<strong>Technical</strong> data<br />
Circuit-breakers, switch-disconnectors for 1000 V AC<br />
149<br />
Moeller SK1230-1157GB-INT<br />
NZMH2, N2 NZMN3, N3 NZMH4, N4<br />
General<br />
Utilization category A A A/B<br />
Maximum operating frequency Ops/h 120 60 60<br />
Lifespan<br />
mechanical<br />
20000 15000 10000<br />
(of which max. 50 % trip by shunt/undervoltage release)<br />
Electrical Operations 3000 1000 500<br />
Rated operational voltage U e V AC 1000 1000 1000<br />
Circuit-breakers<br />
Rated uninterrupted current I u A max. 250 max. 630 max. 1600<br />
Rated short-circuit making capacity<br />
1000 V 50/60 Hz I cm kA 17 17 40<br />
Rated short-circuit breaking capacity I cn<br />
I cu to IEC/EN 60947 operating sequence O-t-CO 1000 V 50/60 Hz I cu kA 10 10 20<br />
I cu to IEC/EN 60947 operating sequence O-t-CO-t-CO 1000 V 50/60 Hz I cs kA 3 10 15<br />
Rated making and breaking capacity<br />
Rated operational current<br />
AC-1 1000 V 50/60 Hz I e 250 630 1600<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Switch-disconnectors<br />
Rated uninterrupted current I u A max. 250 max. 630 max. 1600<br />
Rated short-time withstand current I cw kA 3.5 12 25<br />
Rated making and breaking capacity<br />
Rated operational current<br />
AC-22/23A 1000 V 50/60 Hz I e 250 630 1600