And so the Profile Tariff 1 mask in HEX will be:<br />
04 00 18 F0 00 00 00 00<br />
- Setting the Profile TARIFF 2 mask:<br />
English<br />
Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS0 01000000 40 All Apparent and Reactive Energy Tariff 2<br />
PS1 00000000 00 No one value<br />
PS2 00011000 18<br />
Error Code<br />
Out Of range<br />
PS3 00000000 00 No one value<br />
PS4 00001111 0F<br />
PS5 00000000 00 No one value<br />
PS6 00000000 00 No one value<br />
PS7 00000000 00 No one value<br />
Phase 1, 2, 3 Imported Active Energy Tariff 2<br />
3-Phase Imported Active Energy Tariff 2<br />
Phase 1, 2, 3 Exported Active Energy Tariff 2<br />
3-Phase Exported Active Energy Tariff 2<br />
Table C4 – Tariff 2 Mask Profile<br />
And so the Profile Tariff 2 mask in HEX will be:<br />
40 00 18 00 F0 00 00 00<br />
- Setting the Profile TOTAL ENERGY mask:<br />
Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS0 00001000 08 All Apparent and Reactive Energy Total<br />
PS1 00000000 00 No one value<br />
PS2 00011000 18<br />
PS3 00001111 0F<br />
Error Code<br />
Out Of range<br />
PS4 00000000 00 No one value<br />
PS5 00000000 00 No one value<br />
PS6 00000000 00 No one value<br />
PS7 00000000 00 No one value<br />
Table C5 – Total Energy Mask Profile<br />
Phase 1, 2, 3 Imported Active Energy Total<br />
3-Phase Imported Active Energy Total<br />
Phase 1, 2, 3 Exported Active Energy Total<br />
3-Phase Exported Active Energy Total<br />
And so the Profile Total Energy mask in HEX will be:<br />
08 00 18 0F 00 00 00 00<br />
- Setting the Profile REAL TIME mask:<br />
Parameter<br />
Set<br />
Value (BIN) Value (HEX) Description<br />
PS0 10010000 90<br />
All Apparent and Reactive Energy Balance<br />
Phase 1, 2, 3 Active Power<br />
54 M-<strong>Bus</strong> communication protocol