Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS1 11111111 FF<br />
PS2 11011111 DF<br />
Phase 1, 2, 3 Apparent Power<br />
Phase 1, 2, 3 Reactive Power<br />
Phase 1, 2, 3, Sys Voltage<br />
Line 12, 23, 31 Voltage<br />
Phase 1, 2, 3, N, Sys Current<br />
Phase 1, 2, 3, Sys Power Factor<br />
Frequency<br />
Phase Order<br />
Actual Tariff<br />
CT Value, FSA Value<br />
Pri/Sec Value<br />
Error Code<br />
Out Of range<br />
PS3 00000000 00 No one value<br />
Serial Number, FW Release EC, HW Version EC, Model, Type<br />
FW Release and HW Version M-BUS Module<br />
PS4 00010000 10 All Active Energy Balance<br />
PS5 00000000 00 No one value<br />
PS6 00000000 00 No one value<br />
PS7 00000000 00 No one value<br />
English<br />
Table C6 – Real Time Mask Profile<br />
And so the Profile Real Time mask in HEX will be:<br />
90 FF DF 00 10 00 00 00<br />
- Setting the Profile PARTIAL mask:<br />
Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS0 00100000 20 All Apparent and Reactive Energy Partial<br />
PS1 00000000 00 No one value<br />
PS2 00111000 38<br />
Error Code<br />
Out Of range<br />
Partial Counters Status<br />
PS3 00000000 00 No one value<br />
PS4 00100000 20 All Active Energy Partial<br />
PS5 00000000 00 No one value<br />
PS6 00000000 00 No one value<br />
PS7 00000000 00 No one value<br />
Table C7 – Partial Mask Profile<br />
And so the Profile Partial mask in HEX will be:<br />
20 00 38 00 20 00 00 00<br />