66<br />

Circuit-breakers, switch-disconnectors<br />

Shunt releases with screw terminal<br />

Circuit-breakers, switch-disconnectors<br />

Shunt releases with springloaded terminal<br />

67<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Shunt releases<br />

Without auxiliary contact<br />

Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.<br />

C1 – NZM2(-4), N2(-4)<br />

NZM3(-4), N3(-4)<br />

C2<br />

Moeller SK1230-1157GB-INT<br />

For use with Rated control voltage Part no.<br />

Article no.<br />

when ordered separately<br />

U s<br />

V<br />

12 V AC/DC NZM2/3-XA12AC/DC<br />

259752<br />

24 V AC/DC NZM2/3-XA24AC/DC<br />

259754<br />

48 V AC/DC NZM2/3-XA48AC/DC<br />

259756<br />

60 V AC/DC NZM2/3-XA60AC/DC<br />

259758<br />

110 V – 130 V AC/DC NZM2/3-XA110-130AC/DC<br />

259760<br />

208 V – 250 V AC/DC NZM2/3-XA208-250AC/DC<br />

259763<br />

380 V – 440 V AC/DC NZM2/3-XA380-440AC/DC<br />

259766<br />

480 V – 525 V AC/DC NZM2/3-XA480-525AC/DC<br />

259768<br />

600 V AC/DC NZM2/3-XA600AC/DC<br />

259770<br />

Moeller SK1230-1157GB-INT<br />

C1<br />

C2<br />

Part no.<br />

Article no.<br />

when ordered separately<br />

NZM2/3-XAC12AC/DC<br />

266506<br />

NZM2/3-XAC24AC/DC<br />

266507<br />

NZM2/3-XAC48AC/DC<br />

266508<br />

NZM2/3-XAC60AC/DC<br />

266509<br />

NZM2/3-XAC110-130AC/DC<br />

266510<br />

NZM2/3-XAC208-250AC/DC<br />

266511<br />

NZM2/3-XAC380-440AC/DC<br />

266512<br />

NZM2/3-XAC480-525AC/DC<br />

266513<br />

NZM2/3-XAC600AC/DC<br />

266514<br />

Price<br />

see price<br />

list<br />

Std. pack<br />

Notes<br />

1 off When the undervoltage release is de-energized, accidental contact<br />

with the main contacts of the switch during attempts to switch on,<br />

is safely prevented.<br />

Shunt release cannot be installed simultaneously with<br />

NZM...-XHIV... early-make auxiliary contact or NZM...-XU...<br />

undervoltage release.<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

C1<br />

C2<br />

– NZM4(-4), N4(-4) 12 V AC/DC NZM4-XA12AC/DC<br />

266446<br />

24 V AC/DC NZM4-XA24AC/DC<br />

266447<br />

48 V AC/DC NZM4-XA48AC/DC<br />

266448<br />

60 V AC/DC NZM4-XA60AC/DC<br />

266449<br />

110 V – 130 V AC/DC NZM4-XA110-130AC/DC<br />

266450<br />

208 V – 250 V AC/DC NZM4-XA208-250AC/DC<br />

266451<br />

380 V – 440 V AC/DC NZM4-XA380-440AC/DC<br />

266452<br />

480 V – 525 V AC/DC NZM4-XA480-525AC/DC<br />

266453<br />

600 V AC/DC NZM4-XA600AC/DC<br />

266454<br />

C1<br />

C2<br />

NZM4-XAC12AC/DC<br />

266524<br />

NZM4-XAC24AC/DC<br />

266525<br />

NZM4-XAC48AC/DC<br />

266526<br />

NZM4-XAC60AC/DC<br />

266527<br />

NZM4-XAC110-130AC/DC<br />

266528<br />

NZM4-XAC208-250AC/DC<br />

266529<br />

NZM4-XAC380-440AC/DC<br />

266530<br />

NZM4-XAC480-525AC/DC<br />

266531<br />

NZM4-XAC600AC/DC<br />

266532<br />

1 off When the undervoltage release is de-energized, accidental contact<br />

with the main contacts of the switch during attempts to switch on,<br />

is safely prevented.<br />

Shunt release cannot be installed simultaneously with<br />

NZM...-XHIV... early-make auxiliary contact or NZM...-XU...<br />

undervoltage release.<br />

Capacitor unit 230 V 50/60 Hzin conjunction with NZM...-XA2082-50AC/DC shunt release<br />

Enclosure: degree of protection IP20<br />

not UL/CSA approved<br />

NZM1(-4), N1(-4)<br />

NZM2(-4), N2(-4)<br />

NZM3(-4), N3(-4)<br />

NZM4(-4), N4(-4)<br />

– NZM-XCM<br />

229413<br />

1 off Enables safe use of the circuit-breaker as a mesh network circuitbreaker<br />

in a range from 0 – 110 % U n with constant shutdown<br />

time of 40 ms.<br />

If the mains voltage is absent, the installed capacitor supplies<br />

power for actuating the shunt release for at least 12 hours.<br />

The configuration of the capacitor unit is undertaken<br />

independently of the circuit-breaker.<br />

Connect NZM-XCM to the power feed side.<br />

Engineering note:<br />

Connect the standard auxiliary contact (HIN) als N/O in series to<br />

the coil of the shunt release.<br />

Standard auxiliary contact not supplied.