74<br />

Circuit-breakers, switch-disconnectors<br />

Shunt releases with screw terminal<br />

Circuit-breakers, switch-disconnectors<br />

Shunt releases with springloaded terminal<br />

75<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Shunt releases<br />

With early-make auxiliary contact<br />

For mesh-network circuit-breakers<br />

For intermittent operation<br />

Maximum on time = 1 s<br />

Operating range 10 – 110 % U s<br />

not UL/CSA approved<br />

C1<br />

C2<br />

3.13<br />

3.14<br />

Moeller SK1230-1157GB-INT<br />

For use with Rated control voltage<br />

U s<br />

Part no.<br />

Article no.<br />

when ordered separately<br />

V<br />

NZM3(-4), N3(-4) 230 V AC NZM3-XAHIV-230AC-MNS<br />

274141<br />

Moeller SK1230-1157GB-INT<br />

C1<br />

C2<br />

3.13<br />

3.14<br />

Part no.<br />

Article no.<br />

when ordered separately<br />

NZM3-XAHIVC-230AC-MNS<br />

274142<br />

Price<br />

see price<br />

list<br />

Std. pack<br />

Notes<br />

1 off Cannot be installed simultaneously with NZM...-XHIV... earlymake<br />

auxiliary contact or NZM...-XU... undervoltage release.<br />

Cannot be used in conjunction with NZM...-XR... remote<br />

operator.<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

C1<br />

C2<br />

3.13<br />

3.14<br />

NZM4(-4), N4(-4) 230 V AC NZM4-XAHIV-230AC-MNS<br />

274143<br />

C1<br />

C2<br />

3.13<br />

3.14<br />

NZM4-XAHIVC-230AC-MNS<br />

274144<br />

1 off<br />

Intermittent operation guaranteed by series connection of a<br />

N/O contact M22-(C)K10 (standard auxiliary contact).<br />

The maximum operating time of the shunt release for mesh<br />

network circuit-breaker is 1 s.<br />

NZM3: Early-make of the auxiliary contact with on and off<br />

switching (manual operation): approx. 20 ms.<br />

NZM4: Early-make of the auxiliary contact with switch on<br />

(manual operation): approx. 90 ms.