Circuit-breakers, switch-disconnectors<br />

Earth-fault release<br />

121<br />

Moeller SK1230-1157GB-INT<br />

Earth-fault release<br />

not UL/CSA approved<br />

Suitability for use in three- and single-phase systems<br />

Pulse current sensitive acc. to core-balance principle<br />

For use with<br />

For 3 and 4 pole circuit-breakers NZM1(-4) and switch-disconnectors N1(-4),<br />

dependant on mains power U ε = 200 – 415 V 50/60 Hz, lateral mounting on the<br />

right hand side up to 125 A<br />

Rated fault current<br />

I Dn = 0.03 A<br />

Rated fault current<br />

I Dn = 0.3 A<br />

Rated fault current<br />

I Dn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A,<br />

delay time<br />

t v = 10 – 60 – 150 – 300 – 450 ms.<br />

Bottom mounting up to 100 A<br />

Rated fault current<br />

I Dn = 0.03 A<br />

Rated fault current<br />

I Dn = 0.3 A<br />

Rated fault current<br />

I Dn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A,<br />

delay time<br />

t v = 10 – 60 – 150 – 300 – 450 ms.<br />

NZM1<br />

N1<br />

NZM1-4<br />

N1-4<br />

NZM1<br />

N1<br />

NZM1-4<br />

N1-4<br />

NZM1<br />

N1<br />

NZM1-4<br />

N1-4<br />

NZM1<br />

N1<br />

NZM1-4<br />

N1-4<br />

NZM1<br />

N1<br />

NZM1-4<br />

N1-4<br />

NZM1<br />

N1<br />

NZM1-4<br />

N1-4<br />

Part no.<br />

Order number for<br />

separate orders<br />

3 pole NZM1-XFI30R 1)<br />

104603<br />

4 pole NZM1-4-XFI30R<br />

104606<br />

3 pole NZM1-XFI300R 1)<br />

104604<br />

4 pole NZM1-4-XFI300R<br />

104607<br />

3 pole NZM1-XFIR 1)<br />

104605<br />

4 pole NZM1-4-XFIR<br />

104608<br />

3 pole NZM1-XFI30U<br />

104609<br />

4 pole NZM1-4-XFI30U 1)<br />

104612<br />

3 pole NZM1-XFI300U 1)<br />

104610<br />

4 pole NZM1-4-XFI300U 1)<br />

104613<br />

3 pole NZM1-XFIU<br />

104611<br />

4 pole NZM1-4-XFIU<br />

104614<br />

Price<br />

see price<br />

list<br />

Std. pack<br />

Notes<br />

1 off XFI30R suitable for personnel<br />

protection to IEC/EN 60947-2<br />

Annex B and EN 61009-1<br />

(VDE 0664-20).<br />

With I dn = 0.03 A: delay time t v<br />

always fixed setting at 10 ms.<br />

Alarm message > 30% I dn via yellow<br />

LED.<br />

Trip indication max. 2 auxiliary<br />

contacts can be fitted by user:<br />

N/O = M22-K01, N/C = M22-K10 are<br />

reset via the reset toggle lever.<br />

Not in combination with insulated<br />

enclosure.<br />

NZM1-XFI...U not in combination<br />

with shunt or undervoltage release.<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Pulse current sensitive acc. to core-balance principle<br />

For 4 pole circuit-breakers NZM2-4 and switch-disconnectors N2-4,<br />

independent of mains voltage U e = 280 – 690 V 50/60 Hz, bottom mounting<br />

up to 250 A<br />

Rated fault current<br />

I Dn = 0.03 A<br />

Rated fault current<br />

I Dn 0.1 - 0.3 - 1 - 3 A,<br />

delay time<br />

t v = 60 - 150 - 300 - 450 ms<br />

NZM2-4<br />

N2-4<br />

NZM2-4<br />

N2-4<br />

4 pole NZM2-4-XFI30<br />

292343<br />

4 pole NZM2-4-XFI<br />

292344<br />

1 off XFI30 suitable for personnel<br />

protection to IEC/EN 60947-2<br />

1 off Annex B and EN 61009-1<br />

(VDE 0664-20).<br />

Auxiliary contacts (1 N/O, 1 N/C<br />

integrated) are reset via the reset<br />

button.<br />

Not in combination with plug-in<br />

Core-balance principle with AC/DC current sensitivity (in range 0 – 100 kHz)<br />

For 4 pole circuit-breakers NZM2-4 and switch-disconnectors N2-4,<br />

internal power supply U e = 50 – 400 V, bottom mounting up to 250 A<br />

Rated fault current<br />

I Dn = 0.03 A<br />

Rated fault current<br />

I Dn 0.1 - 0.3 - 1 A,<br />

delay time<br />

t v = 60 - 150 - 300 - 450 ms<br />

NZM2-4<br />

N2-4<br />

NZM2-4<br />

N2-4<br />

4 pole NZM2-4-XFIA30<br />

292345<br />

4 pole NZM2-4-XFIA<br />

292346<br />

1 off XFIA30 suitable for personnel<br />

protection to IEC/EN 60947-2<br />

Annex B and EN 61009-1<br />

(VDE 0664-20).<br />

1 off Observe response threshold<br />

dependence on frequency!<br />

See “Frequency response”<br />

characteristic curve<br />

Auxiliary contacts (1 N/O, 1 N/C<br />

integrated) are reset via the reset<br />

button.<br />

Notes<br />