20<br />
Circuit-breakers<br />
Electronic releases, 4 pole<br />
Circuit-breakers<br />
Electronic releases, 4 pole<br />
21<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Rated current = rated<br />
uninterrupted current<br />
Setting range<br />
Overload releases<br />
Main pole<br />
Neutral conductor<br />
I n = I u I r I r I i<br />
A A A A<br />
I<br />
Short-circuit releases<br />
Moeller SK1230-1157GB-INT<br />
Normal switching capacity<br />
50 kA<br />
at 415 V 50/60 Hz<br />
Part no.<br />
Article no.<br />
Protection of systems and cables<br />
4-pole<br />
Terminal screws standard,<br />
terminals as accessories<br />
400 200 – 400 200 – 400 800 – 4400 NZMN3-4-AE400<br />
265891<br />
400 200 – 400 125 – 250 800 – 4400 NZMN3-4-AE400/250<br />
265892<br />
400 200 – 400 – 800 – 4400 NZMN3-4-AE400/0<br />
265893<br />
630 315 – 630 315 – 630 1260 – 5040 NZMN3-4-AE630<br />
265894<br />
630 315 – 630 200 – 400 1260 – 5040 NZMN3-4-AE630/400<br />
265895<br />
630 315 – 630 – 1260 – 5040 NZMN3-4-AE630/0<br />
265896<br />
800 400 – 800 400 – 800 1600 – 9600 NZMN4-4-AE800<br />
265909<br />
800 400 – 800 250 – 500 1600 – 9600 NZMN4-4-AE800/500<br />
265910<br />
800 400 – 800 – 1600 – 9600 NZMN4-4-AE800/0<br />
265911<br />
1000 500 – 1000 500 – 1000 2000 – 12000 NZMN4-4-AE1000<br />
265912<br />
1000 500 – 1000 315 – 630 2000 – 12000 NZMN4-4-AE1000/630<br />
265913<br />
1000 500 – 1000 – 2000 – 12000 NZMN4-4-AE1000/0<br />
265914<br />
1250 630 – 1250 630 – 1250 2500 – 15000 NZMN4-4-AE1250<br />
265915<br />
1250 630 – 1250 400 – 800 2500 – 15000 NZMN4-4-AE1250/800<br />
265916<br />
1250 630 – 1250 – 2500 – 15000 NZMN4-4-AE1250/0<br />
265917<br />
1600 800 – 1600 800 – 1600 3200 – 19200 NZMN4-4-AE1600<br />
265918<br />
1600 800 – 1600 500 – 1000 3200 – 19200 NZMN4-4-AE1600/1000<br />
265919<br />
1600 800 – 1600 – 3200 – 19200 NZMN4-4-AE1600/0<br />
265920<br />
Price<br />
see price<br />
list<br />
Moeller SK1230-1157GB-INT<br />
High switching capacity<br />
100 kA<br />
at 415 V 50/60 Hz<br />
Part no.<br />
Article no.<br />
NZMH3-4-AE400<br />
265897<br />
NZMH3-4-AE400/250<br />
265898<br />
NZMH3-4-AE400/0<br />
265899<br />
NZMH3-4-AE630<br />
265900<br />
NZMH3-4-AE630/400<br />
265901<br />
NZMH3-4-AE630/0<br />
265902<br />
NZMH4-4-AE800<br />
265921<br />
NZMH4-4-AE800/500<br />
265922<br />
NZMH4-4-AE800/0<br />
265923<br />
NZMH4-4-AE1000<br />
265924<br />
NZMH4-4-AE1000/630<br />
265925<br />
NZMH4-4-AE1000/0<br />
265926<br />
NZMH4-4-AE1250<br />
265927<br />
NZMH4-4-AE1250/800<br />
265928<br />
NZMH4-4-AE1250/0<br />
265929<br />
NZMH4-4-AE1600<br />
265930<br />
NZMH4-4-AE1600/1000<br />
265931<br />
NZMH4-4-AE1600/0<br />
265932<br />
Price<br />
see price<br />
list<br />
Limiter switching capacity 1)<br />
150 kA<br />
at 415 V 50/60 Hz<br />
Part no.<br />
Article no.<br />
NZML3-4-AE400<br />
265903<br />
NZML3-4-AE400/250<br />
265904<br />
NZML3-4-AE400/0<br />
265905<br />
NZML3-4-AE630<br />
265906<br />
NZML3-4-AE630/400<br />
265907<br />
NZML3-4-AE630/0<br />
265908<br />
NZML4-4-AE800<br />
283221<br />
NZML4-4-AE800/500<br />
283222<br />
NZML4-4-AE800/0<br />
283223<br />
NZML4-4-AE1000<br />
283224<br />
NZML4-4-AE1000/630<br />
283225<br />
NZML4-4-AE1000/0<br />
283226<br />
NZML4-4-AE1250<br />
283227<br />
NZML4-4-AE1250/800<br />
283228<br />
NZML4-4-AE1250/0<br />
283229<br />
NZML4-4-AE1600<br />
283230<br />
NZML4-4-AE1600/1000<br />
283231<br />
NZML4-4-AE1600/0<br />
283232<br />
Price<br />
see price<br />
list<br />
Std. pack<br />
Notes<br />
1 off IEC/EN 60947-2<br />
Adjustable overload release I r<br />
• 0.5 – 1 x I n (ex-factory 0.8 x I n )<br />
Setting on neutral pole implemented via the main pole setting I r of<br />
the main pole.<br />
R.m.s. value measurement and “thermal memory”<br />
Adjustable short-circuit release I i<br />
• NZM...3-4-AE400: 2 – 11 x I n (ex-factory 6 x I n )<br />
• NZM...3-4-AE630: 2 – 8 x I n (ex-factory 6 x I n )<br />
• NZM...4-4-AE...: 2 – 12 x I n (ex-factory 6 x I n )<br />
NZM...-4-AE...<br />
• With 100% overload and short-circuit protection in 4th pole<br />
NZM...-4-AE.../...<br />
• With 60% overload and short-circuit protection in 4th pole<br />
NZM...-4-AE.../0<br />
• No overload and 100 % short-circuit protection in the 4th pole<br />
• Not for use in IT electrical power networks<br />
1) For limiter switching capacity with NZML4-4-AE...<br />
the following applies: 100 kA<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Notes Notes for terminals a 103