170710 Analog ultrasound sensor<br />
2/2<br />
The sensor is protected against reverse polarity.<br />
The sensor output supplies an impressed current and is loaded during short-circuit operation.<br />
Ideally, the output should be loaded with a resistance of R L =0Ω.<br />
Technical data<br />
Permissible operating voltage<br />
Current consumption (without load)<br />
Load resistance<br />
Current output<br />
Measuring range<br />
Minimum distance between sensor and a<br />
laterally reflecting wall<br />
Resolution<br />
24 V DC<br />
< 35 mA<br />
< 400 Ohm<br />
4 to 20 mA<br />
500 to 150 mm<br />
>75mm<br />
± 1mm<br />
Operating/ambient temperature range –20 to +75 °C<br />
Temperature drift<br />
Linearity error<br />
Measuring pulse frequency<br />
0.1%/°C<br />
0.2% FSD* (*FSD = full scale deflection)<br />
40 Hz<br />
Sound cone aperture angle Approx. 5°<br />
Reverse polarity protection<br />
Yes<br />
Degree of protection IP 65<br />
Materials (housing)<br />
Weight<br />
Subject to change<br />
Plastic<br />
0.250 kg<br />
240<br />
mm<br />
200<br />
180<br />
160<br />
140<br />
Level<br />
120<br />
100<br />
80<br />
60<br />
40<br />
20<br />
Characteristic curve<br />
0<br />
8 9 10 11 12 13<br />
Sensor output<br />
14 15 16 mA 17<br />
The oszillations at the beginning and the end of the characteristic curve are caused by<br />
the type of sensor construction.<br />
For the characteristic curve displayed, the distance between the sensor and the bottom<br />
of the container was adjusted to 330 mm.<br />