B7 – 4<br />
Commissioning<br />
B.7.3 – <strong>Control</strong>ler settings<br />
(Detailed information regarding the operation of the controller can be found in the<br />
operating instructions of the controller, chapter 6. Please observe the notes on safety in<br />
the operating instructions of the controller.)<br />
The industrial controller can be configured via a number of different<br />
menus. The configuration level of the controller can be accessed by<br />
simultaneously pressing the SELECT and ENTER keys (for 5 seconds).<br />
Temperature<br />
control<br />
Flow<br />
control<br />
Filling level<br />
control<br />
Structure standard standard standard<br />
Input1 Pt100 3-wire Frequency 0-20mA<br />
- Fre: 1000 Rad: off<br />
Scaling - X1o 100.0 X1o 100.0<br />
- X1u 0.00 X1u 0.00<br />
Setpoint limits W1o 60.00 W1o 100.0 W1o 100.0<br />
W1u 0.00 W1u 0.00 W1u 0.00<br />
Alarm mode Al abs Al abs Al abs<br />
Alarm limits X1+ 60.00 X1+ 100.0 X1+ 100.0<br />
X1- 0.00 X1- 0.00 X1- 0.00<br />
Hy 1.00 Hy 1.00 Hy 1.00<br />
Filter Fg1 20.00 Fg1 20.00 Fg1 20.00<br />
<strong>Control</strong>ler Kp 4.00 Kp 3.50 Kp 28<br />
Tn 2500 Tn 0.40 Tn 5.00<br />
Tv 0.00 Tv 0.00 Tv 0.00<br />
Y0 0.00 Y0 0.00 Y0 0.00<br />
Output 2Pkt-PWM steady-state steady-state<br />
Signal type 0-10V 0-10V<br />
Periodic time T+ 10.00<br />
Correcting variables- Yo 100.0 Yo 100.0 Yo 100.0<br />
limit Yu 0.00 Yu 0.00 Yu 0.00<br />
Direction of control action Inv no Inv no Inv no<br />
Pulse output Imp no<br />
Safety<br />
Ys 0.00 Ys 0.00 Ys 0.00<br />
Adap.contr.<br />
Tune off Tune off Tune off<br />
Additions<br />
with visualisation<br />
software<br />
Adapt off Adapt off Adapt off<br />
Language English Language English Language English<br />
Serial remote Serial remote Serial remote<br />
Profibus Addr 002 Addr 003 Addr 005<br />
RS232 Addr 1 Addr 1 Addr 1<br />
BinIn not BinIn not BinIn not<br />
BinOut not BinOut not BinOut not<br />
Ramp out Ramp out Ramp out<br />
SPT out SPT out SPT out<br />
Line2 Act. vaI. Line2 Act. val. Line2 Act. val.<br />
Code - Code - Code -<br />
<strong>Process</strong> <strong>Control</strong> <strong>System</strong>• Festo Didactic