18.01.2014 Views

Technical Data - IC SYSTEMS automatika

Technical Data - IC SYSTEMS automatika

Technical Data - IC SYSTEMS automatika

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Technical</strong> data<br />

Switch-disconnectors, derating<br />

147<br />

Moeller SK1230-1157GB-INT<br />

PN1/N1<br />

160 A max.<br />

PN2/N2<br />

250 A max.<br />

PN3/N3<br />

630 A max.<br />

Switch-disconnectors<br />

Rated impulse withstand voltage U imp<br />

Main contacts V 6000 8000 8000 8000<br />

Auxiliary contacts V 6000 6000 6000 6000<br />

Rated operational voltage U e V AC 690 690 690 690<br />

Rated uninterrupted current max.<br />

IEC/EN 61131-3 I u A 160 250 630 1600<br />

<strong>Technical</strong> data, divergent from I u A 125 160 550 1200<br />

the products for the IEC market<br />

UL489, CSA 22.2 No. 5.1<br />

Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />

Rated insulation voltage U e V AC 690 1000 1000 1000<br />

N4<br />

1600 A max.<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Switching capacity<br />

Rated short-circuit making capacity I cm kA 2.8 5.5 25 53<br />

Rated short-time withstand current<br />

t = 0.3 s I cw kA 2 3.5 1) 12 25<br />

t = 1 s I cw kA 2 3.5 1) 12 25<br />

Rated conditional short-circuit current<br />

with back-up fuse A gG/gL 125<br />

250 630 2 x 800<br />

PN1(N1) - 160: 160<br />

400/415 V kA 100 100 100 100<br />

690 V kA 100 100 80 80<br />

With downstream fuse A gG/gL 125<br />

250 630 2 x 800<br />

PN1(N1) - 160: 160<br />

400/415 V kA 100 100 100 100<br />

690 V kA 10 100 100 80<br />

Rated making and breaking capacity<br />

Rated operational current,<br />

AC-22/23A 415 V I e A 160 250 630 1600<br />

690 V I e A 160 250 630 1600<br />

Lifespan, mechanical Operations 20000 20000 15000 10000<br />

Maximum operating frequency Ops/h 120 120 60 60<br />

Lifespan, electrical to IEC/EN 60947-4-1 section B<br />

AC-1 400/415 V Operations 10000 10000 5000 3000<br />

690 V Operations 7500 7500 3000 2000<br />

AC-3 400/415 V Operations 7500 7500 3000 2000<br />

690 V Operations 5000 5000 3) 2000 1000<br />

Current heat loss per pole at I 2) u W 8 16 40 97<br />

Notes<br />

1) The rated short-time withstand current with PN2/N2 in conjunction with residual-current releases NZM2-4-XFI... I cw = 1.5 kA<br />

2) The current heat loss per pole ratings refer to the maximum current rating of the frame size.<br />

3) 690 V: max. 160 kW<br />

NZM1, PN1, N1, NS1<br />

NZM2, PN2, N2, NS2<br />

250 A<br />

NZM3, PN3, N3, NS3<br />

630 A<br />

NZM4, N4, NS4<br />

1600 A<br />

125 A 160 A without with XSV without with XAV without with XAV<br />

TM E<br />

Permissible loading at different ambient<br />

temperatures (derating)<br />

open 20°C % 100 100 100 100 100 100 96 100 100<br />

30°C % 100 100 100 97 100 100 92 100 98<br />

40°C % 100 100 100 92 100 100 87 100 93<br />

50°C % 100 95 100 87 94 100 83 100 89<br />

60°C % 86 90 90 81 88 90 78 87 85<br />

65°C % 83 85 85 78 84 85 75 85 83<br />

70°C % 79 80 80 75 81 80 73 82 80<br />

Notes<br />

XSV = plug-in unit<br />

XAV = withdrawable unit<br />

TM = thermomagnetic<br />

E = electronic

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!