5. SIMULATION RESULTS <strong>AND</strong> CASE STUDIES Mustafa İNCİ<br />

Simulation parameters used in PSCAD/EMTDC are given in Table 5.1.<br />

Parameters of system, load, diode clamped multilevel inverter and dc-dc converter<br />

injection transformer are presented in Table 5.2-6, respectively.<br />

Table 5.1. PSCAD/EMTDC Simulation Parameters<br />

PSCAD/EMTDC Parameters<br />

Solution Time Step 20 µs<br />

Channel Plot Step 20 µs<br />

Duration of Simulation Run<br />

2 s<br />

Table 5.2. System Parameters<br />

System Parameters<br />

Fundamental Frequency<br />

Voltage Source (V S1 )<br />

Impedance of Feeder-I (R S1 + j2πL S1 )<br />

Short Circuit Powers of Feeder-I<br />

50 Hz<br />

11 kV (L-L, rms), phase angle 0 o<br />

0.000001 + j0.037699 Ω<br />

1500 MVA<br />

Table 5.3. Simulated Load Parameters<br />

Load Parameters<br />

Nonlinear/Sensitive Load (L1)<br />

A three-phase diode rectifier that supplies a load<br />

of 100 + j125.66 Ω, 710 kVA, pf = 0.983,<br />

THD=5.1 %<br />

Table 5.4. Simulation parameters of Voltage Source Inverter<br />

DVR (VSI)<br />

Compensation Rating 30%<br />

Filter inductor (L f )<br />

1.5 mH<br />

Filter Capacitor (C f ) 150 µF<br />

Filter Resistance (R f )<br />

Power Rating<br />

0.05 Ω<br />

1230 kVA<br />