M-Bus Communication Protocol - Gossen-Metrawatt
M-Bus Communication Protocol - Gossen-Metrawatt
M-Bus Communication Protocol - Gossen-Metrawatt
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
3.1.4.11 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Active Energy, Tariff 1<br />
English<br />
Byte Nr. Size (Byte) Value (HEX) Description<br />
YY 1 86 DIF – 48 Bit Integer, 6 Byte; Followed by DIFE<br />
YY + 1 1 10 DIFE: Tariff 1<br />
YY + 2 1 82 VIF: Energy, 0.1Wh; Followed by VIFE<br />
YY + 3 1 FF VIF followed by MANUFACTURER specific VIFE<br />
YY + 4 1 80 VIFE: Imported Energy; Followed by VIFE<br />
YY + 5 1 FF VIFE followed by MANUFACTURER specific VIFE<br />
YY + 6 1 0x<br />
YY + 7 – YY + 12 6 xx xx xx xx xx xx<br />
MANUFACTURER specific VIFE:<br />
0: 3-Phase<br />
1: Phase 1<br />
2: Phase 2<br />
3: Phase 3<br />
Value: 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Active<br />
Energy, Tariff 1<br />
Table 3.33 – 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Active Energy, Tariff 1<br />
3.1.4.12 3-Phase, Phase 1, Phase 2 and Phase 3 Exported Active Energy, Tariff 1<br />
Byte Nr. Size (Byte) Value (HEX) Description<br />
YY 1 86 DIF – 48 Bit Integer, 6 Byte; Followed by DIFE<br />
YY + 1 1 10 DIFE: Tariff 1<br />
YY + 2 1 82 VIF: Energy, 0.1Wh; Followed by VIFE<br />
YY + 3 1 FF VIFE followed by MANUFACTURER specific VIFE<br />
YY + 4 1 81 VIFE: Exported Energy; Followed by VIFE<br />
YY + 5 1 FF VIFE followed by MANUFACTURER specific VIFE<br />
YY + 6 1 0x<br />
YY + 7 – YY + 12 6 xx xx xx xx xx xx<br />
MANUFACTURER specific VIFE:<br />
0: 3-Phase<br />
1: Phase 1<br />
2: Phase 2<br />
3: Phase 3<br />
Table 3.34 – 3-Phase, Phase 1, Phase 2 and Phase 3 Exported Active Energy, Tariff 1<br />
Value: 3-Phase, Phase 1, Phase 2 and Phase 3 Exported Active<br />
Energy, Tariff 1<br />
3.1.4.13 3-Phase, Phase 1, Phase 2 and Phase 3 Imported Inductive Apparent Energy, Tariff 1<br />
Byte Nr. Size (Byte) Value (HEX) Description<br />
YY 1 86 DIF – 48 Bit Integer, 6 Byte; Followed by DIFE<br />
YY + 1 1 90 DIFE: Tariff 1; Followed by DIFE<br />
YY + 2 1 40 DIFE: Apparent Value<br />
YY + 3 1 FF VIF followed by MANUFACTURER specific VIFE<br />
YY + 4 1 91 VIFE: Apparent Energy, 0.1VAh; Followed by VIFE<br />
YY + 5 1 FF VIFE followed by MANUFACTURER specific VIFE<br />
YY + 6 – YY + 11 1 1x<br />
MANUFACTURER specific VIFE:<br />
0: 3-Phase Imported Inductive<br />
1: Phase 1 Imported Inductive<br />
2: Phase 2 Imported Inductive<br />
3: Phase 3 Imported Inductive<br />
32 M-<strong>Bus</strong> communication protocol