<strong>Mi</strong> <strong>Distribution</strong> <strong>boards</strong> <br />

Technical details<br />

References/Types Technics HENPAS<br />

LES<br />

MC<br />

<strong>Mi</strong><br />

KV<br />

DK<br />

Service<br />

Rated power dissipation of empty boxes<br />

The following table indicates the maximum rated power dissipation<br />

for any empty boxes. A difference is made between single<br />

boxes with lateral, frontal and rear radiation, an equipment with<br />

frontal and rear radiation.<br />

Box type<br />

174<br />

External<br />

dimensions<br />

W x H x D<br />

in mm<br />

Power dissipation (W/box)<br />

single box<br />

<strong>Mi</strong> 0100 300x150x170 25 18<br />

<strong>Mi</strong> 0101 300x150x170 25 18<br />

<strong>Mi</strong> 0200 300x300x170 40 32<br />

<strong>Mi</strong> 0201 300x300x170 40 32<br />

<strong>Mi</strong> 0210 300x300x214 46 38<br />

<strong>Mi</strong> 0211 300x300x214 46 38<br />

<strong>Mi</strong> 0220 300x300x182 40 32<br />

<strong>Mi</strong> 0221 300x300x182 40 32<br />

<strong>Mi</strong> 0300 300x450x170 53 45<br />

<strong>Mi</strong> 0301 300x450x170 53 45<br />

<strong>Mi</strong> 0310 300x450x214 65 53<br />

<strong>Mi</strong> 0311 300x450x214 65 53<br />

<strong>Mi</strong> 0400 300x600x170 70 58<br />

<strong>Mi</strong> 0401 300x600x170 70 58<br />

<strong>Mi</strong> 0410 300x600x214 82 60<br />

<strong>Mi</strong> 0411 300x600x214 82 60<br />

<strong>Mi</strong> 0400 +<br />

<strong>Mi</strong> ZR 4<br />

<strong>Mi</strong> 0401 +<br />

<strong>Mi</strong> ZR 4<br />

300x600x255 85 60<br />

300x600x255 85 60<br />

<strong>Mi</strong> 0800 600x600x170 120 98<br />

<strong>Mi</strong> 0801 600x600x170 120 98<br />

<strong>Mi</strong> 0800 +<br />

<strong>Mi</strong> ZR 8<br />

<strong>Mi</strong> 0801 +<br />

<strong>Mi</strong> ZR 8<br />

600x600x255 142 120<br />

600x600x255 142 120<br />

in assemblies<br />

The values indicated refer to the ambient temperature of 25° C<br />

and an interior temperature of 55° C.<br />

For the nominal load factor the square dependence of the power<br />

dissipation from the current shall be taken into consideration.<br />

Rated current and short circuit resistance<br />

of busbars<br />

Rated<br />

current<br />

A<br />

busbar<br />

crosssection<br />

mm<br />

Material<br />

Rated peak<br />

withstand<br />

current<br />

I pk<br />

kA cos ϕ<br />

250 12x10 Cu 30 0,3 300<br />

400 20x10 Cu 30 0,3 300<br />

630 30x10 Cu 45 0,3 300<br />

distances<br />

between<br />

busbar<br />

supports<br />

max. mm<br />

<strong>Mi</strong>-distribution <strong>boards</strong> comply with the requirements for<br />

type-tested switchgear and controlgear assemblies (TTA)<br />

in accordance with IEC 60 439-1/EN 60 439-1.<br />

Type-tested switchgear assemblies are switchgear and controlgear<br />

assemblies which are assembled and wired according to<br />

manufacturer data without essential deviations from the original<br />

type or system.<br />

To meet these requirements for Hensel <strong>Mi</strong> <strong>Distribution</strong> <strong>boards</strong>,<br />

the following must be noted:<br />

1. The switchgear must consist of the type-tested enclosures<br />

documented in this list.<br />

2. The wiring of the equipment must be carried out with the<br />

cross-sections and conductor types indicated in Table<br />

„Rating of insulated conductors in switchgear assemblies“,<br />

Index Technics, page 212.<br />

3. Once the switchgear is completed, a routine test must be<br />

carried out in accordance with this standard.<br />

4. The test must be certified with a test report.<br />

5. The switchgear must be provided with a manufacturer’s<br />

identification mark.<br />

Compliance with important data such as<br />

- limit of temperature rise<br />

- dielectric strength<br />

- short-circuit withstand capacity<br />

- short-circuit withstand capacity of the PE conductor<br />

- IP degrees of protection<br />

- creepage distances and clearances<br />

is verified by type tests for this system.<br />

<strong>Mi</strong>-distribution <strong>boards</strong> comply with the following standards<br />

and requirements:<br />

- IEC 60 439-1 / EN 60 439-1<br />

Low voltage swichgear and control gear assemblies<br />

- IEC 999 and EN 60 999<br />

Safety requirements for screw-type and screwless-type<br />

clamping units for electrical copper conductors<br />

- EN 50 262<br />

Metric threaded cable glands for electrical installations<br />

- IEC 269<br />

Low voltage fuses<br />

- DIN 43 880<br />

Built-in equipment for electrical installations;<br />

overall dimensions and related mounting dimensions<br />

- IEC 60 529<br />

Degrees of protection provided by enclosures (IP-Code)<br />

Approvals:<br />

EZU Czech Republic<br />

MEEI Hungary