66<br />
Circuit-breakers, switch-disconnectors<br />
Shunt releases with screw terminal<br />
Circuit-breakers, switch-disconnectors<br />
Shunt releases with springloaded terminal<br />
67<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Shunt releases<br />
Without auxiliary contact<br />
Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.<br />
C1 – NZM2(-4), N2(-4)<br />
NZM3(-4), N3(-4)<br />
C2<br />
Moeller SK1230-1157GB-INT<br />
For use with Rated control voltage Part no.<br />
Article no.<br />
when ordered separately<br />
U s<br />
V<br />
12 V AC/DC NZM2/3-XA12AC/DC<br />
259752<br />
24 V AC/DC NZM2/3-XA24AC/DC<br />
259754<br />
48 V AC/DC NZM2/3-XA48AC/DC<br />
259756<br />
60 V AC/DC NZM2/3-XA60AC/DC<br />
259758<br />
110 V – 130 V AC/DC NZM2/3-XA110-130AC/DC<br />
259760<br />
208 V – 250 V AC/DC NZM2/3-XA208-250AC/DC<br />
259763<br />
380 V – 440 V AC/DC NZM2/3-XA380-440AC/DC<br />
259766<br />
480 V – 525 V AC/DC NZM2/3-XA480-525AC/DC<br />
259768<br />
600 V AC/DC NZM2/3-XA600AC/DC<br />
259770<br />
Moeller SK1230-1157GB-INT<br />
C1<br />
C2<br />
Part no.<br />
Article no.<br />
when ordered separately<br />
NZM2/3-XAC12AC/DC<br />
266506<br />
NZM2/3-XAC24AC/DC<br />
266507<br />
NZM2/3-XAC48AC/DC<br />
266508<br />
NZM2/3-XAC60AC/DC<br />
266509<br />
NZM2/3-XAC110-130AC/DC<br />
266510<br />
NZM2/3-XAC208-250AC/DC<br />
266511<br />
NZM2/3-XAC380-440AC/DC<br />
266512<br />
NZM2/3-XAC480-525AC/DC<br />
266513<br />
NZM2/3-XAC600AC/DC<br />
266514<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
1 off When the undervoltage release is de-energized, accidental contact<br />
with the main contacts of the switch during attempts to switch on,<br />
is safely prevented.<br />
Shunt release cannot be installed simultaneously with<br />
NZM...-XHIV... early-make auxiliary contact or NZM...-XU...<br />
undervoltage release.<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
C1<br />
C2<br />
– NZM4(-4), N4(-4) 12 V AC/DC NZM4-XA12AC/DC<br />
266446<br />
24 V AC/DC NZM4-XA24AC/DC<br />
266447<br />
48 V AC/DC NZM4-XA48AC/DC<br />
266448<br />
60 V AC/DC NZM4-XA60AC/DC<br />
266449<br />
110 V – 130 V AC/DC NZM4-XA110-130AC/DC<br />
266450<br />
208 V – 250 V AC/DC NZM4-XA208-250AC/DC<br />
266451<br />
380 V – 440 V AC/DC NZM4-XA380-440AC/DC<br />
266452<br />
480 V – 525 V AC/DC NZM4-XA480-525AC/DC<br />
266453<br />
600 V AC/DC NZM4-XA600AC/DC<br />
266454<br />
C1<br />
C2<br />
NZM4-XAC12AC/DC<br />
266524<br />
NZM4-XAC24AC/DC<br />
266525<br />
NZM4-XAC48AC/DC<br />
266526<br />
NZM4-XAC60AC/DC<br />
266527<br />
NZM4-XAC110-130AC/DC<br />
266528<br />
NZM4-XAC208-250AC/DC<br />
266529<br />
NZM4-XAC380-440AC/DC<br />
266530<br />
NZM4-XAC480-525AC/DC<br />
266531<br />
NZM4-XAC600AC/DC<br />
266532<br />
1 off When the undervoltage release is de-energized, accidental contact<br />
with the main contacts of the switch during attempts to switch on,<br />
is safely prevented.<br />
Shunt release cannot be installed simultaneously with<br />
NZM...-XHIV... early-make auxiliary contact or NZM...-XU...<br />
undervoltage release.<br />
Capacitor unit 230 V 50/60 Hzin conjunction with NZM...-XA2082-50AC/DC shunt release<br />
Enclosure: degree of protection IP20<br />
not UL/CSA approved<br />
NZM1(-4), N1(-4)<br />
NZM2(-4), N2(-4)<br />
NZM3(-4), N3(-4)<br />
NZM4(-4), N4(-4)<br />
– NZM-XCM<br />
229413<br />
1 off Enables safe use of the circuit-breaker as a mesh network circuitbreaker<br />
in a range from 0 – 110 % U n with constant shutdown<br />
time of 40 ms.<br />
If the mains voltage is absent, the installed capacitor supplies<br />
power for actuating the shunt release for at least 12 hours.<br />
The configuration of the capacitor unit is undertaken<br />
independently of the circuit-breaker.<br />
Connect NZM-XCM to the power feed side.<br />
Engineering note:<br />
Connect the standard auxiliary contact (HIN) als N/O in series to<br />
the coil of the shunt release.<br />
Standard auxiliary contact not supplied.