148 <strong>Technical</strong> data<br />

Molded Case Switches<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

NS1-...-NA<br />

max. 125A<br />

Molded Case Switch<br />

Rated impulse withstand voltage<br />

U imp<br />

Main contacts 6000 8000<br />

Auxiliary contacts 6000 6000<br />

Rated operational voltage U e 690 690<br />

Rated uninterrupted current max.<br />

IEC/EN 60947-2 Annex L I u 125 250<br />

UL489/CSA 22.2 No. 5.1 I u 125 250<br />

Overvoltage category/pollution degree III/3 III/3<br />

Rated insulation voltage U i 690 1000<br />

Moeller SK1230-1157GB-INT<br />

NS2-...-NA<br />

max. 250A<br />

Switching capacity to UL 489, CSA 22.2 No. 5.1<br />

240 V 85 150<br />

480 V 35 100<br />

600 V – 50<br />

Switching capacity, divergent from the products for the NA market<br />

Rated short-circuit making capacity 240 V I cm 187 330<br />

400/415 V I cm 105 330<br />

440 V I cm 74 286<br />

525 V I cm 53 105<br />

690 V I cm 17 53<br />

Rated short-circuit breaking capacity<br />

I cc = I cu to IEC/EN 60947-2 Annex L<br />

I cu to IEC/EN 60947<br />

test cycle O-t-CO<br />

I cs to IEC/EN 60947<br />

test cycle O-t-CO-t-CO<br />

240 V I cu 85 150<br />

400/415 V I cu 50 150<br />

440 V I cu 35 130<br />

525 V I cu 20 50<br />

690 V I cu 10 20<br />

240 V I cs 85 150<br />

400/415 V I cs 50 150<br />

440 V I cs 35 130<br />

525 V I cs 10 37.5<br />

690 V I cs 7.5 5<br />

Lifespan, mechanical Operations 20000 20000<br />

Maximum operating frequency 120 120<br />

Lifespan, electrical AC-1 400/415 V Operations 10000 10000<br />

690 V Operations 7500 7500<br />

AC–-3 400/415 V Operations 7500 6500<br />

690 V Operations 5000 5000<br />

Current heat loss per pole at I 1) u 13 19<br />

Total opening delay on short-circuit < 10 < 10<br />

Notes<br />

1) Details relate to the maximum nominal current of the frame size