5. SIMULATION RESULTS <strong>AND</strong> CASE STUDIES Mustafa İNCİ<br />
Table 5.7. Sag inception and finish time for three methods<br />
Voltage Sag (Phase A) Inception Finish Result<br />
EPLL 0.3028 s 0.4046 s Medium<br />
SRF 0.3012 s 0.4019 s Fast<br />
SogiPLL 0.3039 s 0.4055 s Slow<br />
It is shown Table 5.7, SRF is the best way to detect voltage sag and swell<br />
compared to EPLL and SOGIPLL. Although EPLL and SogiPLL extract the phase<br />
information compared to SRF, SRF is more superior than EPLL and SOGIPLL due<br />
to its speed and accuracy. However, It is clear that EPLL and SOGIPLL have more<br />
oscillatory than SRF as shown in Figure 5.2 (c).<br />
Figure 5.3 and Figure 5.4 show injected voltages and load-side voltages by<br />
using three sag detection methods.<br />
Figure 5.3. Injected voltages by using three sag detection methods<br />
87