01.01.2014 Views

M-Bus Communication Protocol - Gossen-Metrawatt

M-Bus Communication Protocol - Gossen-Metrawatt

M-Bus Communication Protocol - Gossen-Metrawatt

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

- Setting the Profile ACTIVE mask:<br />

English<br />

Parameter<br />

Set<br />

Value (BIN) Value (HEX) Description<br />

PS0 10000000 80 Phase 1, 2, 3 Active Power<br />

PS1 01000000 40 Frequency<br />

PS2 00011000 18<br />

PS3 11111111 FF<br />

PS4 00011111 1F<br />

Error Code<br />

Out Of range<br />

Phase 1, 2, 3 Imported Active Energy Total<br />

3-Phase Imported Active Energy Total<br />

Phase 1, 2, 3 Exported Active Energy Total<br />

3-Phase Exported Active Energy Total<br />

Phase 1, 2, 3 Imported Active Energy Tariff 1<br />

3-Phase Imported Active Energy Tariff 1<br />

Phase 1, 2, 3 Exported Active Energy Tariff 1<br />

3-Phase Exported Active Energy Tariff 1<br />

Phase 1, 2, 3 Imported Active Energy Tariff 2<br />

3-Phase Imported Active Energy Tariff 2<br />

Phase 1, 2, 3 Exported Active Energy Tariff 2<br />

3-Phase Exported Active Energy Tariff 2<br />

All Active Energy Balance<br />

PS5 00000000 00 No one value<br />

PS6 00000000 00 No one value<br />

PS7 00000000 00 No one value<br />

Table C8 – Active Mask Profile<br />

And so the Profile Active mask in HEX will be:<br />

80 40 18 FF 1F 00 00 00<br />

- Setting the Profile REACTIVE mask:<br />

Parameter<br />

Set<br />

Value (BIN) Value (HEX) Description<br />

PS0 00000000 00<br />

PS1 01000010 42<br />

PS2 00011000 18<br />

From Bit 39 to Bit 50 Reactive Values has to be taken<br />

From Bit 51 to Bit 64 Reactive Values has to be taken<br />

Phase 1, 2, 3 Reactive Power<br />

Frequency<br />

Error Code<br />

Out Of range<br />

PS3 00000000 00 No one value<br />

PS4 11000000 C0<br />

PS5 11111111 FF<br />

Phase 1, 2, 3 Imported Inductive Energy Total (Reactive from PS0 bit 0)<br />

3-Phase Imported Inductive Energy Total (Reactive from PS0 bit 0)<br />

Phase 1, 2, 3 Exported Inductive Energy Total (Reactive from PS0 bit 0)<br />

3-Phase Exported Inductive Energy Total (Reactive from PS0 bit 0)<br />

Phase 1, 2, 3 Imported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />

3-Phase Imported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />

Phase 1, 2, 3 Exported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />

3-Phase Exported Inductive Energy Tariff 1 (Reactive from PS0 bit 0)<br />

Phase 1, 2, 3 Imported Inductive Energy Tariff 2 (Reactive from PS0 bit 0)<br />

3-Phase Imported Inductive Energy Tariff 2 (Reactive from PS0 bit 0)<br />

56 M-<strong>Bus</strong> communication protocol

Hooray! Your file is uploaded and ready to be published.

Saved successfully!