RE: Wastewater Treatment Plant Inspection<br />

AFIN: 75-00024<br />

NPDES Permit No.: AR0033421<br />

Dear <strong>Mayor</strong> <strong>McGee</strong>:<br />

On February 18, <strong>2010</strong>, I performed a routine compliance inspection <strong>of</strong> the waste water treatment<br />

facility in accordance with the provisions <strong>of</strong> the Federal Clean Water Act, the Arkansas Water and<br />

Air Pollution Control Act, and the regulations promulgated thereunder. This inspection revealed<br />

the following violations:<br />

TSS and BOD5 grab samples are not being stored at < 6 C prior to compositing. This is a violation <strong>of</strong> Part<br />

III, Section C. 3 <strong>of</strong> the permit. The facility collects three grab samples, one each hour, for 3-hour composite<br />

sampling. Mr. Parks states that he was told by the inspector to store these samples in an incubator at 20 C<br />

during the previous inspection. Mr. Parks reported that Standard methods required cooling to < 4 C. I<br />

reported that 40 CFR Part 136 requires cooling to < 6 C. Mr. Parks reported that the facility would start<br />

storing samples at < 4 C.<br />

The above items require your immediate attention. Please submit a written response to these<br />

findings to the Water Division Enforcement Branch <strong>of</strong> this Department at the following address:<br />

Water Division Enforcement Section<br />

Arkansas Department <strong>of</strong> Environmental Quality<br />

5301 Northshore Drive<br />

North Little Rock, AR 72118-5317<br />

This response should contain detailed documentation describing the course <strong>of</strong> action taken to<br />

correct the items noted. This corrective action should be completed as soon as possible, and the<br />

written response is due by <strong>March</strong> 26, <strong>2010</strong>.<br />

For additional information you may contact the enforcement branch by telephone at 501-682-0639<br />

or by fax at 501-682-0910.


<strong>Mayor</strong> <strong>Carolyn</strong> <strong>McGee</strong>, <strong>City</strong> <strong>of</strong> <strong>Dardanelle</strong><br />

<strong>March</strong> 1, <strong>2010</strong><br />

Page 2<br />

If I can be <strong>of</strong> any assistance, please contact me at 479-968-7339 extension 14.<br />

Sincerely,<br />

Travis Harmon<br />

District 5 Field Inspector<br />

Water Division<br />

harmont@adeq.state.ar.us<br />

cc:<br />

Water Division Enforcement Branch<br />

Water Division Permits Branch<br />

NPDES R eport Page 2


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

Form Approved<br />

OMB No. 2040-0003<br />

UNITED STATES ENVIRONMENTAL PROTECTION AGENCY<br />

Washington, D.C. 20460<br />

NPDES Compliance Inspection Report<br />

Section A: National Data System Coding<br />

Transaction Code NPDES Yr/Mo/Day Inspec. Type Inspector Fac. Type<br />

1 N 2 5 3 A R 0 0 3 3 4 2 1 11 <strong>12</strong> 1 0 0 2 1 8 17 18 C 19 S 20 1<br />

A F I N 7 5 --- 0 0 0 2 4<br />

Remarks<br />

Inspection Work Days Facility Evaluation Rating BI QA -------------------------------Reserved------------------------------<br />

67<br />

0 0<br />

69 70 3 71 N 72 N 73 74 75 80<br />

Section B: Facility Data<br />

Name and Location <strong>of</strong> Facility Inspected (For industrial users discharging to POTW, also<br />

include POTW name and NPDES permit number)<br />

<strong>City</strong> <strong>of</strong> <strong>Dardanelle</strong><br />

10532 Water Plant Rd<br />

<strong>Dardanelle</strong>, AR 72834<br />

Name(s) <strong>of</strong> On-Site Representative(s)/Title(s)/Phone and Fax Number(s)<br />

H. Dale Parks/ Chief Operator/ 479-229-4538<br />

Entry Time/Date<br />

09:30/ 2/18/<strong>2010</strong><br />

Exit Time/Date<br />

1:30/ 2/18/<strong>2010</strong><br />

Permit Effective Date<br />

10/1/2009<br />

Permit Expiration Date<br />

9/30/2014<br />

Other Facility Data<br />

Name, Address <strong>of</strong> Responsible Official/Title/Phone and Fax Number<br />

<strong>Carolyn</strong> <strong>McGee</strong>/ <strong>Mayor</strong>/ 479-229-3992<br />

<strong>116</strong> N 1 st St<br />

<strong>Dardanelle</strong>, AR 72834<br />

Yesþ<br />

Contacted<br />

No¨<br />

Section C: Areas Evaluated During Inspection<br />

(S = Satisfactory, M = Marginal, U = Unsatisfactory, N = Not Evaluated)<br />

S Permit S Flow Measurement S Operations & Maintenance M Sampling<br />

S Records/Reports S Self-Monitoring Program S Sludge Handling/Disposal N Pollution Prevention<br />

S Facility Site Review N Compliance Schedules N Pretreatment N Multimedia<br />

N Effluent/Receiving Waters S Laboratory N Storm Water N Other:<br />

Section D: Summary <strong>of</strong> Findings/Comments (Attach additional sheets if necessary)<br />

1. TSS and BOD5 grab samples are not being stored at < 6 C prior to compositing.<br />

2. TSS monthly load rates were under-reported. by 5-9 lb/day in the DMRs. The under-reported values do not affect<br />

compliance status with TSS limits. The highest calculated monthly TSS load was 43 lb/day and the facility limit is<br />

245 lb/day.<br />

3. FCB monthly average was over-reported in 09/2009 due to rounding <strong>of</strong> log values up to 2.<br />

Name(s) and Signature(s) <strong>of</strong> Inspector(s)<br />

Travis Harmon<br />

Agency/Office/Telephone/Fax<br />

Arkansas Department <strong>of</strong> Environmental Quality /<br />

Russellville / 479-968-7339 x 14 / 479-968-7321<br />

Date<br />

3/2/<strong>2010</strong><br />

Signature <strong>of</strong> Reviewer Agency/Office/Phone and Fax Numbers Date<br />

NPDES R eport Page 3


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

SECTION A: PERMIT VERIFICATION<br />

PERMIT SATISFACTORILY ADDRESSES OBSERVATIONS<br />

DETAILS:<br />

þS ¨M ¨U ¨NA ¨NE<br />

1. CORRECT NAME AND MAILING ADDRESS OF PERMITTEE: þY ¨N ¨NA ¨NE<br />

2. NOTIFICATION GIVEN TO EPA/STATE OF NEW DIFFERENT OR INCREASED DISCHARGES: ¨Y ¨N þNA ¨NE<br />

3. NUMBER AND LOCATION OF DISCHARGE POINTS AS DESCRIBED IN PERMIT: þY ¨N ¨NA ¨NE<br />

4. ALL DISCHARGES ARE PERMITTED: þY ¨N ¨NA ¨NE<br />

SECTION B: RECORDKEEPING AND REPORTING EVALUATION<br />

RECORDS AND REPORTS MAINTAINED AS REQUIRED BY PERMIT<br />

DETAILS:<br />

þS ¨M ¨U ¨NA ¨NE<br />

1. ANALYTICAL RESULTS CONSISTENT WITH DATA REPORTED ON DMRS: þY ¨N ¨NA ¨NE<br />

2. SAMPLING AND ANALYSES DATA ADEQUATE AND INCLUDE: ¨S ¨M ¨U ¨NA ¨NE<br />

a. DATES AND TIME(S) OF SAMPLING: þY ¨N ¨NA ¨NE<br />

b. EXACT LOCATION(S) OF SAMPLING: þY ¨N ¨NA ¨NE<br />

c. NAME OF INDIVIDUAL PERFORMING SAMPLING: þY ¨N ¨NA ¨NE<br />

d. ANALYTICAL METHODS AND TECHNIQUES: þY ¨N ¨NA ¨NE<br />

e. RESULTS OF CALIBRATIONS: þY ¨N ¨NA ¨NE<br />

f. RESULTS OF ANALYSES: þY ¨N ¨NA ¨NE<br />

g. DATES AND TIMES OF ANALYSES: þY ¨N ¨NA ¨NE<br />

h. NAME OF PERSON(S) PERFORMING ANALYSES: þY ¨N ¨NA ¨NE<br />

3. LABORATORY EQUIPMENT CALIBRATION AND MAINTENANCE RECORDS ADEQUATE: þS ¨M ¨U ¨NA ¨NE<br />

4. PLANT RECORDS INCLUDE SCHEDULES, DATES OF EQUIPMENT MAINTENANCE AND REPAIR: þS ¨M ¨U ¨NA ¨NE<br />

5. EFFLUENT LOADINGS CALCULATED USING DAILY EFFLUENT FLOW AND DAILY ANALYTICAL DATA: þY ¨N ¨NA ¨NE<br />

SECTION C: OPERATIONS AND MAINTENANCE<br />

TREATMENT FACILITY PROPERLY OPERATED AND MAINTAINED<br />

DETAILS:<br />

þS ¨M ¨U ¨NA ¨NE<br />

1. TREATMENT UNITS PROPERLY OPERATED: þS ¨M ¨U ¨NA ¨NE<br />

2. TREATMENT UNITS PROPERLY MAINTAINED: þS ¨M ¨U ¨NA ¨NE<br />

3. STANDBY POW ER OR OTHER EQUIVALENT PROVIDED: Generator on-site. þS ¨M ¨U ¨NA ¨NE<br />

4. ADEQUATE ALARM SYSTEM FOR POW ER OR EQUIPMENT FAILURES AVAILABLE: Guardtronic calls after 30 min power failure. þS ¨M ¨U ¨NA ¨NE<br />

5. ALL NEEDED TREATMENT UNITS IN SERVICE: þS ¨M ¨U ¨NA ¨NE<br />

6. ADEQUATE NUMBER OF QUALIFIED OPERATORS PROVIDED: Mr. Dale Parks (III) and Blake Robinson (I). þS ¨M ¨U ¨NA ¨NE<br />

7. SPARE PARTS AND SUPPLIES INVENTORY MAINTAINED: þS ¨M ¨U ¨NA ¨NE<br />

8. OPERATION AND MAINTENANCE MANUAL AVAILABLE: þY ¨N ¨NA ¨NE<br />

9. STANDARD OPERATING PROCEDURES AND SCHEDULES ESTABLISHED: þY ¨N ¨NA ¨NE<br />

10. PROCEDURES FOR EMERGENCY TREATMENT CONTROL ESTABLISHED: þY ¨N ¨NA ¨NE<br />

11. HAVE BYPASSES/OVERFLOWS OCCURRED AT THE PLANT OR IN THE COLLECTION SYSTEM IN THE LAST YEAR: Bar screen<br />

became clogged and overflowed. Some material on ground during inspection. Facility could not clean yet due to ice/snow cover. þY ¨N ¨NA ¨NE<br />

Facility now has written instructions in place for staff to check and/or clear bar screen.<br />

<strong>12</strong>. IF SO, HAS THE REGULATORY AGENCY BEEN NOTIFIED: Was contained at plant. ¨Y ¨N þNA ¨NE<br />

13. HAS CORRECTIVE ACTION BEEN TAKEN TO PREVENT ADDITIONAL BYPASSES/OVERFLOWS: þY ¨N ¨NA ¨NE<br />

14. HAVE ANY HYDRAULIC OVERLOADS OCCURRED AT THE TREATMENT PLANT: þY ¨N ¨NA ¨NE<br />

15. IF SO, DID PERMIT VIOLATIONS OCCUR AS A RESULT: ¨Y þN ¨NA ¨NE<br />

NPDES R eport Page 4


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

SECTION D: SAMPLING<br />

PERMITTEE SAMPLING MEETS PERMIT REQUIREMENTS<br />

DETAILS:<br />

¨S þM ¨U ¨NA ¨NE<br />

1. SAMPLES TAKEN AT SITE(S) SPECIFIED IN PERMIT: þY ¨N ¨NA ¨NE<br />

2. LOCATIONS ADEQUATE FOR REPRESENTATIVE SAMPLES: þY ¨N ¨NA ¨NE<br />

3. FLOW PROPORTIONED SAMPLES OBTAINED W HEN REQUIRED BY PERMIT: Facility reads flow each hour during compositing<br />

sampling and includes a representative proportion <strong>of</strong> each hourly sample in the composite sample.<br />

þY ¨N ¨NA ¨NE<br />

4. SAMPLING AND ANALYSES COMPLETED ON PARAMETERS SPECIFIED IN PERMIT: þY ¨N ¨NA ¨NE<br />

5. SAMPLING AND ANALYSES PERFORMED AT FREQUENCY SPECIFIED IN PERMIT: þY ¨N ¨NA ¨NE<br />

6. SAMPLE COLLECTION PROCEDURES ADEQUATE: þY ¨N ¨NA ¨NE<br />

a. SAMPLES REFRIGERATED DURING COMPOSITING: 3 hr composite samples are placed in incubator at 20 C prior to compositing.<br />

Mr. Parks reports being told to store these samples at 20 C during the previous inspection and was doing so.<br />

¨Y þN ¨NA ¨NE<br />

b. PROPER PRESERVATION TECHNIQUES USED: Samples are analyzed or processed on-site within 15 minutes <strong>of</strong> collection.<br />

Excludes 3 hr composite samples (BOD and TSS).<br />

þY ¨N ¨NA ¨NE<br />

c. CONTAINERS AND SAMPLE HOLDING TIMES CONFORM TO 40 CFR 136: þY ¨N ¨NA ¨NE<br />

7. IF MONITORING IS PERFORMED MORE OFTEN THAN REQUIRED ARE RESULTS REPORTED ON THE DMR: ¨Y ¨N þNA ¨NE<br />

SECTION E: FLOW MEASUREMENT<br />

PERMITTEE FLOW MEASUREMENT MEETS PERMIT REQUIREMENTS<br />

DETAILS:<br />

þS ¨M ¨U ¨NA ¨NE<br />

1. PRIMARY FLOW MEASUREMENT DEVICE PROPERLY INSTALLED AND MAINTAINED: TYPE OF DEVICE: 9 in Parshall flume þY ¨N ¨NA ¨NE<br />

2. FLOW MEASURED AT EACH OUTFALL AS REQUIRED: þY ¨N ¨NA ¨NE<br />

3. SECONDARY INSTRUMENTS (TOTALIZERS, RECORDERS, ETC.) PROPERLY OPERATED AND MAINTAINED: þY ¨N ¨NA ¨NE<br />

4. CALIBRATION FREQUENCY ADEQUATE: þY ¨N ¨NA ¨NE<br />

5. RECORDS MAINTAINED OF CALIBRATION PROCEDURES: þY ¨N ¨NA ¨NE<br />

6. CALIBRATION CHECKS DONE TO ASSURE CONTINUED COMPLIANCE: 2 or 3 times each year (not including annual calibration). þY ¨N ¨NA ¨NE<br />

7. FLOW ENTERING DEVICE WELL DISTRIBUTED ACROSS THE CHANN EL AND FREE OF TURBULENCE: þY ¨N ¨NA ¨NE<br />

8. FLOW MEASUREMENT EQUIPMENT ADEQUATE TO HANDLE EXPECTED RANGE OF FLOW RATES: þY ¨N ¨NA ¨NE<br />

9. HEAD MEASURED AT PROPER LOCATION: þY ¨N ¨NA ¨NE<br />

SECTION F: LABORATORY<br />

PERMITTEE LABORATORY PROCEDURES MEET PERMIT REQUIREMENTS<br />

DETAILS:<br />

1. EPA APPROVED ANALYTICAL PROCEDURES USED (40 CFR 136.3 FOR LIQUIDS, 503.8(B) FOR SLUDGES) : Using Standard<br />

methods.<br />

þS ¨M ¨U ¨NA ¨NE<br />

þY ¨N ¨NA ¨NE<br />

2. IF ALTERNATIVE ANALYTICAL PROCEDURES ARE USED, PROPER APPROVAL HAS BEEN OBTAINED: ¨Y ¨N þNA ¨NE<br />

3. SATISFACTORY CALIBRATION AND MAINTENANCE OF INSTRUMENTS AND EQUIPMENT: þY ¨N ¨NA ¨NE<br />

4. QUALITY CONTROL PROCEDURES ADEQUATE: þY ¨N ¨NA ¨NE<br />

5. DUPLICATE SAMPLES ARE ANALYZED >10% OF THE TIME: 100% <strong>of</strong> time. þY ¨N ¨NA ¨NE<br />

6. SPIKED SAMPLES ARE ANALYZED >10% OF THE TIME: Blanks analyzed. ¨Y þN ¨NA ¨NE<br />

7. COMMERCIAL LABORATORY USED: N/A ¨Y þN ¨NA ¨NE<br />

a. LAB NAME:<br />

b. LAB ADDRESS:<br />

c. PARAMETERS PERFORMED:<br />

8. BIOMONITORING PROCEDURES ADEQUATE: ¨Y ¨N þNA ¨NE<br />

a. PROPER ORGANISMS USED: ¨Y ¨N þNA ¨NE<br />

b. PROPER DILUTION SERIES FOLLOWED: ¨Y ¨N þNA ¨NE<br />

c. PROPER TEST METHODS AND DURAT ION: ¨Y ¨N þNA ¨NE<br />

d. RETESTS AND/OR TRE PERFORMED AS REQUIRED: ¨Y ¨N þNA ¨NE<br />

NPDES R eport Page 5


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

SECTION G: EFFLUENT/RECEIVING WATERS OBSERVATIONS<br />

BASED ON VISUAL OBSERVATIONS ONLY<br />

¨S ¨M ¨U ¨NA þNE<br />

DETAILS: Arkansas River. Could not view effluent as outfall was submerged during the inspection. I did not view<br />

any foam, solids, or turbidity as effluent left the flume.<br />

OUTFALL #: OIL SHEEN GREASE TURBIDITY VISIBLE FOAM FLOATING SOLIDS COLOR OTHER<br />

001<br />

SECTION H: SLUDGE DISPOSAL<br />

SLUDGE DISPOSAL MEETS PERMIT REQUIREMENTS<br />

þS ¨M ¨U ¨NA ¨NE<br />

DETAILS: Dried in drying beds and disposed <strong>of</strong> at Yell Co. landfill.<br />

1. SLUDGE MANAGEMENT ADEQUATE TO MAINTAIN EFFLUENT QUALITY: þS ¨M ¨U ¨NA ¨NE<br />

2. SLUDGE RECORDS MAINTAINED AS REQUIRED BY 40 CFR 503: ¨S ¨M ¨U þNA ¨NE<br />

3. FOR LAND APPLIED SLUDGE, TYPE OF LAND APPLIED TO: (E.G., FOREST, AGRICULTURAL, PUBLIC CONTACT SITE):<br />

SECTION I: SAMPLING INSPECTION PROCEDURES<br />

SAMPLE RESULTS WITHIN PERMIT REQUIREMENTS<br />

¨S ¨M ¨U þNA ¨NE<br />

DETAILS: No samples collected.<br />

1. SAMPLES OBTAINED THIS INSPECTION: ¨Y ¨N þNA ¨NE<br />

2. TYPE OF SAMPLE: ¨GRAB: ¨COMPOSITE: METHOD: FREQUENCY:<br />

3. SAMPLES PRESERVED: ¨Y ¨N þNA ¨NE<br />

4. FLOW PROPORTIONED SAMPLES OBTAINED: ¨Y ¨N þNA ¨NE<br />

5. SAMPLE OBTAINED FROM FACILITY'S SAMPLING DEVICE: ¨Y ¨N þNA ¨NE<br />

6. SAMPLE REPRESENTATIVE OF VOLUME AND NATURE OF DISCHARG E: ¨Y ¨N þNA ¨NE<br />

7. SAMPLE SPLIT WITH PERMITTEE: ¨Y ¨N þNA ¨NE<br />

8. CHAIN-OF-CUSTODY PROCEDURES EMPLOYED: ¨Y ¨N þNA ¨NE<br />

9. SAMPLES COLLECTED IN ACCORDANCE WITH PERMIT: ¨Y ¨N þNA ¨NE<br />

SECTION J: STORM WATER POLLUTION PREVENTION PLAN<br />

STORM WATER MANAGEMENT MEETS PERMIT REQUIREMENTS<br />

¨S ¨M ¨U þNA ¨NE<br />

DETAILS:<br />

1. SWPPP UPDATED AS NEEDED: DATE OF LAST UPDATE: ¨Y ¨N þNA ¨NE<br />

2. SITE MAP INCLUDING ALL DISCHARGES AND SURFACE WATERS: ¨Y ¨N þNA ¨NE<br />

3. POLLUTION PREVENTION TEAM IDENTIFIED: ¨Y ¨N þNA ¨NE<br />

4. POLLUTION PREVENTION TEAM PROPERLY TRAINED: ¨Y ¨N þNA ¨NE<br />

5. LIST OF POTENTIAL POLLUTANT SOURCES: ¨Y ¨N þNA ¨NE<br />

6. LIST OF POTENTIAL SOURCES AND PAST SPILLS AND LEAKS: ¨Y ¨N þNA ¨NE<br />

7. ALL NON-STORM WATER DISCHARGES ARE AUTHORIZED: ¨Y ¨N þNA ¨NE<br />

8. LIST OF STRUCTURAL BMPS: ¨Y ¨N þNA ¨NE<br />

9. LIST OF NON-STRUCTURAL BMPS: ¨Y ¨N þNA ¨NE<br />

10. BMPS PROPERLY OPERATED AND MAINTAINED: ¨Y ¨N þNA ¨NE<br />

11. INSPECTIONS CONDUCT ED AS REQUIRED: ¨Y ¨N þNA ¨NE<br />

NPDES R eport Page 6


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

FLOW CALCULATION SHEET<br />

Date: 2/18/<strong>2010</strong> Time: 11:35<br />

Head in Inches: 5 3/4 Feet: 0.4792<br />

Type & Size <strong>of</strong> Primary Flow Measurement Device:<br />

9 inch Parshall flume.<br />

Name & Model <strong>of</strong> Secondary Flow Measurement Device:<br />

Milltronics Hydroranger Totalizer.<br />

Date <strong>of</strong> last Calibration <strong>of</strong> Secondary Flow Device:<br />

1/8/<strong>2010</strong>.<br />

Recorded Flow at Date & Time Listed Above: 462 GPM (Facility Flow Meter)<br />

Calculated Flow at Date & Time Listed Above:<br />

448.3 GPM<br />

(Flow is calculated using flow charts in: ISCO Open Channel Flow Measurement Handbook-5 th Edition)<br />

% Error =<br />

% Error =<br />

Recorded Value - Calculated Value<br />

Calculated Value<br />

462 - 448.3<br />

448.3<br />

X 100<br />

X 100<br />

% Error =<br />

13.7<br />

448.3<br />

X 100<br />

% Error = 0.0305598929 X 100<br />

% Error = 3.05598929 % 3.1 %<br />

Comments: Within 10%.<br />

NPDES R eport Page 7


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

DMR Calculation Check<br />

Reporting Period: From 09 09 01 To 09 09 30<br />

Year Month Day Year Month Day<br />

Parameter Checked:<br />

TSS<br />

Loading<br />

Concentration<br />

Mass<br />

Monthly<br />

Mo. Avg. - lbs/day Mo. Avg. - mg/l 7-day Avg. - mg/l<br />

Reported Value: 31 7.3 10<br />

Calculated Value: 36 7.3 10<br />

Permit Value: 245 30 45<br />

If calculated value does not equal reported value, explain:<br />

Results: (9/30/09, .552 MGD, 8 mg/l), (9/23/09, 0.632 MGD, 4 mg/l), (9/9/09, 0.608 MGD, 10 mg/l).<br />

NPDES R eport Page 8


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

DMR Calculation Check<br />

Reporting Period: From 09 10 01 To 09 10 31<br />

Year Month Day Year Month Day<br />

Parameter Checked:<br />

TSS<br />

Loading<br />

Concentration<br />

Mass<br />

Monthly<br />

Mo. Avg. - lbs/day Mo. Avg. - mg/l 7-day Avg. - mg/l<br />

Reported Value: 37.5 9.3 10<br />

Calculated Value: 43 9.3 <strong>12</strong>*<br />

Permit Value: 245 30 45<br />

If calculated value does not equal reported value, explain:<br />

Results: (10/7/09, 0.552 MGD, 10 mg/l), (10/22/09, 0.560 MGD, <strong>12</strong> mg/l), (10/28/09, 0.592 MGD, 6 mg/l).<br />

*No more than one sample collected in a week. Results were 10 mg/l on 10/7, <strong>12</strong> mg/l on 10/22, and 6 mg/l on<br />

10/28.<br />

NPDES R eport Page 9


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

DMR Calculation Check<br />

Reporting Period: From 09 11 01 To 09 11 30<br />

Year Month Day Year Month Day<br />

Parameter Checked:<br />

TSS<br />

Loading<br />

Concentration<br />

Mass<br />

Monthly<br />

Mo. Avg. - lbs/day Mo. Avg. - mg/l 7-day Avg. - mg/l<br />

Reported Value: 27 8 9<br />

Calculated Value: 36 8 10<br />

Permit Value: 245 30 45<br />

If calculated value does not equal reported value, explain:<br />

Results: (11/<strong>12</strong>/09, 0.536 MGD, 6 mg/l), (11/20/09, 0.560 MGD, 10 mg/l), (11/25/09, 0.544 MGD, 8 mg/l).<br />

NPDES R eport Page 10


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

DMR Calculation Check<br />

Reporting Period: From 09 09 01 To 09 09 30<br />

Year Month Day Year Month Day<br />

Parameter Checked:<br />

FCB<br />

Loading<br />

Concentration<br />

Mass<br />

Monthly<br />

Mo. Avg. - lbs/day Mo. Avg. - mg/l 7-day Avg. - mg/l<br />

Reported Value: 100 100<br />

Calculated Value: 83* 98*<br />

Permit Value: 200 400<br />

If calculated value does not equal reported value, explain: Rounding <strong>of</strong> logs.<br />

Results (9/9/09 72, <strong>12</strong>1, 82, 130), (9/23/09 54, 91), (9/30/09 67, 103).<br />

* Facility is rounding log values to 2. For example, for 54 colonies, the log <strong>of</strong> 54 is 1.732. The<br />

facility rounds 1.732 to 2 and averages before taking the anti-log.<br />

2 + 2 = 4, average 2, and anti-log <strong>of</strong> 2 is 100 vs.<br />

1.732 + 1.959 = 3.691, average 1.845, and anti-log <strong>of</strong> 1.845 is 69.9.<br />

NPDES R eport Page 11


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

NPDES Compliance Inspection Report<br />

Further Explanation<br />

The facility collects three grab samples, one each hour, for a 3 hour composite sample. TSS and BOD5 grab samples<br />

are not being stored at < 6 C prior to compositing. Mr. Parks states that he was told by the inspector to store these<br />

samples in an incubator at 20 C during the previous inspection.<br />

I reviewed DMR and analysis data for 09/2009, 10/2009, and 11/2009. I identified some differences in the TSS monthly<br />

load rate reported in the DMRs and my calculated monthly TSS load rates. TSS monthly load rates were under-reported<br />

by 5-9 lb/day in the DMRs. The under-reported values do not affect compliance status with TSS limits. The highest calculated monthly<br />

TSS load was 43 lb/day and the facility limit is 245 lb/day. ADEQ inspector Amy Beck visited the facility with me on<br />

2/26/<strong>2010</strong>. We went through the process <strong>of</strong> calculating values for the DMR. Mr. Parks requested copies which show<br />

how monthly load rates should be calculated.<br />

FCB colonies monthly average appear to be over-reported on the 09/2009 DMR due to rounding. The facility is<br />

correctly calculating the monthly average; however, the log values were rounded to 2 prior to determining the average<br />

<strong>of</strong> the log values. For example (for 9/23) sampling the logs <strong>of</strong> 54 and 91 were both rounded to 2 with an average <strong>of</strong> 2<br />

instead <strong>of</strong> log <strong>of</strong> 54 = 1.7 + log <strong>of</strong> 91 = 1.9 = 3.6 then averaged to 1.8. The anti-log <strong>of</strong> 2 = 100 colonies while the antilog<br />

<strong>of</strong> 1.8 = 63 colonies. For the month <strong>of</strong> September 2009, I determined a monthly average <strong>of</strong> 83 colonies while a<br />

monthly average <strong>of</strong> 100 colonies was reported in the DMR.<br />

NPDES R eport Page <strong>12</strong>


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

Location:<br />

Water Division NPDES Photographic Evidence Sheet<br />

Photos <strong>of</strong> records obtained from the facility.<br />

Photographer: Travis Harmon Witness: None<br />

Photo # 1 Of 3 Date: 2/26/<strong>2010</strong> Time: 15:43<br />

Description:<br />

Flow and monthly load (TSS) calculations. 220 on the sheet is equivalent <strong>of</strong> 22,000<br />

gallons/hour as the totalizer reads gallons x 100.<br />

Photographer: Travis Harmon Witness: None<br />

Photo # 2 Of 3 Date: 2/26/<strong>2010</strong> Time: 15:42<br />

Description:<br />

Facility FCB geometric mean calculations. Shows log values rounded to 2 prior to<br />

averaging and calculating anti-log.<br />

NPDES R eport Page 13


ADEQ Water NPDES Inspection AFIN: 75-00024 Permit #: AR0033421<br />

Location:<br />

Water Division NPDES Photographic Evidence Sheet<br />

<strong>City</strong> <strong>of</strong> <strong>Dardanelle</strong> POTW.<br />

Photographer: Travis Harmon Witness: None<br />

Photo # 3 Of 3 Date: 2/18/<strong>2010</strong> Time: 11:21<br />

Description:<br />

Nocardia bacteria generating foam in clarifier. Has been an on-going issue at the facility<br />

but does not appear to be impacting the facilitys ability to meet effluent limits.<br />

NPDES R eport Page 14

Hooray! Your file is uploaded and ready to be published.