<strong>Technical</strong> data<br />

Circuit-breakers, switch-disconnectors for 1000 V AC<br />

149<br />

Moeller SK1230-1157GB-INT<br />

NZMH2, N2 NZMN3, N3 NZMH4, N4<br />

General<br />

Utilization category A A A/B<br />

Maximum operating frequency Ops/h 120 60 60<br />

Lifespan<br />

mechanical<br />

20000 15000 10000<br />

(of which max. 50 % trip by shunt/undervoltage release)<br />

Electrical Operations 3000 1000 500<br />

Rated operational voltage U e V AC 1000 1000 1000<br />

Circuit-breakers<br />

Rated uninterrupted current I u A max. 250 max. 630 max. 1600<br />

Rated short-circuit making capacity<br />

1000 V 50/60 Hz I cm kA 17 17 40<br />

Rated short-circuit breaking capacity I cn<br />

I cu to IEC/EN 60947 operating sequence O-t-CO 1000 V 50/60 Hz I cu kA 10 10 20<br />

I cu to IEC/EN 60947 operating sequence O-t-CO-t-CO 1000 V 50/60 Hz I cs kA 3 10 15<br />

Rated making and breaking capacity<br />

Rated operational current<br />

AC-1 1000 V 50/60 Hz I e 250 630 1600<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Switch-disconnectors<br />

Rated uninterrupted current I u A max. 250 max. 630 max. 1600<br />

Rated short-time withstand current I cw kA 3.5 12 25<br />

Rated making and breaking capacity<br />

Rated operational current<br />

AC-22/23A 1000 V 50/60 Hz I e 250 630 1600