146 <strong>Technical</strong> data<br />
Circuit-breakers<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Current limiting specifications: NZML2... and NZML3...<br />
Moeller SK1230-1157GB-INT<br />
Circuit-breakers Voltage Threshold current Intermediate current High interrupting capacity<br />
Type max.<br />
Maximum Maximum Maximum<br />
frame size At 60 Hz sym. rms Peak I 2 dt sym. rms Peak I 2 dt sym. rms Peak I 2 dt<br />
[A] [V] [kA] [kA] [kA 2 s] [kA] [kA] [kA 2 s] [kA] [kA] [kA 2 s]<br />
NZML2- 250 A 240 16,25 12,80 0,36 100 20,23 0,40 150 20,00 0,38<br />
A... 480 16,25 13,20 0,50 65 23,63 0,85 100 26,55 0,78<br />
AF... 600 16,25 12,98 0,60 30 19,40 0,67 50 24,40 0,84<br />
NZML2- 250 A 240 16,25 11,40 0,31 100 18,23 0,27 150 20,40 0,32<br />
VE... 480 16,25 14,23 0,48 65 23,63 0,58 100 26,43 0,62<br />
VEF... 600 16,25 14,33 0,48 30 19,60 0,60 50 24,63 0,79<br />
NZML3 600 A 240 39 41,20 3,30 100 31,00 1,01 150 36,80 1,34<br />
480 39 29,50 1,60 65 36,40 2,34 100 43,10 1,92<br />
600 30 29,50 2,24 42 33,80 2,04 50 39,15 2,42