5. SIMULATION RESULTS <strong>AND</strong> CASE STUDIES Mustafa İNCİ<br />

Table 5.8. Comparison and RMS values of phase voltages in open loop and close<br />

loop control method<br />

RMS Values Of Phase Voltages<br />

Fault Type Open Loop Closed Loop<br />

Va Vb Vc Va Vb Vc<br />

Single Phase Fault 6.35 6.35 6.17 6.35 6.35 6.35<br />

Two Phase Fault 6.15 6.15 6.35 6.32 6.32 6.35<br />

Three Phase Fault 6.1 6.075 6.08 6.27 6.26 6.25<br />

As it is seen from simulation results, closed loop shows better performance<br />

than open loop control method. Also, simulation results show the effectiveness of<br />

closed loop control method against open loop method. It is clear that injected voltage<br />

in close loop has more sinusoidal shape than injected voltage than open loop. Closed<br />

loop regulate the output voltage and keeps it constant at the side where a nonlinear<br />

load is connected.<br />