English<br />

Byte Nr. Size (Byte) Value (HEX) Description<br />

YY + 6 1 1x<br />

YY + 7 – YY + 12 6 xx xx xx xx xx xx<br />

MANUFACTURER specific VIFE:<br />

0: 3-Phase Imported Inductive<br />

1: Phase 1 Imported Inductive<br />

2: Phase 2 Imported Inductive<br />

3: Phase 3 Imported Inductive<br />

Table 3.49 – 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Inductive Reactive Energy, Tariff 2<br />

Value: 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Inductive<br />

Reactive Energy, Tariff 2<br />

3.1.4.28 3-Phase, Phase 1, Phase 2 and Phase 3 Exported Inductive Reactive Energy, Tariff 2<br />

Byte Nr. Size (Byte) Value (HEX) Description<br />

YY 1 86 DIF – 48 Bit Integer, 6 Byte; Followed by DIFE<br />

YY + 1 1 A0 DIFE: Tariff 2; Followed by DIFE<br />

YY + 2 1 00 DIFE: Reactive Value<br />

YY + 3 1 FF VIF followed by MANUFACTURER specific VIFE<br />

YY + 4 1 93 VIFE: Reactive Energy, 0.1varh; Followed by VIFE<br />

YY + 5 1 FF VIFE followed by MANUFACTURER specific VIFE<br />

YY + 6 1 2x<br />

YY + 7 – YY + 12 6 xx xx xx xx xx xx<br />

MANUFACTURER specific VIFE:<br />

0: 3-Phase Exported Inductive<br />

1: Phase 1 Exported Inductive<br />

2: Phase 2 Exported Inductive<br />

3: Phase 3 Exported Inductive<br />

Table 3.50 – 3-Phase, Phase 1, Phase 2 and Phase 3 Exported Inductive Reactive Energy, Tariff 2<br />

Value: 3-Phase, Phase 1, Phase 2 and Phase 3 Exported Inductive<br />

Reactive Energy, Tariff 2<br />

3.1.4.29 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Capacitive Reactive Energy, Tariff 2<br />

Byte Nr. Size (Byte) Value (HEX) Description<br />

YY 1 86 DIF – 48 Bit Integer, 6 Byte; Followed by DIFE<br />

YY + 1 1 A0 DIFE: Tariff 2; Followed by DIFE<br />

YY + 2 1 00 DIFE: Reactive Value<br />

YY + 3 1 FF VIF followed by MANUFACTURER specific VIFE<br />

YY + 4 1 93<br />

MANUFACTURER specific VIFE: Reactive Energy, 0.1varh;<br />

Followed by VIFE<br />

YY + 5 1 FF VIFE followed by MANUFACTURER specific VIFE<br />

YY + 6 1 3x<br />

YY + 7 – YY + 12 6 xx xx xx xx xx xx<br />

MANUFACTURER specific VIFE:<br />

0: 3-Phase Imported Capacitive<br />

1: Phase 1 Imported Capacitive<br />

2: Phase 2 Imported Capacitive<br />

3: Phase 3 Imported Capacitive<br />

Value: 3-Phase, Phase 1, Phase 2 and Phase 3 Imported<br />

Capacitive Reactive Energy, Tariff 2<br />

Table 3.51 – 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Capacitive Reactive Energy, Tariff 2<br />