 16-150 50-150 35-150 <strong>Mi</strong> VS .. 250 A 20 Nm<br />
<strong>Mi</strong> VE 125 5-pole<br />
4 (B)<br />
16-50 16-70 50-70 35-70<br />
<strong>Mi</strong> VE 240 4-pole 240 mm 2 2 (A) 25-50 25-240 50-185 35-240 <strong>Mi</strong> VS .. 400 A 40 Nm<br />
<strong>Mi</strong> VE 245 5-pole<br />
4 (B)<br />
25-50 25-120 50-120 35-120<br />
<strong>Mi</strong> VE 302 2-pole 300 mm 2 2 (A) - 120-300 120-185 120-300 <strong>Mi</strong> VS 630 630 A 50 Nm<br />
<strong>Mi</strong> VE 303 3-pole 4 (B) 70 70-185 95-185 95-185<br />
<strong>Mi</strong> VE 304<br />
4-pole<br />
1) Prior to connection, aluminium conductors must be prepared according to the relevant technical recommendations.<br />
The connections must be checked at regular intervals and maintained after 6 months at the latest.<br />
177<br />
HENPAS<br />
Technics<br />
References/Types