M-Bus Communication Protocol - Gossen-Metrawatt
M-Bus Communication Protocol - Gossen-Metrawatt
M-Bus Communication Protocol - Gossen-Metrawatt
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
- Setting the Profile ACTIVE mask:<br />
English<br />
Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS0 10000000 80 Phase 1, 2, 3 Active Power<br />
PS1 01000000 40 Frequency<br />
PS2 00011000 18<br />
PS3 11111111 FF<br />
PS4 00011111 1F<br />
Error Code<br />
Out Of range<br />
Phase 1, 2, 3 Imported Active Energy Total<br />
3-Phase Imported Active Energy Total<br />
Phase 1, 2, 3 Exported Active Energy Total<br />
3-Phase Exported Active Energy Total<br />
Phase 1, 2, 3 Imported Active Energy Tariff 1<br />
3-Phase Imported Active Energy Tariff 1<br />
Phase 1, 2, 3 Exported Active Energy Tariff 1<br />
3-Phase Exported Active Energy Tariff 1<br />
Phase 1, 2, 3 Imported Active Energy Tariff 2<br />
3-Phase Imported Active Energy Tariff 2<br />
Phase 1, 2, 3 Exported Active Energy Tariff 2<br />
3-Phase Exported Active Energy Tariff 2<br />
All Active Energy Balance<br />
PS5 00000000 00 No one value<br />
PS6 00000000 00 No one value<br />
PS7 00000000 00 No one value<br />
Table C8 – Active Mask Profile<br />
And so the Profile Active mask in HEX will be:<br />
80 40 18 FF 1F 00 00 00<br />
- Setting the Profile REACTIVE mask:<br />
Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS0 00000000 00<br />
PS1 01000010 42<br />
PS2 00011000 18<br />
From Bit 39 to Bit 50 Reactive Values has to be taken<br />
From Bit 51 to Bit 64 Reactive Values has to be taken<br />
Phase 1, 2, 3 Reactive Power<br />
Frequency<br />
Error Code<br />
Out Of range<br />
PS3 00000000 00 No one value<br />
PS4 11000000 C0<br />
PS5 11111111 FF<br />
Phase 1, 2, 3 Imported Inductive Energy Total (Reactive from PS0 bit 0)<br />
3-Phase Imported Inductive Energy Total (Reactive from PS0 bit 0)<br />
Phase 1, 2, 3 Exported Inductive Energy Total (Reactive from PS0 bit 0)<br />
3-Phase Exported Inductive Energy Total (Reactive from PS0 bit 0)<br />
Phase 1, 2, 3 Imported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />
3-Phase Imported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />
Phase 1, 2, 3 Exported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />
3-Phase Exported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />
Phase 1, 2, 3 Imported Inductive Energy Tariff 2 (Reactive from PS0 bit 0)<br />
3-Phase Imported Inductive Energy Tariff 2 (Reactive from PS0 bit 0)<br />
56 M-<strong>Bus</strong> communication protocol