74<br />
Circuit-breakers, switch-disconnectors<br />
Shunt releases with screw terminal<br />
Circuit-breakers, switch-disconnectors<br />
Shunt releases with springloaded terminal<br />
75<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Shunt releases<br />
With early-make auxiliary contact<br />
For mesh-network circuit-breakers<br />
For intermittent operation<br />
Maximum on time = 1 s<br />
Operating range 10 – 110 % U s<br />
not UL/CSA approved<br />
C1<br />
C2<br />
3.13<br />
3.14<br />
Moeller SK1230-1157GB-INT<br />
For use with Rated control voltage<br />
U s<br />
Part no.<br />
Article no.<br />
when ordered separately<br />
V<br />
NZM3(-4), N3(-4) 230 V AC NZM3-XAHIV-230AC-MNS<br />
274141<br />
Moeller SK1230-1157GB-INT<br />
C1<br />
C2<br />
3.13<br />
3.14<br />
Part no.<br />
Article no.<br />
when ordered separately<br />
NZM3-XAHIVC-230AC-MNS<br />
274142<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
1 off Cannot be installed simultaneously with NZM...-XHIV... earlymake<br />
auxiliary contact or NZM...-XU... undervoltage release.<br />
Cannot be used in conjunction with NZM...-XR... remote<br />
operator.<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
C1<br />
C2<br />
3.13<br />
3.14<br />
NZM4(-4), N4(-4) 230 V AC NZM4-XAHIV-230AC-MNS<br />
274143<br />
C1<br />
C2<br />
3.13<br />
3.14<br />
NZM4-XAHIVC-230AC-MNS<br />
274144<br />
1 off<br />
Intermittent operation guaranteed by series connection of a<br />
N/O contact M22-(C)K10 (standard auxiliary contact).<br />
The maximum operating time of the shunt release for mesh<br />
network circuit-breaker is 1 s.<br />
NZM3: Early-make of the auxiliary contact with on and off<br />
switching (manual operation): approx. 20 ms.<br />
NZM4: Early-make of the auxiliary contact with switch on<br />
(manual operation): approx. 90 ms.