Circuit-breakers, switch-disconnectors<br />
NZM4 terminals<br />
Circuit-breakers, switch-disconnectors<br />
NZM4 terminals<br />
111<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Max. cable connection area<br />
Moeller SK1230-1157GB-INT<br />
Moeller SK1230-1157GB-INT<br />
Rated For use with Terminal capacities Terminal capacities Part no.<br />
current 1) Article no.<br />
Type of conductor Terminal<br />
capacities<br />
AWG/kcmil<br />
Cu strip<br />
(number of segments x<br />
Copper busbar<br />
width x thickness<br />
I n<br />
A<br />
width x segment thickness)<br />
mm 2 mm mm<br />
Flat cable terminal<br />
– Max. 1100 NZM4, N(S)4 3 pole Min. 6 x 16 x 0.8<br />
Max. 20 x 32 x 0.5<br />
– NZM4-4, N(S)4-4 4 pole Min. 6 x 16 x 0.8<br />
Max. 20 x 32 x 0.5<br />
when ordered<br />
separately<br />
NZM4-XKB<br />
266829<br />
NZM4-4-XKB<br />
266831<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
1 off Type contains parts for a terminal located at top or<br />
bottom for 3 or 4-pole circuit-breakers.<br />
1 off Conversion kit for circuit-breaker with screw connection.<br />
Insulation through cover NZM4(-4)-XKSA or phase<br />
isolator NZM4(4)-XKP necessary.<br />
With switch mpunting on conductive mounting plates use<br />
of the shroud NZM4(-4)-XKSA necessary (supplied item).<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Tunnel terminal<br />
– Max. 1400 NZM4, N(S)4 3 pole Copper cablesS<br />
Al cable s S<br />
– NZM4-4,<br />
N(S)4-4<br />
1 x 50 – 240<br />
4 x 50 – 240<br />
1 x 50 – 240<br />
4 x 50 – 240<br />
1 x 0 – 500<br />
4 x 0 – 500<br />
NZM4-XKA<br />
266836<br />
4 pole NZM4-4-XKA<br />
266837<br />
1 off Type contains parts for a terminal located at top or<br />
bottom for 3 or 4-pole circuit-breakers.<br />
1 off A standard with control circuit terminal for<br />
1 x 0.75 – 2.5 mm 2 (18 – 14 AWG) or 2 x 0.75 – 1.5 mm 2<br />
(18 – 16 AWG) copper conductors.<br />
Can be fitted to circuit-breaker with screw termination<br />
Use with flexible and highly flexible conductors ferrules.<br />
Mounting of the cover NZM4 (-4)-XKSA obligatory<br />
(supplied).<br />
Connection on rear<br />
not UL/CSA approved<br />
– Max. 1250 NZM4-4,<br />
N4-4<br />
Threeand<br />
fourpole<br />
Copper cable lugs<br />
Aluminium<br />
cable lugs<br />
1 x 120 – 185<br />
2 x 95 – 185<br />
4 x 35 – 185<br />
1 x 185<br />
2 x 70 – 185<br />
4 x 50 – 185<br />
NZM4-XKR<br />
266842<br />
– Max. 1600 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 NZM4-4-XKR<br />
266843<br />
1 off Type contains parts for a terminal located at top or<br />
bottom for 3 or 4-pole circuit-breakers.<br />
Can also be retrofitted:<br />
NZM4...-XKM... module plate or NZM4-...-XKV...<br />
connection width extension<br />
1 off<br />
NZM4/NZM14 adapter kit<br />
not UL/CSA approved<br />
– Max. 1250 NZM4, N4 3 pole NZM4-XAS14-1250<br />
283291<br />
– Max. 1600 NZM4, N4 3 pole NZM4-XAS14-1600<br />
283292<br />
1 off Conversion kit from NZM14 to NZM4. Same connection<br />
schematic as NZM14. Type contains parts for both switch<br />
sides.<br />
3 connection extensions on outlet side.<br />
3 connection extensions on trip block side.<br />
1 long shroud for the outlet side<br />
1 off<br />
Paper drilling template in the installation instructions<br />
(AWA)<br />
Cannot be combined with the module plate<br />
(NZM4-XKM...), flat cable terminal (NZM4-XKB),<br />
connection width extension (NZM4-XKV...), tunnel<br />
terminal (NZM4-XKA), connection on rear<br />
(NZM4-XKR) and withdrawable unit (NZM4-XAV...).<br />
Notes<br />
1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to<br />
the max. defined cross-sections and are intended for the purpose of orientation.<br />
The engineering standards which apply in each case must be observed.