Technical Data - IC SYSTEMS automatika
Technical Data - IC SYSTEMS automatika
Technical Data - IC SYSTEMS automatika
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
i<br />
f<br />
162 <strong>Technical</strong> data<br />
Direction of blow-out, minimum clearances, pipe cable lugs<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Direction of blow-out<br />
Top<br />
Front<br />
NZM1 X –<br />
NZM2 X X<br />
NZM3 X X<br />
NZM4 X –<br />
Bottom<br />
Rear<br />
Moeller SK1230-1157GB-INT<br />
Minimum clearance<br />
Between two switches mounted side-by-side<br />
Minimum clearance a in mm<br />
b<br />
a<br />
b<br />
c<br />
d<br />
NZM1 NZM2 NZM3 NZM4<br />
NZM1 0 5 5 15<br />
NZM2 5 5 5 15<br />
NZM3 5 5 5 15<br />
NZM4 15 15 15 15<br />
Between switch and other components<br />
Minimum clearance in mm<br />
b c d<br />
F 690 V 1000 V F 690 V 1000 V F 690 V 1000 V<br />
NZM1 0 – 60 – 0 –<br />
NZM2 5 5 35 35 35 35<br />
NZM3 5 5 60 60 60 60<br />
NZM4 15 15 100 200 0 0<br />
Dimensions<br />
g<br />
d<br />
e<br />
b<br />
c<br />
h<br />
a<br />
Cable lug For use with Nominal<br />
cross-section<br />
Terminal bolts<br />
Dimensions<br />
in mm<br />
mm 2 o a b c d e f g h i<br />
KS95-NZM7 NZM2 95 M8 53+2 23g0.5 18g0.2 10g1 19 8,5 25 13,5 4,4<br />
KS120-NZM7 NZM2 120 M8 56+2 23g0.5 19.5g0.2 10g1 19 8,5 26 15 4,4<br />
KS150-NZM7 NZM2 150 M8 61+2 23g0.5 21g0.2 10g1 19 8,5 30 16,5 4,4<br />
NZM2-XKS185 NZM2 185 M8 65g1.5 22g1 24g0.3 9 +1<br />
–0,5 19 +2,5<br />
–0,5 8,5 +0,05<br />
–0,1 30g2 19g0.4 7<br />
NZM3-XKS185 NZM3, NZM4 185 M10 65 24,5 24 11,5 18 10,5 30 19 7.0g0.8<br />
NZM3-XKS240 NZM3, NZM4 240 M10 72 31 26 11,5 19 10,5 35 21 5.0g0.8