154 <strong>Technical</strong> data<br />
Remote operator, capacitor unit, auxiliary contact<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
at AC = 50/60 Hz M22-K... XHIV XHI<br />
Auxiliary contacts<br />
Rated operational voltage<br />
AC U e V AC 500 500 500<br />
DC U e V DC 220 220 220<br />
Conventional thermal current I th = I e A 4 4 4<br />
Rated operational current<br />
AC–15 115 V I e A 4 4 4<br />
230 V I e A 4 4 4<br />
400 V I e A 2 2 2<br />
500 V I e A 1 1 1<br />
DC-13 24 V I e A 3 3 3<br />
42 V I e A 1.7 1.5 –<br />
60 V I e A 1.2 0.8 1.2<br />
110 V I e A 0.8 0.5 0.5<br />
220 V I e A 0.3 0.2 0.2<br />
Short-circuit protection<br />
max. fuse A gG/gL 10 10 10<br />
Max. miniature circuit-breaker A PKZM0-10/FAZ-B6 FAZ-B6 FAZ-B6<br />
Early-make time compared to the main contacts<br />
during switch on and off (switching times with<br />
manual operation)<br />
Terminal capacities<br />
Solid or flexible conductor with ferrule mm 2 1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
AWG 1 x (18 – 14)<br />
2 x (18 – 14)<br />
UL/CSA<br />
Rated operational current I e A 10 A – 600 V AC<br />
1 A – 250 V DC<br />
Heavy Pilot Duty<br />
A600/P300<br />
above 300 V AC same<br />
polarity<br />
ms – NZM1, PN1, N1: approx. 20<br />
NZM2, PN2, N2: approx. 20<br />
NZM3, PN3, N3: approx. 20<br />
NZM4, N4: ca. 90<br />
With NZM4/N4 the HIV does<br />
not feature early break.<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (18 – 14)<br />
2 x (18 – 14)<br />
2.5 A – 240 V AC<br />
1 A – 250 V DC<br />
C300/R300<br />
Moeller SK1230-1157GB-INT<br />
–<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 2.5)<br />
1 x (18 – 14)<br />
2 x (18 – 14)<br />
2.5 A – 240 V AC<br />
1 A – 250 V DC<br />
C300/R300