Technical Data - IC SYSTEMS automatika
Technical Data - IC SYSTEMS automatika
Technical Data - IC SYSTEMS automatika
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Circuit-breakers, switch-disconnectors<br />
Earth-fault release<br />
121<br />
Moeller SK1230-1157GB-INT<br />
Earth-fault release<br />
not UL/CSA approved<br />
Suitability for use in three- and single-phase systems<br />
Pulse current sensitive acc. to core-balance principle<br />
For use with<br />
For 3 and 4 pole circuit-breakers NZM1(-4) and switch-disconnectors N1(-4),<br />
dependant on mains power U ε = 200 – 415 V 50/60 Hz, lateral mounting on the<br />
right hand side up to 125 A<br />
Rated fault current<br />
I Dn = 0.03 A<br />
Rated fault current<br />
I Dn = 0.3 A<br />
Rated fault current<br />
I Dn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A,<br />
delay time<br />
t v = 10 – 60 – 150 – 300 – 450 ms.<br />
Bottom mounting up to 100 A<br />
Rated fault current<br />
I Dn = 0.03 A<br />
Rated fault current<br />
I Dn = 0.3 A<br />
Rated fault current<br />
I Dn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A,<br />
delay time<br />
t v = 10 – 60 – 150 – 300 – 450 ms.<br />
NZM1<br />
N1<br />
NZM1-4<br />
N1-4<br />
NZM1<br />
N1<br />
NZM1-4<br />
N1-4<br />
NZM1<br />
N1<br />
NZM1-4<br />
N1-4<br />
NZM1<br />
N1<br />
NZM1-4<br />
N1-4<br />
NZM1<br />
N1<br />
NZM1-4<br />
N1-4<br />
NZM1<br />
N1<br />
NZM1-4<br />
N1-4<br />
Part no.<br />
Order number for<br />
separate orders<br />
3 pole NZM1-XFI30R 1)<br />
104603<br />
4 pole NZM1-4-XFI30R<br />
104606<br />
3 pole NZM1-XFI300R 1)<br />
104604<br />
4 pole NZM1-4-XFI300R<br />
104607<br />
3 pole NZM1-XFIR 1)<br />
104605<br />
4 pole NZM1-4-XFIR<br />
104608<br />
3 pole NZM1-XFI30U<br />
104609<br />
4 pole NZM1-4-XFI30U 1)<br />
104612<br />
3 pole NZM1-XFI300U 1)<br />
104610<br />
4 pole NZM1-4-XFI300U 1)<br />
104613<br />
3 pole NZM1-XFIU<br />
104611<br />
4 pole NZM1-4-XFIU<br />
104614<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
1 off XFI30R suitable for personnel<br />
protection to IEC/EN 60947-2<br />
Annex B and EN 61009-1<br />
(VDE 0664-20).<br />
With I dn = 0.03 A: delay time t v<br />
always fixed setting at 10 ms.<br />
Alarm message > 30% I dn via yellow<br />
LED.<br />
Trip indication max. 2 auxiliary<br />
contacts can be fitted by user:<br />
N/O = M22-K01, N/C = M22-K10 are<br />
reset via the reset toggle lever.<br />
Not in combination with insulated<br />
enclosure.<br />
NZM1-XFI...U not in combination<br />
with shunt or undervoltage release.<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Pulse current sensitive acc. to core-balance principle<br />
For 4 pole circuit-breakers NZM2-4 and switch-disconnectors N2-4,<br />
independent of mains voltage U e = 280 – 690 V 50/60 Hz, bottom mounting<br />
up to 250 A<br />
Rated fault current<br />
I Dn = 0.03 A<br />
Rated fault current<br />
I Dn 0.1 - 0.3 - 1 - 3 A,<br />
delay time<br />
t v = 60 - 150 - 300 - 450 ms<br />
NZM2-4<br />
N2-4<br />
NZM2-4<br />
N2-4<br />
4 pole NZM2-4-XFI30<br />
292343<br />
4 pole NZM2-4-XFI<br />
292344<br />
1 off XFI30 suitable for personnel<br />
protection to IEC/EN 60947-2<br />
1 off Annex B and EN 61009-1<br />
(VDE 0664-20).<br />
Auxiliary contacts (1 N/O, 1 N/C<br />
integrated) are reset via the reset<br />
button.<br />
Not in combination with plug-in<br />
Core-balance principle with AC/DC current sensitivity (in range 0 – 100 kHz)<br />
For 4 pole circuit-breakers NZM2-4 and switch-disconnectors N2-4,<br />
internal power supply U e = 50 – 400 V, bottom mounting up to 250 A<br />
Rated fault current<br />
I Dn = 0.03 A<br />
Rated fault current<br />
I Dn 0.1 - 0.3 - 1 A,<br />
delay time<br />
t v = 60 - 150 - 300 - 450 ms<br />
NZM2-4<br />
N2-4<br />
NZM2-4<br />
N2-4<br />
4 pole NZM2-4-XFIA30<br />
292345<br />
4 pole NZM2-4-XFIA<br />
292346<br />
1 off XFIA30 suitable for personnel<br />
protection to IEC/EN 60947-2<br />
Annex B and EN 61009-1<br />
(VDE 0664-20).<br />
1 off Observe response threshold<br />
dependence on frequency!<br />
See “Frequency response”<br />
characteristic curve<br />
Auxiliary contacts (1 N/O, 1 N/C<br />
integrated) are reset via the reset<br />
button.<br />
Notes<br />
1) on request