Parameter<br />

Set<br />

Value (BIN) Value (HEX) Description<br />

PS1 11111111 FF<br />

PS2 11011111 DF<br />

Phase 1, 2, 3 Apparent Power<br />

Phase 1, 2, 3 Reactive Power<br />

Phase 1, 2, 3, Sys Voltage<br />

Line 12, 23, 31 Voltage<br />

Phase 1, 2, 3, N, Sys Current<br />

Phase 1, 2, 3, Sys Power Factor<br />

Frequency<br />

Phase Order<br />

Actual Tariff<br />

CT Value, FSA Value<br />

Pri/Sec Value<br />

Error Code<br />

Out Of range<br />

PS3 00000000 00 No one value<br />

Serial Number, FW Release EC, HW Version EC, Model, Type<br />

FW Release and HW Version M-BUS Module<br />

PS4 00010000 10 All Active Energy Balance<br />

PS5 00000000 00 No one value<br />

PS6 00000000 00 No one value<br />

PS7 00000000 00 No one value<br />

English<br />

Table C6 – Real Time Mask Profile<br />

And so the Profile Real Time mask in HEX will be:<br />

90 FF DF 00 10 00 00 00<br />

- Setting the Profile PARTIAL mask:<br />

Parameter<br />

Set<br />

Value (BIN) Value (HEX) Description<br />

PS0 00100000 20 All Apparent and Reactive Energy Partial<br />

PS1 00000000 00 No one value<br />

PS2 00111000 38<br />

Error Code<br />

Out Of range<br />

Partial Counters Status<br />

PS3 00000000 00 No one value<br />

PS4 00100000 20 All Active Energy Partial<br />

PS5 00000000 00 No one value<br />

PS6 00000000 00 No one value<br />

PS7 00000000 00 No one value<br />

Table C7 – Partial Mask Profile<br />

And so the Profile Partial mask in HEX will be:<br />

20 00 38 00 20 00 00 00<br />

M-<strong>Bus</strong> communication protocol 55