B8 – 2<br />

Networking with Profibus<br />

• Bus termination<br />

A bus termination must be effected on the first and last noted, in this<br />

case nodes 1 and 4. This can be set via DIP switches on many<br />

Profibus stations. The bus termination corresponds to the illustrated<br />

circuit.<br />

390 Ohm, 1/4 W150 Ohm, 1/4 W 390 Ohm, 1/4 W<br />

5V<br />

(Pin 6)<br />

Data +<br />

(Pin 3)<br />

Data -<br />

(Pin 8)<br />

GND<br />

(Pin 5)<br />

• Interconnection<br />

The individual components are interconnected as shown in the<br />

following table.<br />

consec.<br />

No.<br />

Connection of<br />

1 Profibus plug-in card PC Profibus branch tee 1<br />

Part system Temperature control<br />

2 Profibus branch tee 1<br />

Part system Temperature control<br />

a) PLC<br />

b) Profibus branch tee 2<br />

Part system<br />

Temperature control<br />

3 Profibus branch tee 2<br />

Part system Temperature control<br />

4 Profibus branch tee<br />

part system Flow control<br />

5 Profibus branch tee<br />

Part system Filling level control<br />

to<br />

a) Industrial controller<br />

Temperature control<br />

b) Profibus branch tee<br />

Part system Flow control<br />

a) Industrial controller<br />

Flow control<br />

b) Profibus branch tee<br />

Part system Filling level control<br />

a) Industrial controller<br />

Filling level control<br />

<strong>Process</strong> <strong>Control</strong> <strong>System</strong> • Festo Didactic