ÇUKUROVA UNIVERSITY INSTITUTE OF NATURAL AND APPLIED ...
ÇUKUROVA UNIVERSITY INSTITUTE OF NATURAL AND APPLIED ... ÇUKUROVA UNIVERSITY INSTITUTE OF NATURAL AND APPLIED ...
3. FUNDAMENTALS OF DVR Mustafa İNCİ If the distribution circuit is weak there is need to inject small compensation voltage to operate correctly. During short circuit operation, the injected voltages and magnetic fluxes are virtually zero thereby full load current pass through the primary. The DVR will be most of the time in normal mode operation. During standby mode normal operation), the short circuit impedance of the injection transformer determines the voltage drop across the DVR (Teke, 2005). 3.3.2.3. Injection Mode The primary function of Dynamic Voltage Restorer is compensating voltage disturbances on distribution system. To achieve compensation, three single-phase ac voltages are injected in series with required magnitude, phase and wave shape. The types of voltage sags, load conditions and power rating of DVR will determine the possibility of compensating voltage sag (Teke, 2005). 3.3.3. Voltage Injection Strategies The way in which the dynamic voltage restorer (DVR) is used during the voltage injection mode depends upon several limiting factors such as: DVR power rating, load conditions, and voltage-sag type. For example, some loads are sensitive to phase-angel jumps, some others are sensitive to a change in voltage magnitude and some others are tolerant to all these disturbances. Therefore the control strategies to be applied depend upon the load characteristics (Shazly et al., 2013). There are four different methods of DVR voltage injection strategies: • Pre-sag compensation • In-phase compensation • In-phase advanced compensation 33
3. FUNDAMENTALS OF DVR Mustafa İNCİ 3.3.3.1. Pre-sag compensation The pre-sag compensation method tracks supply voltage continuously load voltage during a fault to restore the pre-fault condition. Figure 3.13 shows the singlephase vector diagram of the pre-sag compensation. In this method, the load voltage can be restored ideally, but injected active power cannot be controlled and is determined by external conditions such as the type of faults and load condition (Quirl et al., 2006). Figure 3.13. Vector diagram of pre-sag compensation 3.3.3.2. In-phase compensation As already mentioned, the pre-sag compensation does not lead to a minimized voltage amplitude. This can be realized with the in-phase strategy, which is designed to control the DVR with a minimum output voltage. In Figure 3.14, the voltages for this strategy are depicted. In contrast to the pre-sag version, the voltage is now compensated in phase to the grid voltage after the sag. Hence, the required voltage amplitude is minimized, but the phase jump is not compensated (Meyer et al., 2008). 34
- Page 1 and 2: ÇUKUROVA UNIVERSITY INSTITUTE OF N
- Page 3 and 4: ABSTRACT MSc THESIS MODELING AND AN
- Page 5 and 6: ACKNOWLEDGEMENTS First and foremost
- Page 7 and 8: 3.2.2.1. Inverters ................
- Page 9 and 10: VII
- Page 12 and 13: LIST OF FIGURES PAGES Figure 1.1. D
- Page 14 and 15: Figure 5.3. Injected voltages by us
- Page 16 and 17: LIST OF SYMBOLS C : DC Link Capacit
- Page 18 and 19: LIST OF ABBREVATIONS A AC APF ASD C
- Page 20: 1. INTRODUCTION Mustafa İNCİ 1. I
- Page 23 and 24: 1. INTRODUCTION Mustafa İNCİ 4
- Page 25 and 26: 2. POWER QUALITY Mustafa İNCİ 2.1
- Page 27 and 28: 2. POWER QUALITY Mustafa İNCİ 2.2
- Page 29 and 30: 2. POWER QUALITY Mustafa İNCİ 2.2
- Page 31 and 32: 2. POWER QUALITY Mustafa İNCİ •
- Page 34 and 35: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 36 and 37: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 38 and 39: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 42 and 43: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 44 and 45: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 46: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 49 and 50: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 51: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 55 and 56: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 58: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 61 and 62: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 63: 3. FUNDAMENTALS OF DVR Mustafa İNC
- Page 66 and 67: 4. MODELING OF PROPOSED DVR Mustafa
- Page 68 and 69: 4. MODELING OF PROPOSED DVR Mustafa
- Page 70 and 71: 4. MODELING OF PROPOSED DVR Mustafa
- Page 72 and 73: 4. MODELING OF PROPOSED DVR Mustafa
- Page 74 and 75: 4. MODELING OF PROPOSED DVR Mustafa
- Page 76 and 77: 4. MODELING OF PROPOSED DVR Mustafa
- Page 78 and 79: 4. MODELING OF PROPOSED DVR Mustafa
- Page 81 and 82: 4. MODELING OF PROPOSED DVR Mustafa
- Page 83 and 84: 4. MODELING OF PROPOSED DVR Mustafa
- Page 85 and 86: 4. MODELING OF PROPOSED DVR Mustafa
- Page 88 and 89: 4. MODELING OF PROPOSED DVR Mustafa
- Page 90 and 91: 4. MODELING OF PROPOSED DVR Mustafa
- Page 92: 4. MODELING OF PROPOSED DVR Mustafa
- Page 95 and 96: 4. MODELING OF PROPOSED DVR Mustafa
- Page 97 and 98: 4. MODELING OF PROPOSED DVR Mustafa
- Page 100 and 101: 4. MODELING OF PROPOSED DVR Mustafa
3. FUNDAMENTALS <strong>OF</strong> DVR Mustafa İNCİ<br />
If the distribution circuit is weak there is need to inject small compensation<br />
voltage to operate correctly. During short circuit operation, the injected voltages and<br />
magnetic fluxes are virtually zero thereby full load current pass through the primary.<br />
The DVR will be most of the time in normal mode operation. During standby mode<br />
normal operation), the short circuit impedance of the injection transformer<br />
determines the voltage drop across the DVR (Teke, 2005).<br />
3.3.2.3. Injection Mode<br />
The primary function of Dynamic Voltage Restorer is compensating voltage<br />
disturbances on distribution system. To achieve compensation, three single-phase ac<br />
voltages are injected in series with required magnitude, phase and wave shape. The<br />
types of voltage sags, load conditions and power rating of DVR will determine the<br />
possibility of compensating voltage sag (Teke, 2005).<br />
3.3.3. Voltage Injection Strategies<br />
The way in which the dynamic voltage restorer (DVR) is used during the<br />
voltage injection mode depends upon several limiting factors such as: DVR power<br />
rating, load conditions, and voltage-sag type. For example, some loads are sensitive<br />
to phase-angel jumps, some others are sensitive to a change in voltage magnitude and<br />
some others are tolerant to all these disturbances. Therefore the control strategies to<br />
be applied depend upon the load characteristics (Shazly et al., 2013). There are four<br />
different methods of DVR voltage injection strategies:<br />
• Pre-sag compensation<br />
• In-phase compensation<br />
• In-phase advanced compensation<br />
33