Rated power dissipation of empty boxes<br />
The following table indicates the maximum rated power dissipation<br />
for any empty boxes. A difference is made between single<br />
boxes with lateral, frontal and rear radiation, an equipment with<br />
frontal and rear radiation.<br />
Box type<br />
174<br />
External<br />
dimensions<br />
W x H x D<br />
in mm<br />
Power dissipation (W/box)<br />
single box<br />
<strong>Mi</strong> 0100 300x150x170 25 18<br />
<strong>Mi</strong> 0101 300x150x170 25 18<br />
<strong>Mi</strong> 0200 300x300x170 40 32<br />
<strong>Mi</strong> 0201 300x300x170 40 32<br />
<strong>Mi</strong> 0210 300x300x214 46 38<br />
<strong>Mi</strong> 0211 300x300x214 46 38<br />
<strong>Mi</strong> 0220 300x300x182 40 32<br />
<strong>Mi</strong> 0221 300x300x182 40 32<br />
<strong>Mi</strong> 0300 300x450x170 53 45<br />
<strong>Mi</strong> 0301 300x450x170 53 45<br />
<strong>Mi</strong> 0310 300x450x214 65 53<br />
<strong>Mi</strong> 0311 300x450x214 65 53<br />
<strong>Mi</strong> 0400 300x600x170 70 58<br />
<strong>Mi</strong> 0401 300x600x170 70 58<br />
<strong>Mi</strong> 0410 300x600x214 82 60<br />
<strong>Mi</strong> 0411 300x600x214 82 60<br />
<strong>Mi</strong> 0400 +<br />
<strong>Mi</strong> ZR 4<br />
<strong>Mi</strong> 0401 +<br />
<strong>Mi</strong> ZR 4<br />
300x600x255 85 60<br />
300x600x255 85 60<br />
<strong>Mi</strong> 0800 600x600x170 120 98<br />
<strong>Mi</strong> 0801 600x600x170 120 98<br />
<strong>Mi</strong> 0800 +<br />
<strong>Mi</strong> ZR 8<br />
<strong>Mi</strong> 0801 +<br />
<strong>Mi</strong> ZR 8<br />
600x600x255 142 120<br />
600x600x255 142 120<br />
in assemblies<br />
The values indicated refer to the ambient temperature of 25° C<br />
and an interior temperature of 55° C.<br />
For the nominal load factor the square dependence of the power<br />
dissipation from the current shall be taken into consideration.<br />
Rated current and short circuit resistance<br />
of busbars<br />
Rated<br />
current<br />
A<br />
busbar<br />
crosssection<br />
mm<br />
Material<br />
Rated peak<br />
withstand<br />
current<br />
I pk<br />
kA cos ϕ<br />
250 12x10 Cu 30 0,3 300<br />
400 20x10 Cu 30 0,3 300<br />
630 30x10 Cu 45 0,3 300<br />
distances<br />
between<br />
busbar<br />
supports<br />
max. mm<br />
<strong>Mi</strong>-distribution <strong>boards</strong> comply with the requirements for<br />
type-tested switchgear and controlgear assemblies (TTA)<br />
in accordance with IEC 60 439-1/EN 60 439-1.<br />
Type-tested switchgear assemblies are switchgear and controlgear<br />
assemblies which are assembled and wired according to<br />
manufacturer data without essential deviations from the original<br />
type or system.<br />
To meet these requirements for Hensel <strong>Mi</strong> <strong>Distribution</strong> <strong>boards</strong>,<br />
the following must be noted:<br />
1. The switchgear must consist of the type-tested enclosures<br />
documented in this list.<br />
2. The wiring of the equipment must be carried out with the<br />
cross-sections and conductor types indicated in Table<br />
„Rating of insulated conductors in switchgear assemblies“,<br />
Index Technics, page 212.<br />
3. Once the switchgear is completed, a routine test must be<br />
carried out in accordance with this standard.<br />
4. The test must be certified with a test report.<br />
5. The switchgear must be provided with a manufacturer’s<br />
identification mark.<br />
Compliance with important data such as<br />
- limit of temperature rise<br />
- dielectric strength<br />
- short-circuit withstand capacity<br />
- short-circuit withstand capacity of the PE conductor<br />
- IP degrees of protection<br />
- creepage distances and clearances<br />
is verified by type tests for this system.<br />
<strong>Mi</strong>-distribution <strong>boards</strong> comply with the following standards<br />
and requirements:<br />
- IEC 60 439-1 / EN 60 439-1<br />
Low voltage swichgear and control gear assemblies<br />
- IEC 999 and EN 60 999<br />
Safety requirements for screw-type and screwless-type<br />
clamping units for electrical copper conductors<br />
- EN 50 262<br />
Metric threaded cable glands for electrical installations<br />
- IEC 269<br />
Low voltage fuses<br />
- DIN 43 880<br />
Built-in equipment for electrical installations;<br />
overall dimensions and related mounting dimensions<br />
- IEC 60 529<br />
Degrees of protection provided by enclosures (IP-Code)<br />
Approvals:<br />
EZU Czech Republic<br />
MEEI Hungary