Switch-disconnectors for North America<br />
3 pole<br />
43<br />
Moeller SK1230-1157GB-INT<br />
Rated current = rated<br />
uninterrupted current<br />
Short-circuit<br />
protection,<br />
max. gG/gL fuse 1)<br />
Short-circuit<br />
protection max. fuse<br />
OTS characteristic<br />
Short-circuit rating with<br />
OTS fuse<br />
At 480 V: At 600 V:<br />
I n = I u<br />
A A A kA kA<br />
3 switch positions I, + , 0 ;<br />
can be tripped remotely with<br />
shunt/under voltage release<br />
Part no.<br />
Article no.<br />
Switch-disconnector<br />
3 pole<br />
Terminals standard,<br />
terminal screws as accessories<br />
63 125 150 10 – N1-63-NA<br />
272259<br />
100 125 150 10 – N1-100-NA<br />
272260<br />
125 125 150 10 – N1-125-NA<br />
272261<br />
Terminal screws standard<br />
terminals as accessories<br />
160 250 225 10 10 N2-160-NA<br />
271166<br />
Price<br />
see price<br />
list<br />
Std.<br />
pack<br />
1 off<br />
1 off<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
400 630 – 2) 14 14 N3-400-NA<br />
271169<br />
550 630 – 2) 14 14 N3-550-NA<br />
293635<br />
600 1600 – 2) 25 25 N4-600-NA<br />
292386<br />
800 1600 – 2) 25 25 N4-800-NA<br />
271171<br />
1000 1600 – 2) 25 25 N4-1000-NA<br />
271172<br />
1200 1600 – 2) 25 25 N4-1200-NA<br />
271173<br />
Notes Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.<br />
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.<br />
Protection against accidental contact according to IEC.<br />
Undervoltage and shunt releases and HIA trip-indicating auxiliary contacts can be used in addition with N switch-disconnectors.<br />
N2..., N3... and N4... can also be combined with the NZM...-XR... remote operator.<br />
Switches conform to UL 489/CSA 22.2 No. 5.1 as well as to the IEC regulations.<br />
Rated current ranges 200 A and 250 A are covered by the molded case switches NS2-200-NA or NS2-250-NA.<br />
Notes for terminals a 95<br />
1) for use when using a switch-disconnector to EN 60947-3.<br />
2) for use when using a switch-disconnector to N3...-NA and N4...-NA without protective device to UL 1087, CSA 22.2 No 5.2.