Technical Data - IC SYSTEMS automatika
Technical Data - IC SYSTEMS automatika
Technical Data - IC SYSTEMS automatika
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
68<br />
Circuit-breakers, switch-disconnectors<br />
Shunt releases with screw terminal<br />
Circuit-breakers, switch-disconnectors<br />
Shunt releases with springloaded terminal<br />
69<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Shunt releases<br />
Without auxiliary contacts<br />
For mesh-network circuit-breakers<br />
For intermittent operation<br />
Maximum on time = 1 s<br />
Operating range 10 – 110 % U s<br />
not UL/CSA approved<br />
C1<br />
For use with Rated control voltage Part no.<br />
Article no.<br />
when ordered separately<br />
U s<br />
V<br />
NZM3(-4), N3(-4) 230 V AC NZM3-XA-230AC-MNS<br />
274097<br />
Moeller SK1230-1157GB-INT<br />
Price<br />
see price list<br />
Std. pack<br />
Moeller SK1230-1157GB-INT<br />
Part no.<br />
Article no.<br />
when ordered separately<br />
1 off C1<br />
NZM3-XAC-230AC-MNS<br />
274137<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
1 off Cannot be installed simultaneously with NZM...-XHIV... earlymake<br />
auxiliary contact or NZM...-XU... undervoltage release.<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
C2<br />
C2<br />
Intermittent operation guaranteed by series connection of an<br />
M22-(C)K10 make contact.<br />
The maximum operating time of the shunt release for mesh<br />
network circuit-breaker is 1 s.<br />
L1 (L+)<br />
C1<br />
NZM4(-4), N4(-4) 230 V AC NZM4-XA-230AC-MNS<br />
274138<br />
1 off C1 NZM4-XAC-230AC-MNS<br />
274140<br />
1 off<br />
C2<br />
C2<br />
a<br />
-S11<br />
0<br />
Q<br />
HIN<br />
1.13<br />
1.14<br />
M22-...K10<br />
-Q1<br />
C1<br />
C2<br />
NZM...-XA...-MNS<br />
N (L-, L2)<br />
a Reverse-power relay contact<br />
-S11 Remote off<br />
Q Standard auxiliary contact<br />
-Q1 Shunt release