18.01.2014 Views

Technical Data - IC SYSTEMS automatika

Technical Data - IC SYSTEMS automatika

Technical Data - IC SYSTEMS automatika

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Switch-disconnectors for North America<br />

3 pole<br />

43<br />

Moeller SK1230-1157GB-INT<br />

Rated current = rated<br />

uninterrupted current<br />

Short-circuit<br />

protection,<br />

max. gG/gL fuse 1)<br />

Short-circuit<br />

protection max. fuse<br />

OTS characteristic<br />

Short-circuit rating with<br />

OTS fuse<br />

At 480 V: At 600 V:<br />

I n = I u<br />

A A A kA kA<br />

3 switch positions I, + , 0 ;<br />

can be tripped remotely with<br />

shunt/under voltage release<br />

Part no.<br />

Article no.<br />

Switch-disconnector<br />

3 pole<br />

Terminals standard,<br />

terminal screws as accessories<br />

63 125 150 10 – N1-63-NA<br />

272259<br />

100 125 150 10 – N1-100-NA<br />

272260<br />

125 125 150 10 – N1-125-NA<br />

272261<br />

Terminal screws standard<br />

terminals as accessories<br />

160 250 225 10 10 N2-160-NA<br />

271166<br />

Price<br />

see price<br />

list<br />

Std.<br />

pack<br />

1 off<br />

1 off<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

400 630 – 2) 14 14 N3-400-NA<br />

271169<br />

550 630 – 2) 14 14 N3-550-NA<br />

293635<br />

600 1600 – 2) 25 25 N4-600-NA<br />

292386<br />

800 1600 – 2) 25 25 N4-800-NA<br />

271171<br />

1000 1600 – 2) 25 25 N4-1000-NA<br />

271172<br />

1200 1600 – 2) 25 25 N4-1200-NA<br />

271173<br />

Notes Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.<br />

Isolating characteristics to IEC/EN 60947-3 and VDE 0660.<br />

Protection against accidental contact according to IEC.<br />

Undervoltage and shunt releases and HIA trip-indicating auxiliary contacts can be used in addition with N switch-disconnectors.<br />

N2..., N3... and N4... can also be combined with the NZM...-XR... remote operator.<br />

Switches conform to UL 489/CSA 22.2 No. 5.1 as well as to the IEC regulations.<br />

Rated current ranges 200 A and 250 A are covered by the molded case switches NS2-200-NA or NS2-250-NA.<br />

Notes for terminals a 95<br />

1) for use when using a switch-disconnector to EN 60947-3.<br />

2) for use when using a switch-disconnector to N3...-NA and N4...-NA without protective device to UL 1087, CSA 22.2 No 5.2.