R<br />

D.C. AMPS<br />

A.C. AMPS<br />

MEDIA TEMPERATURE LIMITS<br />

125V 250V 480V 600V<br />

TEMPERATURE INDICATING AND<br />

F<br />

C<br />

SWITCH NUMBER<br />

ADJUSTABLE RANGE<br />

6V 12V 24V 125V 250V<br />

0<br />

50 F 100<br />

C<br />

TYPE 4<br />

50<br />

TEMP<br />

SW<br />

NELSON HEAT TRACING SYSTEMS SPECIFICATION / APPLICATION<br />

<strong>TA4X140</strong> THERMOSTAT<br />

INSTALLATION<br />

DESCRIPTION<br />

ENCLOSURE<br />

Die Cast Aluminum<br />

CLASSIFICATIONS<br />

NEMA Type 4X IP66<br />

TEMPERATURE RANGE<br />

Range<br />

-9 to 60°C (15 to 140°F)<br />

CAPILLARY<br />

Length Material Max. Bulb Temperature<br />

N/A Stainless Steel 71°C (160°F)<br />

ELECTRICAL DATA<br />

CSA Rating<br />

UL Rating<br />

22 amp resistance 480 VAC 22 amp resistance 480 VAC<br />

CALIBRATION ACCURACY<br />

1.1°C (2°F)<br />

SWITCH TYPE<br />

Single Pole Double Throw<br />

These thermostats are used for ambient temperature<br />

control in ordinary or corrosive locations.<br />

OUTLINE<br />

124mm (4.9")<br />

114mm (4.5")<br />

26mm (3")<br />

102mm (4")<br />

10mm (.38")<br />

203mm (8")<br />

102mm (4")<br />

114mm (4.5")<br />

REGULATING EQUIPMENT.<br />

LISTED 266T<br />

142mm (5.6")<br />

29mm (0.16")<br />

20mm (.81")<br />

Annual Maintenance:<br />

1. Remove Cover.<br />

2. Lubricate dial stem and spray a coat of lubricant and rust preventative such as CRC Stor & Lube,<br />

electrical grade, on the thermostat body.<br />

3. Replace Cover.<br />

Approvals:<br />

General Locations<br />

UL - E89748 CSA - LR701949 CE<br />

P.O. BOX 726 • TULSA, OK 74101 • TEL 918-627-5530 • FAX 918-641-7336 • www.nelsonheaters.com<br />

GA-1990 Rev. 3<br />

August, 2005


NELSON HEAT TRACING SYSTEMS SPECIFICATION / APPLICATION<br />

<strong>TA4X140</strong> THERMOSTAT<br />

INSTALLATION<br />

INSTALLATION<br />

Junction Box<br />

Sensing Bulb<br />

Conduit to<br />

<strong>Thermostat</strong><br />

Stand-off<br />

<strong>Thermostat</strong><br />

Power Supply<br />

MI Cold Section<br />

Pipe Clamps<br />

Method for installing LT, HLT,<br />

CLT and NC heater cable types.<br />

Low Point Drain<br />

Pipe<br />

WIRING DIAGRAM<br />

DIRECT CONTROL<br />

LOW TEMP. ALARM<br />

Phase<br />

C<br />

Phase<br />

C<br />

NO<br />

NO<br />

Heater<br />

NC<br />

Alarm<br />

(low temperature)<br />

NC<br />

Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's website<br />

at www.nelsonheaters.com.<br />

P.O. BOX 726 • TULSA, OK 74101 • TEL 918-627-5530 • FAX 918-641-7336 • www.nelsonheaters.com<br />

GA-1990 Rev. 3<br />

August, 2005

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!